Integrated Access Controller –
Installation manual
AAT SYSTEMY BEZPIECZEŃSTWA Sp. z o.o.
All rights reserved.
11
Users Operation & Reset to Factory Default
Open the door: Read the valid user card/Input the valid PIN on the keypad,
the door will open.
Remove Alarm: Read the valid user card/Input the valid PIN on the keypad
or Input Master Code #
To reset to factory default
, power off, press the Exit Button, hold it and pow-
er on, there will be two beeps, and the LED light turns into yellow, release the
exit button, then read any two 125KHz EM card or HID card, the LED will turn
into red, means reset to factory default successfully. Of the two cards reading,
the 1
st
one is Master Add Card, the 2
nd
one is the Master Delete Card.
Remarks:
-
If
no
Master
Cards
added,
must
press
the
Exit
Button
for
at
least
10
seconds
before
release
-
Reset to factory default, the user
’
s information is still retained.
Access controller mode
In this mode unit works as controller. This is factory default mode
(command
8 0 #
).
It
’
s possible to connect additional reader for two way control.
To change unit for Wiegand reader mode please use command:
8 1 #
(this mode
is describe on next pages) .
Attention
: Install a 1N4004 or equivalent diode is needed when use
a common power supply, or the reader might be damaged. (1N4004
is included in the packing)
KDH
-
KZ330U/H/M
GND
+12V
D0
D1
Reader