Chapter 17
Configuration
Manual Corrigo Ventilation, revision R
Alarm text
The alarm text that should be shown in the display when there is an alarm can be changed using E
tool
©
. For more information, see the E tool
©
manual.
Alarm list
The alarm text and priority columns show the factory set values.
Alarm text
Pri Description
1
Run Error Supply Air Fan
B
Malfunction Supply air fan
2
Run Error Extract Air Fan
B
Malfunction Extract air fan
3
Run Error P1-Heater
B
Malfunction pump, Heating circuit
4
Run Error P1-Cooler
B
Malfunction pump, Cooling circuit
5
Run Error P1-Exchanger
B
Malfunction pump, Liquid connected
exchanger
6
Filter guard
B
Filter guard pressure switch activated
7
Flow switch
B
Flow switch activated
8
External frost guard
A
External Frost protection thermostat
activated
9
Deicing pressure guard
-
Exchanger de-icing pressure switch
activated
10
Fire alarm
A
Fire alarm activated
11
External switch
C
"External switch" activated
12
External alarm
B
External alarm activated
13
Supply Air control error
B
Supply air temp deviates too much from the
setpoint for too long.
14
Humidity control error
-
The room humidity deviates too much from
the setpoint.
15
High supply air temp
B
Supply air temp too high
16
Low supply air temp
B
Supply air temp too low
17
Supply air temp max
-
Maximum limiting of supply air temp active
18
Supply air temp min
-
Minimum limiting of supply air temp active
19
High room temp
B
Room temp too high during room temp
control
20
Low room temp
B
Room temp too low during room temp
control
21
High extract air temp
B
High extract air temp during extract air
control
22
Low extract air temp
B
Low extract air temp during extract air
control
23
Electric heating is overheated A
Heater high temperature limit switch
activated
24
Frost risk
B
Frost protection function is overriding the
control of the heater output
25
Low frostguard temp
A
Frost protection temperature below frost
limit value
26
Low efficiency
B
Heat exchanger efficiency below limit value
27
Sensor error Outdoor temp
B
Malfunction of connected sensor
28
Analogue de-icing
-
Exchanger de-icing activated by de-icing
sensor
29
Rotation guard exchanger
B
Exchanger rotation sentinel alarm activated