Section 4
1MAC050144-MB C
Protection functions
118
615 series ANSI
Technical Manual
Figure 48:
Functionality of numerical multiple-stage overcurrent protection
The coordination plan is an effective tool to study the operation of time selective operation
characteristics. All the points mentioned earlier, required to define the overcurrent
protection parameters, can be expressed simultaneously in a coordination plan. In Figure
49, the coordination plan shows an example of operation characteristics in the LV-side
incoming feeder and radial outgoing feeder.