IT
10
2CSYD0201B
Figure 8
1)
Set the detector sensitivity (L = low, M = medium, H = high) with the proper
selector.
2)
Set the DIP switch of the detector (see the following table).
3)
Set the DIP switch 1 of the detector to ON (test mode).
4)
Lay the front cover back on the device and walk in the area to be protected
to check if the detector signals possible intrusion attempts (the front LED
turns on). If there are no signals, try to adjust the detection area again or to
increase the sensitivity. Check if it works with the DomusLink3 control unit
(please read the installation and user manuals related to the control unit for
details about the detector test procedure).
5)
Remove the front cover of the detector, set the DIP switch 1 to OFF
(standard operation), lay the cover back on the device and fix it with the
screw.
Switch
Function
1
ON
Test mode.
OFF *
Standard operation.
2
ON
Suppression: only one alarm every 5 seconds is
generated even if multiple detections occurred (the
battery duration is reduced).
OFF *
Idem, but every 120 seconds.
3
ON *
N.O. Contact (do not change)
OFF
N.C. Contact (do not change)
4
ON
Active LED (it turns on for each detection during the
standard operation).
OFF *
Inactive LED.
5
ON *
Anti-masking activated. The detector issues an hazard
signal after having detected a masking condition for
more than 3 minutes.
OFF
Antimasking deactivated.
* Factory configuration
IMPORTANT
: if the anti-masking function is activated, when you refit the front cover,
the detector starts the self-recognition phase that lasts 1 minute.