AAT KaDe KDH-KZ2000-IP-U Installation Manual Download Page 10

Integrated Access Controller  –

 

Installation manual 

 

10

 

                                                                    AAT SYSTEMY BEZPIECZEŃSTWA Sp. z o.o.

 

                                                             All rights reserved.

 

 

 

5. Programming controller in standalone mode

 

 

 

Controller KDH

-

KZ2000

-

IP

-

U_M can be operated in stand

-

alone mode or 

network under the supervisory software KaDe Premium Plus II installed on your 

computer.

 

Working in stand

-

alone mode (without communication with the supervisor soft-

ware on the PC) must be programmed using the controller's built

-

in keypad. 

There is no in this mode the possibility to monitor the system "on

-

line" and gen-

erate reports. Cards added in this mode works without any time limit. This mode 

is recommended for the control a few doors with a small number of users.

 

It is also possible operation of the controller in the "off

-

line" after being pro-

grammed by supervisory software with controller connecting using TCP port.

 

Programming procedure using the keyboard controller

 

Signalling functions:

 

• 

audible alarm (buzzer)

 

• 

Single long sound 

-

 the operation succeeded or enter the menu

 

• 

Triple sound 

-

 the operation was not successful

 

• 

Quad sound 

-

 at the selected position is already stored card

 

• 

Triple sound 

-

 card with this number is already added

 

• 

Optical indicator (LED)

 

• 

Red LED 

-

 Power on

 

• 

Blue LED 

-

 confirmation of the validity of the operation

 

• 

Green LED / steady light 

-

 programming mode

 

 

5. 1 The procedure for entry into the programming mode:

 

• 

Press * 

 

• 

Enter the master code (default "000000")

 

• 

Green LED should light up permanently

 

If no password is entered correctly within 20 seconds after pressing * it auto-

matically returns to normal. Even after entering the programming mode, no key-

pad operation for 20 seconds to exit the programming mode. After entering the 

programming mode, you can make only one type of operation. To perform the 

next operation re

-

enter the programming mode.

 

 

Notes: 

Default admin code 

000000

 must be change after first enter into pro-

gramming mode for own using 

41

 command code. Leave default code allows un-

authorized persons enter into programming mode and add own card. Reset ad-

min password is available from KaDe Premium Plus II software 

-

 > Controller 

setup 

-

> Context menu/Initialize. New password should be download to the con-

troller.

 

 

Procedure exited from programming mode:

 

(After programming)

 

• 

Press # 

-

 a single sound, red LED light.

 

Summary of Contents for KaDe KDH-KZ2000-IP-U

Page 1: ...SYSTEMY BEZPIECZE STWA Sp z o o All rights reserved 1 Installation Manual INTEGRATED ACCESS CONTROLLER KDH KZ2000 IP U KDH KZ2000 IP M VERSION 1 0 Installation Manual INTEGRATED ACCESS CONTROLLER KDH...

Page 2: ...STWA Sp z o o All rights reserved 1 Introduction 3 2 Controller technical data 4 3 Controller wiring diagram 6 4 Controller installation 9 5 Management in standalone mode 10 6 Programming codes table...

Page 3: ...can use for two way control Recom mended supply power type AWZ 200 plus 7Ah battery It s possibility to set one from four identification mode Card only default mode PIN only Card or PIN Card PIN KZ 1...

Page 4: ...P For additional module connection RS485 for future used Readers and Cards Integrated reader For UNIQUE card read range 5 10 cm U For MIFARE card red range 2 5 cm M External for two way control 26 U 3...

Page 5: ...nnectors 12V 110 mA Lock control relay output Alarm relay output Bell control output from keypad key LED located on front panel upper left light in RED as supply power indicator Blue access granted li...

Page 6: ...der SW Purple Door contact AN Gray Exit button ALM Yellow PIR sensor input 485 Black RS485 port signal 485 Red RS485 port signal 12V Black Controller supply power 12 VDC 12V Black Supply power for ext...

Page 7: ...2NC Black 2C Red 2NO White 1NC Yellow 1C Orange 1NO Green Electric lock connection NO type Electric lock VDC D0 Green D1 White BUZ Blue SW Purple AN Gray ALM Yellow 485 Black 485 Red J6 connector 8 p...

Page 8: ...tric lock Sound alarm KDH KZ2000 IP U_M controller RS485 For future use Alarm sensor Exit button Door Status sensor Reader KaDe Premium Plus II supervisor software Buzzer Battery Tamper Administrator...

Page 9: ...and one in the middle for the cables 2 Attach the back cover of the controller to the wall Place the plugs from the wires in the appropriate sockets and drag them to the other side of the wall 3 Mount...

Page 10: ...ion was not successful Quad sound at the selected position is already stored card Triple sound card with this number is already added Optical indicator LED Red LED Power on Blue LED confirmation of th...

Page 11: ...ters of the exit button After entering the programming mode enter the code 141 then 01 code for the NO type button normally open Default setting 00 code for the NC type button normally closed After en...

Page 12: ...dalone or network Before adding users it is recommended that the admin istrator has created a list of users with assigned four digit ID code This makes it easier to add new users later and in particul...

Page 13: ...list or Close deleting card to the reader After you read the card controller will generate a single beep and automatically exits the programming mode 7 1 Removal of all users After entering the progr...

