Device description
Connections
Environmental conditions - mechanical
100 m/s², 16 ms
1000 shocks per direction
IEC 60255-21-2 class 1
Emission test
Radiated emissions - enclosure ports (30 Mhz
to 1 GHz), CISPR 16-2-3/ EN 55016-2-3
EN 55022/ CISPR 22 class A
Immunity test
61000-4-2
8 kV air / 6 kV contact (level 3), criterion A
Radiated radio-frequency electromagnetic
field, IEC
61000-4-3
10 V/m (level 3), criterion A
Radiated radio-frequency electromagnetic
field, IEC
61000-4-3
80 MHz to 1 GHz: 20 V/m (level x), criterion A
1 GHz to 2.7 GHz: 10 V/m (level 3), criterion A
Power frequency magnetic field,
61000-4-8
100 A/m (level 5), criterion A
Impulse magnetic field, IEC
61000-4-9
300 A/m (level 4), criterion A
4.5
Connections
4.5.1
Power connector (X1)
The EDS500 devices are equipped with a wide range power supply for voltages between 24
and 60 Volts DC (power consumption see device label). The connector is a 3-pin Phoenix plug
with screw terminals.
The power lead has to be sufficiently fused and a manual interrupter for the power supply
has to be installed (emergency switch). For the full effect of the overvoltage protection the
functional earthing has to be connected and the hat rail has to be earthed.
The installation has to comply with national installation standards. An external, optional
power supply can be used for connection to 230 VAC.
Power supply input (X1)
Operating voltage
-15%...+20%
Power consumption (typical)
specific for device, see device label
Current demand (peak)
specific for device, see device label
Plug type
Phoenix Contact MSTBT 2.5/3-ST
Reverse polarity protection
yes
Circuit classification
ES2 (acc. to IEC 62368-1)
Galvanic isolation
1.5 kV isolation voltage
Overvoltage protection
±4 kV line to earth, ±2 kV line to line
Electrical fast transient / Burst, IEC
61000-4-4 4 kV (level 4), criterion A
Surge 1.2/50 µs, IEC
61000-4-5
4 kV line to earth, 2 kV line to line (level 4), cri-
terion A
Conducted, common mode disturbances
in the frequency range 0 Hz to 150 kHz,
61000-4-16
30 V continuous disturbance/ 300 V short
duration disturbance (level 4), criterion A
1KGT151042
V000 1