ABB 266HSH Operating Instructions Manual Download Page 25

2600T Series Pressure transmitters | 

OI/266/LowP-EN Rev.A   25

10 Maintenance

10 Maintenance

If transmitters are used as intended under normal operating 
conditions, no maintenance is required. It is sufficient to check 
the output signal at regular intervals (in accordance with the 
operating conditions), as described in the instructions in the 
section “Operation resp. Configuration of the transmitter”. If 
deposits are expected to accumulate, the measuring equipment 
should be cleaned on a regular basis, in accordance with the 
operating conditions. Cleaning should ideally be carried out in a 
workshop. Repair and maintenance activities may only be 
performed by authorized customer service personnel. When 
replacing or repairing individual components, original spare parts 
must be used.

Attention – Potential damage to parts.

 The electronic 

components of the printed circuit board can be damaged by static 
electricity (observe ESD guidelines). Make sure that the static 
electricity in your body is discharged when touching electronic 
components. If a remote seal is mounted on the measuring 
equipment, it must not be removed (please refer to the dedicated 
document).

Warning – <Bodily injury>.

 Explosion-proof transmitters must be 

either repaired by the manufacturer or approved by a certified 
expert following repair work. Observe the relevant safety 
precautions before, during and after repair work. Only disassemble 
the transmitter to the extent necessary for cleaning, inspection, 
repairs, and replacement of damaged components.

10.1 Returns and removal

Defective transmitters sent to the repairs department must, 
wherever possible, be accompanied by your own description 
of the fault and its underlying cause.

Warning – General risks.

 Before removing or disassembling the 

device, check for hazardous process conditions such as pressure 
on the device, high temperatures, aggressive or toxic media, and 
so on. Read the instructions in the sections “Safety” and “Electrical 
connection”, and perform the steps outlined there in reverse order.

10.2 Pressure transmitter sensor

Essentially maintenance is not required for the transmitter sensor. 
Anyway the following items should be checked periodically:

  — Check the integrity of the pressure boundary (no cracks  

 

    should be visible on the process connection or on the  

 

    process flanges.

  — Check that there is no leakage from the sensor or from the    
    vent/drain valve.

In case one of the check points above fails, please replace the 
damaged part with an original spare part. Please contact your 
local ABB office for spare parts support information or refer to 
the spare part list. The use of non-original spare parts makes the 
warranty void. In case you want ABB to perform the repair, 
please send back the transmitter to your local ABB office 
complete with the return form that you find in this manual 
appendix and include it with the device.

Attention – Potential damage to parts.

 Do not use sharp or 

pointed tools. Do not damage the insolating diaphragms.

10.3 Pressure transducer replacement

If the pressure transducer needs to be replaced proceed as 
follows:

  1.   Insulate the transmitter from the process by acting on the    
   

manifolds or on the insulation valves

  2.   Open the vent valves to allow sensor depressurization

  3.   Disconnect the power supply and disconnect the wiring

  4.   Disconnect the transmitter from the bracket unscrewing the  
   

fixing bolts.

  5.   Open the communication board/HMI compartment cover

  6.   The communication board is connected to the sensor via a  
   

flat cable and a connector. Remove the communication    

   

board and gently disconnect the connector

  7.   Release the tang screw completely and rotate the housing   
   

until its complete removal

  8.  The 266 can reconfigure itself with the previous configured  
   

parameters thanks to the auto-configuration functionality.

  9.  Before powering on the transmitter raise dip-switches 1 and  
   

2 in up position. Connect the transmitter to power supply,   

   

wait ten seconds and lower dip-switched 1 and 2.

  10. After installing the transmitter on the bracket and   

 

   

connecting it to the manifold, perform a PV zero bias.

10.4 Electronic replacement

If the electronic module needs to be replaced proceed as follows:

  1.   Insulate the transmitter from the process by acting on the    
   

manifolds or on the insulation valves.

  2.   Open the vent valves to allow sensor depressurization.

  3.   Power the transmitter off by disconnecting the wiring.

  4.   Open the windowed cover and gently remove the electronic  
   

module with integrated LCD by acting on the removal slots  

   

placed on the external part of the module itself (see picture  

   

below). This operation shall be carried out very carefully by   

   

using a dedicated removing tool or a thin, flat screwdriver.

  5.  Gently disconnect the sensor flat cable from the rear of the  
   

electronic module.

  6.  Connect the sensor flat cable to the new electronic module  
   

with dip switch 1 in up position.

  7.  Connect the transmitter to power supply, wait ten seconds  
   

and lower dip-switch 1 to 0 position. 266 can reconfigure    

   

itself with the previous configured parameters thanks to the  

   

auto-configuration functionality. 

Figure 14: Slot for electronic module removal 

Summary of Contents for 266HSH

Page 1: ...2600T Series Pressure Transmitters 266HSH Model Low Power Consumption 1 5 V DC Operating Instruction OI 266 LowP EN Rev A Engineered solutions for all applications Measurement Made Easy...

Page 2: ...ns As a part of ABB a world leader in process automation technology we offer customers application expertise service and support worldwide We are committed to teamwork high quality manufacturing advan...