Page 14: ...s Alarm action delay Alarm relay output 161 01 type NO 00 type NC 162 00 99 sec 0 sec default 163 1 RL1 2 RL2 3 RL1 2 4 no out Access mode setup Card only 221 Card PIN 222 PIN only 223 Card or PIN 224...

Page 15: ...hat the minimum distance from cables and high voltage devices and other devices that generate elec trical noise was 2 m The minimum distance from telephone lines should be 1 m and from 8 m transmittin...

Page 16: ...Integrated Access Controller Installation manual 16 AAT SYSTEMY BEZPIECZE STWA Sp z o o All rights reserved...

Page 17: ...l AAT SYSTEMY BEZPIECZE STWA Sp z o o All rights reserved 1 Kontroler zintegrowany Instrukcja instalacji AAT Holding S A Wszelkie prawa zastrze one Instrukcja instalacji KONTROLER ZINTEGROWANY KDH KZ2...

Page 18: ...rmacje wst pne 3 2 Dane techniczne kontrolera 4 3 Schemat blokowy pod czenia akcesori w do kontrolera 6 4 Monta kontrolera 9 5 Programowanie kontrolera w trybie autonomicznym 10 6 Tabela kod w program...

Page 19: ...y r wnie czytnik z klawiatur Kontroler wraz z czytnikiem z klawiatur oferuje 4 tryby identyfikacji u ytkownika karta PIN karta lub PIN karta PIN Ka dy u ytkownik mo e mie sw j indywidulany kod PIN r w...

Page 20: ...rzysz o ci Czytniki i karty zintegrowany w urz dzeniu Na karty UNIQUE zasi g 5 15 cm U Na karty MIFARE zasi g 2 5 cm M dodatkowy Zgodny z 26 U 34 M bit Wiegand format kart ISO UNIQUE 125 kHz MIFARE CL...

Page 21: ...ie przeka nikowe do sterowania sygnalizatorem alarmowym wyj cie do sterowania dzwonkiem z przycisku na klawiaturze Dioda LED na panelu przednim lewy g rny r g wieci w kolorze Czerwonym w czone zasilan...

Page 22: ...cisk wyj cia ALM ty Linia dozorowa czujki PIR 485 Czarny RS485 port sygna 485 Czerwony RS485 port sygna 12V Czarny Zasilanie kontrolera 12 VDC 12V Czarny Zasilanie czytnika zew 12 VDC 12V Czerwony Zas...

Page 23: ...y 1NC ty 1C Pomara 1NO Zielony Pod czenie zamka elektrycznego typu NO rygiel rewersyjny lub zwora Zamek elektryczny VDC D0 Zielony D1 Bia y BUZ Niebieski SW Fioletowy AN Szary ALM ty 485 Czarny 485 C...

Page 24: ...oler KDH KZ2000 IP U_M RS485 Do przysz ych zastosowa Czujka PIR Przycisk wyj cia Czujnik stanu drzwi Czytnik Program nadzorczy KaDe Premium Plus II Sygnalizator akustyczny Bateria Czujnik sabota owy R...

Page 25: ...jeden na rodku pod kable 2 Zamocuj tyln ciank kontrolera do cia ny Umie wtyczki od przewod w w odpowied nich gniazdach i przeci gnij je na drug stron ciany 3 Zamontuj modu kontrolera na tylnej cian ce...

Page 26: ...orowej przycisku wyj cia Po wej ciu w tryb programowania wprowadzi kod 141 nast pnie kod 01 dla przycisku typu NO normalnie otwarty ustawienie domy l kod 00 dla przycisku typu NC normalnie zamkni ty P...

Page 27: ...k na wybranej pozycji jest ju zapisana karta sygnalizator optyczny diody LED czerwony zasilanie w czone niebieski potwierdzenie wa no ci operacji zielony tryb programowania 5 1 Procedura wej cia w try...

Page 28: ...unikn prowadzenia podw jnej ewidencji kart i utrud nie zwi zanych z dwoma bazami danych kart zaleca si w praktyce u ywanie tylko jednego trybu pracy kontrolera autonomicznego lub sieciowego Przed przy...

Page 29: ...do czytnika Po odczytanej karcie kontroler wygeneruje pojedynczy sygna akustyczny i auto matycznie wyjdzie z trybu programowania 7 1 Usuni cie wszystkich u ytkownik w Po wej ciu w tryb programowania...

Page 30: ...typ NO 00 typ NC 162 00 99 sekund 0s domy l 163 1 PK1 2 PK2 3 PK1 i 2 4 brak Tryby identyfikacji u ytkownika Tylko karta 221 Karta PIN 222 Tylko kod PIN 223 Karta lub kod PIN 224 Zarz dzanie u ytkowni...

Page 31: ...odle g o od kabli i urz dze wysokiego napi cia oraz innych urz dze generu j cych zak cenia elektryczne wynosi a 2 m Minimalna odleg o od linii te lefonicznych powinna wynosi 1 m a od urz dze nadawczy...

Page 32: ...rc w prowadzonego przez S d Rejonowy dla m st Warszawy w Warszawie XIII Wydzia Gospodarczy Krajowego Rejestru S dowego pod numerem KRS 0000838329 kapita zak adowy wp acony w ca o ci w wysoko ci 5 000...

Reviews: