Mounting position
The devices have to be mounted horizontally with the input terminals on the bottom. In order to ensure a sufficient
convection, the minimum distance to other modules should not be less than 15 mm (0.59 in) in vertical and 25 mm (0.98 in)
horizontal direction.
2CDC 272 001 F0012
IN
OUT
Electrical connection
+, -
Output voltage
SH Shield
L, N Input voltage
o
Protective earth
Preparations:
– Connect to mains according to the specific national regulations.
– Power supply cables and unit must be sufficiently fused. A disconnecting device has to be provided for the power supply
to disengage unit and supply cables from supply mains if required.
– We recommend to choose the cable section as large as possible in order to minimize voltage drops.
– In order to ensure sufficient air-cooling the distance to other devices has to be considered.
Instructions:
1. Connect the input terminals L and N.
2. Connect the protective earth conductor to terminal
o
(protection class I).
3. Provide a suitable disconnecting device (e.g. line protection switch) in the supply line acc. to IEC/EN 60950-1.
4. Rate the lines for the maximum output current (considering the short-circuit current) or provide a separate fuse protection.
The input side is protected by an internal input fuse.
5. Observe the polarity.
Connect the ‘shield’ terminal on the AS-i power supply to the machine ground so that the AS-i system is symmetrically
operated against this machine ground. This improves noise sensitivity in case of symmetrical interference on the AS-i cable.
The device is overload, short-circuit and open-circuit proof. The secondary side of the power supply unit is electrically
isolated from the input.
2CDC272003F0012
SH
_
_
+
+
N
L
o
PWM
SH
L
+
N
o