Advant Controller AC 31 / Issued: 01.99
3 – 23
Technical specifications
3
Voltage output ± 10 V:
1 LSB = 10 V/2
11
= 4.88 mV
with minimum value (step 8)
32767
V
10
value
PLC
V
in
output
Voltage
×
=
Current output 0-20 mA:
1 LSB = 20 mA/2
12
= 4.88 µA with minimum value (step 8)
32767
mA
20
value
PLC
mA
in
output
Current
×
=
Current output 4-20 mA:
Resolution is equal to 0-20 mA
32767
mA
20
value
PLC
mA
in
output
Current
×
=
A PLC value <0 generates a constant current of 4 mA.
3.6.5
Hardware configuration, switches on left side of analog extension
XM 06 B5
The configuration current or voltage depends upon a DIP switch in the side of the extension.
One dip switch for one channel.
Switch 1
Channel 0
OFF
⇒
Voltage
ON
⇒
Current
Switch 2
Channel 1
OFF
⇒
Voltage
ON
⇒
Current
Switch 3
Channel 2
OFF
⇒
Voltage
ON
⇒
Current
Switch 4
Channel 3
OFF
⇒
Voltage
ON
⇒
Current
The configuration PT100 or PT1000 is set with switch 5 of the DIP switch:
it controls all channels.
Switch 5
Channels 0 to 3
OFF
⇒
PT1000
ON
⇒
PT100
⇒
Configuration of value ranges: see 3.6.6 on page 3–24.
XE 08 B5
The configuration current or voltage depends upon a DIP switch in the side of the extension.
One dip switch for one channel.
Switch 1
Channel 0
OFF
⇒
Voltage
ON
⇒
Current
Switch 2
Channel 1
OFF
⇒
Voltage
ON
⇒
Current
Switch 3
Channel 2
OFF
⇒
Voltage
ON
⇒
Current
Switch 4
Channel 3
OFF
⇒
Voltage
ON
⇒
Current
Switch 7
Channel 4
OFF
⇒
Voltage
ON
⇒
Current
Switch 8
Channel 5
OFF
⇒
Voltage
ON
⇒
Current
Switch 9
Channel 6
OFF
⇒
Voltage
ON
⇒
Current
Switch 10
Channel 7
OFF
⇒
Voltage
ON
⇒
Current
Summary of Contents for 07CR41
Page 6: ...Contents 4 Advant Controller AC 31 Issued 08 99 3 ...
Page 62: ...Installation 4 14 Advant Controller AC 31 Issued 08 99 3 Figure 22 Extension XK 08 F1 l ...
Page 94: ...Programming 5 22 Advant Controller AC 31 Issued 01 99 3 ...
Page 110: ...Communication 6 16 Advant Controller AC 31 Issued 01 99 3 ...
Page 122: ...Appendix A 4 Advant Controller AC 31 Issued 08 99 3 ...
Page 123: ......