Technical
data
IM/265D/V-EN-02 265Dx,
265VS
67
Pos: 23.1 /Überschriften/1/S - U/Technische Daten @ 0\mod_1132904574837_3101.doc @ 3169
10 Technical data
Pos: 23.2 /Überschriften/1.1/2-spaltig/D - F/Funktionale Spezifikation @ 1\mod_1148976354843_3101.doc @ 27494
10.1 Functional specifications
Pos: 23.3 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828
Change from one to two columns
Pos: 23.4 /Technische Daten / Datenblatt/Druck/Druckmessumformer/265Dx, 265Vx/Messbereich und Messspannengrenzwerte @ 5\mod_1164182285812_3101.doc @ 49207
Measured variable
265Dx
: Differential pressure, vacuum pressure, gauge pressure
265Vx
: Absolute
pressure
Measuring range and span limits
Minimum span
Sensor
code
Upper
range limit
(URL)
Lower range
limit (LRL)
265Dx
265Vx
A
1 kPa
10 mbar
4 in H
2
O
-1 kPa
-10 mbar
-4 in H
2
O
0.05 kPa
0.5 mbar
0.2 in H
2
O
C
6 kPa
60 mbar
24 in H
2
O
-6 kPa
-60 mbar
-24 in H
2
O
0.2 kPa
2 mbar
0.8 in H
2
O
F
40 kPa
400 mbar
160 in H
2
O
-40 kPa
-400 mbar
-160 in H
2
O
0.4 kPa
4 mbar
1.6 in H
2
O
2 kPa
20 mbar
15 mm Hg
L
250 kPa
2,500 mbar
1,000 in H
2
O
-250 kPa
-2,500 mbar
-1,000 in H
2
O
2.5 kPa
25 mbar
10 in H
2
O
12.5 kPa
125 mbar
93.76 mm Hg
N
2,000 kPa
20 bar
290 psi
-2,000 kPa
-20 bar
-290 psi
20 kPa
0.2 bar
2.9 psi
100 kPa
1 bar
14.5 psi
R
10,000 kPa
100 bar
1,450 psi
-10,000 kPa
-100 bar
-1,450 psi
100 kPa
1 bar
14.5 psi
Important
The lower range limit (LRL) for 265Vx is absolute 0 for all
measuring ranges.
Span limits
Maximum span = URL = Upper range limit
265Dx
Linear/freely programmable characteristic:
Within the range
limits, may be adjusted up to ± upper
range limit
Sample setting: -400 ... 400 mbar
Square root characteristic: Sample setting: 0 ... 400 mbar
(Recommendation for square root function:
At least 10 % of upper range limit
(URL)).
265Vx
Linear/freely programmable characteristic: Sample
setting:
0 … 400 mbar abs.
To optimize performance characteristics, it is recommended that you
select the transmitter sensor with the lowest turndown ratio.
Zero suppression and elevation
(265Vx: Zero suppression only)
The zero position and span can be set to any value within the range
limits listed in the table if:
- Set
span
≥
minimum span
Damping
Adjustable time constant: 0 … 60 s
This is in addition to the sensor response time.
Second sensor for absolute pressure measurement (
265Dx)
Measuring range: 41 MPa, 410 bar, 5,945 psi
(0.6 MPa, 6 bar, 87 psi for sensor code A)
Warm-up period
According to technical data, ready for operation in
≤
2.5 s after
switching on the transmitter, with minimum damping.
Insulation resistance
> 100 M
Ω
at 500 VDC (between terminals and ground)