Page 3: ...dard instruments 13 6 Transmitter wiring 14 6 1 Cable connection 14 6 2 Analogue output HART transmitter wiring 14 6 3 Supply requirement 15 6 4 Wiring procedure 15 6 5 Grounding 16 6 6 Surge protecto...

Page 4: ...g from the receipt of the transmitter and its identification passing to the installation to the electrical connections to the configuration and to the troubleshooting and maintenance operations 1 2 Mo...

Page 5: ...se of adequate safety systems For safety reasons ABB draws your attention to the fact that only sufficiently insulated tools conforming to DIN EN 60900 may be used Since the transmitter may form part...

Page 6: ...EE Directive 2002 96 EC or corresponding national laws e g the ElektroG Electrical and Electronic Equipment Act in Germany Dispose of the product solution directly at a specialist recycling facility d...

Page 7: ...2600T Series Pressure transmitters OI 266 LowP EN Rev A 7 3 Transmitter overview 3 Transmitter overview 3 1 Transmitter components overview Figure 1 Gauge pressure transmitter components...

Page 8: ...nsor The lowest value of the measured value that the transmitter can be adjusted to measure URV Upper Range Value The highest value of the measured value to which the transmitter is calibrated LRV Low...

Page 9: ...ctronics housing as standard Option I2 allows to select these plates as metal AISI 316 ss fastened to the electronics housing with rivets or screws The instrument may be used as a pressure accessory c...

Page 10: ...bodies including water 6 means that the housing is protected against water specifically powerful jets of water under standardized conditions 7 means that the housing is protected against water specif...

Page 11: ...pressure on the measuring diaphragm resulting in a zero shift In such an event the zero point can be corrected via the set PV to zero command Please refer to the configuration section for further det...

Page 12: ...71 16 0 63 108 4 25 52 2 05 27 1 06 width across flats Figure 7 Model 266HSH with 1 2 14 NPT male process connection and barrel housing installed on a 2 pipe with optional bracket B6 carbon steel or B...

Page 13: ...ipes must be as short as possible and free from sharp bends Lay the impulse piping in such a way that no deposits accumulate in them Gradients should not be less than approx 8 ascending or descending...

Page 14: ...out Voltmeter 1 2 5 4 3 6 HART hand held communicator may be connected or between the terminals Vout COMM and PWR or at the terminal blocks of the voltmeter Figure 10 HART transmitter connection schem...

Page 15: ...overs when power is applied to the unit Run the cable through the cable gland and the open port Connect the POWER supply the positive lead to the PWR terminal and the negative lead to the PWR terminal...

Page 16: ...d is direct connection to earth ground with impedance equal or less of 5 ohm Figure 11 Ground connection on transmitter housing 6 6 Surge protector equipped terminal block optional The pressure transm...

Page 17: ...on the sums of the capacitances and inductances of all circuits including the transmitter see EC type examination certificate must be equal to or less than the permissible capacitances and inductances...

Page 18: ...ly the pressure for the lower range value and upper range value to the measuring equipment Make sure that the measuring limits are not exceeded Important Reducing station with adjustable pressure and...

Page 19: ...Select Select submenu parameter Edit Edit parameter Ok Save selected parameter and display stored parameter value 8 6 HMI as feedback of the local push button operations As consequence of the operati...

Page 20: ...selections are available Linear Custom Linearization Curve Cylindrical Lying Tank and Spherical Tank This submenu allows user to set the display view One or two lines with our without bargraph are the...

Page 21: ...is High 5 4V on 1 position the output is Low 0 94V Write lock switch 4 If the user wants to protect the configuration from unauthorized writing dip switch 4 has to be moved up in 1 position 8 9 Dampi...

Page 22: ...herical tank The transmitter calculates the volume from the measured filling level 8 11 Configuration with the PC or HHT The 266 transmitters can be configured by either one of the following device Ha...

Page 23: ...ed error messages Error message Tx LCD message Possible cause Suggested action Tx response F120 016 Sensor Invalid The sensor signal is not being updated correctly as a result of an electronics failur...

Page 24: ...and process conditions has to be checked A different transmitter type could be required no effect F102 004 P dP Out Of Limits The measurement range has not been correctly calculated OR an incorrect t...

Page 25: ...part with an original spare part Please contact your local ABB office for spare parts support information or refer to the spare part list The use of non original spare parts makes the warranty void I...

Page 26: ...FM Approvals for the following Class Divisions and Gas groups hazardous classified locations temperature class and types of protection Explosionproof US for Class I Division 1 Groups A B C and D hazar...

Page 27: ...N DANGEROUS FLUIDS In case of toxic or otherwise dangerous fluid please attach the relevant Material Safety Data Sheet Trouble found during Installation Commissioning Maintenance At start up On servic...

Page 28: ...dismantle without any special precautions Material s which have been in contact with this equipment C If A or B are not applicable full instructions for the safe handling of this equipment for dispos...

Page 29: ...2600T Series Pressure transmitters OI 266 LowP EN Rev A 29 Intentionally blank...

Page 30: ...30 OI 266 LowP EN Rev A 2600T Series Pressure transmitters Intentionally blank...

Page 31: ...level transmitters ABB s portfolio of device management Fieldbus and wireless solutions Scalable asset device management Asset vision software Mobility handhelds Customer support We provide a comprehe...

Page 32: ...us Note We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not acc...

Reviews: