Operating Instructions
7
CP650, CP660, CP675
Technical Specifications
Parameter
Value
Back-up battery
3V 50mAh Lithium, rechargeable, not user-replaceable, PANASONIC model VL2330
Fuse
Automatic
Environmental Conditions
Parameter
Value
According to
Operating temperature (vertical installation)
0
°C … +50 °C
EN 60068-2-14
Storage temperature
-20
°C … +70 °C
EN 60068-2-14
Operating and storage humidity
5
% … 85 % RH not-condensing
EN 60068-2-30
Vibrations
5
Hz … 9 Hz, 7 mm
p-p
9
Hz … 150 Hz, 1 g
EN 60068-2-6
Shock
± 50 g, 11 ms, 3 pulses per axis
EN 60068-2-27
Protection class
IP66 front panel *
EN 60529
Touchscreen technology
Resistive
-
Touchscreen reliability
> 1 million operations
-
*) The front face of the Control Panel unit, installed in a solid panel, has been tested using conditions
equivalent to the standards shown
in the table above. Even though the Control Panel unit‟s level of re-
sistance is equivalent to these standards, oils that should have no effect on the Control Panel can possi-
bly harm the unit. This can occur in areas where either vaporized oils are present, or where low viscosity
cutting oil are allowed to adhere to the unit for long periods of time. If the Control Panel‟s front face pro-
tection sheet becomes peeled off, these conditions can lead to the ingress of oil into the Control Panel
and separate protection measures are suggested.
Also, if non-approved oils are present, it may cause deformation or corrosion of the front face. Therefore,
prior to installing the Control Panel be sure to confirm the type of conditions that will be present in the
Control Pa
nel‟s operating environment.
If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the
panel, the original level of the protection cannot be guaranteed. To maintain the original protection level,
be sure to replace the installation gasket regularly.