ABB 266HSH Operating Instructions Manual Download Page 18

18   OI/266/LowP-EN Rev.A 

| 2600T Series Pressure transmitters

8 Operation

8 Operation

8.1 Factory settings 

Transmitters are calibrated at the factory to the customer’s 
specified measuring range. The calibrated range is provided on 
the name plate whereas the tag number on the additional tag 
plate. The calibrated range and tag number are provided on the 
name plate. If this data has not been specified, the transmitter 
will be delivered with the following configuration: 

Parameter

Factory setting

Lower Range Value (LRV) (1V)

Zero

Upper Range Value (URV) (5V)

Upper Range Limit (URL)

Output transfer function

Linear

Damping

1 second

Transmitter failure (alarm)

Upscale (5.4V)

Optional LCD HMI scale

1 line PV

Important.

 Every configurable parameters listed here above can 

easily be modified with an HART handheld terminal running proper 
EDD file. Information regarding materials, filling liquid type, etc. is 
stored inside the non-volatile memory of the device. 

8.2 Configuration types

Pressure transmitters can be configured as follows:

  — Configuration of the parameters for the lower and upper   
    range values via LCD keys.

  — Configuration with a handheld terminal

8.3 Configuring the transmitter with LCD keys

The “lower range value” and “span” parameters can be set 
directly on the transmitter using the LCD keys.

The transmitter has been calibrated by the manufacturer based 
on the order information. The tag plate contains information on 
the “lower range value” and “upper range value” set. In general, 
the following applies:

The first pressure value (e.g., 0 mbar) is always assigned to the 
1V signal (or 0%), while the second pressure value (e.g., 400 
mbar) is always assigned to the 5V signal (or 100%). To change 
the transmitter ranging apply the pressure for the “lower range 
value” and “upper range value” to the measuring equipment. 
Make sure that the measuring limits are not exceeded.

Important.

 Reducing station with adjustable pressure and 

reference displays can be used as pressure generators. 

When making the connection, please ensure that there are no 
residual fluids (for gaseous testing materials) or air bubbles (for fluid 
testing materials) in the impulse lines, since these can lead to errors 
during inspection. Any potential measuring error for the pressure 
generator should be at least three times smaller than the desired 
measuring error for the transmitter. It is recommended that the 
damping is set to 1 second.

8.4 LRV and URV configuration (1 ... 5 V ranging)

  — Apply the lower range value for pressure (1 V) from the    
    process or from a pressure generator. The pressure must  
    be stable and applied with a high level of accuracy  

 

    << 0.05 % (observing the set damping value).

  — Remove instrument windowed cover.

  — Press “Z” LCD key for two seconds to set the output  

 

    signal to 1 V. Operator will be asked about proceeding    
    with the operation in progress. By depressing “Yes” a  

 

    small screwdriver icon will appear on the bottom of the    
    LCD. A confirmation string (“Oper Done”) will be shown on  
    device main screen on button release (for additional string  
    messages, refer to section ”8.6 HMI as feedback of the    
    local push button operations”). The span will remain  

 

   unchanged.

  — Apply the pressure for the “upper range value” and wait    
    approx. 30 s until it has stabilized.

  — Press “S” LCD key to set the output current to 5V and  

 

    adjust the Span. As described above, operator will be  

 

    asked about proceeding with the operation in progress. A  
    confirmation message will be shown at the end of Span    
   adjustment. 

  — Record the new settings. The respective parameter will be  
    stored in the non-volatile memory 20 seconds after the    
    confirmation has been given.

Figure 12: Operating with the display keypad

Summary of Contents for 266HSH

Page 1: ...2600T Series Pressure Transmitters 266HSH Model Low Power Consumption 1 5 V DC Operating Instruction OI 266 LowP EN Rev A Engineered solutions for all applications Measurement Made Easy...

Page 2: ...ns As a part of ABB a world leader in process automation technology we offer customers application expertise service and support worldwide We are committed to teamwork high quality manufacturing advan...

Page 3: ...dard instruments 13 6 Transmitter wiring 14 6 1 Cable connection 14 6 2 Analogue output HART transmitter wiring 14 6 3 Supply requirement 15 6 4 Wiring procedure 15 6 5 Grounding 16 6 6 Surge protecto...

Page 4: ...g from the receipt of the transmitter and its identification passing to the installation to the electrical connections to the configuration and to the troubleshooting and maintenance operations 1 2 Mo...

Page 5: ...se of adequate safety systems For safety reasons ABB draws your attention to the fact that only sufficiently insulated tools conforming to DIN EN 60900 may be used Since the transmitter may form part...

Page 6: ...EE Directive 2002 96 EC or corresponding national laws e g the ElektroG Electrical and Electronic Equipment Act in Germany Dispose of the product solution directly at a specialist recycling facility d...

Page 7: ...2600T Series Pressure transmitters OI 266 LowP EN Rev A 7 3 Transmitter overview 3 Transmitter overview 3 1 Transmitter components overview Figure 1 Gauge pressure transmitter components...

Page 8: ...nsor The lowest value of the measured value that the transmitter can be adjusted to measure URV Upper Range Value The highest value of the measured value to which the transmitter is calibrated LRV Low...

Page 9: ...ctronics housing as standard Option I2 allows to select these plates as metal AISI 316 ss fastened to the electronics housing with rivets or screws The instrument may be used as a pressure accessory c...

Page 10: ...bodies including water 6 means that the housing is protected against water specifically powerful jets of water under standardized conditions 7 means that the housing is protected against water specif...

Page 11: ...pressure on the measuring diaphragm resulting in a zero shift In such an event the zero point can be corrected via the set PV to zero command Please refer to the configuration section for further det...

Page 12: ...71 16 0 63 108 4 25 52 2 05 27 1 06 width across flats Figure 7 Model 266HSH with 1 2 14 NPT male process connection and barrel housing installed on a 2 pipe with optional bracket B6 carbon steel or B...

Page 13: ...ipes must be as short as possible and free from sharp bends Lay the impulse piping in such a way that no deposits accumulate in them Gradients should not be less than approx 8 ascending or descending...

Page 14: ...out Voltmeter 1 2 5 4 3 6 HART hand held communicator may be connected or between the terminals Vout COMM and PWR or at the terminal blocks of the voltmeter Figure 10 HART transmitter connection schem...

Page 15: ...overs when power is applied to the unit Run the cable through the cable gland and the open port Connect the POWER supply the positive lead to the PWR terminal and the negative lead to the PWR terminal...

Page 16: ...d is direct connection to earth ground with impedance equal or less of 5 ohm Figure 11 Ground connection on transmitter housing 6 6 Surge protector equipped terminal block optional The pressure transm...

Page 17: ...on the sums of the capacitances and inductances of all circuits including the transmitter see EC type examination certificate must be equal to or less than the permissible capacitances and inductances...

Page 18: ...ly the pressure for the lower range value and upper range value to the measuring equipment Make sure that the measuring limits are not exceeded Important Reducing station with adjustable pressure and...

Page 19: ...Select Select submenu parameter Edit Edit parameter Ok Save selected parameter and display stored parameter value 8 6 HMI as feedback of the local push button operations As consequence of the operati...

Page 20: ...selections are available Linear Custom Linearization Curve Cylindrical Lying Tank and Spherical Tank This submenu allows user to set the display view One or two lines with our without bargraph are the...

Page 21: ...is High 5 4V on 1 position the output is Low 0 94V Write lock switch 4 If the user wants to protect the configuration from unauthorized writing dip switch 4 has to be moved up in 1 position 8 9 Dampi...

Page 22: ...herical tank The transmitter calculates the volume from the measured filling level 8 11 Configuration with the PC or HHT The 266 transmitters can be configured by either one of the following device Ha...

Page 23: ...ed error messages Error message Tx LCD message Possible cause Suggested action Tx response F120 016 Sensor Invalid The sensor signal is not being updated correctly as a result of an electronics failur...

Page 24: ...and process conditions has to be checked A different transmitter type could be required no effect F102 004 P dP Out Of Limits The measurement range has not been correctly calculated OR an incorrect t...

Page 25: ...part with an original spare part Please contact your local ABB office for spare parts support information or refer to the spare part list The use of non original spare parts makes the warranty void I...

Page 26: ...FM Approvals for the following Class Divisions and Gas groups hazardous classified locations temperature class and types of protection Explosionproof US for Class I Division 1 Groups A B C and D hazar...

Page 27: ...N DANGEROUS FLUIDS In case of toxic or otherwise dangerous fluid please attach the relevant Material Safety Data Sheet Trouble found during Installation Commissioning Maintenance At start up On servic...

Page 28: ...dismantle without any special precautions Material s which have been in contact with this equipment C If A or B are not applicable full instructions for the safe handling of this equipment for dispos...

Page 29: ...2600T Series Pressure transmitters OI 266 LowP EN Rev A 29 Intentionally blank...

Page 30: ...30 OI 266 LowP EN Rev A 2600T Series Pressure transmitters Intentionally blank...

Page 31: ...level transmitters ABB s portfolio of device management Fieldbus and wireless solutions Scalable asset device management Asset vision software Mobility handhelds Customer support We provide a comprehe...

Page 32: ...us Note We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not acc...

Reviews: