Due to the gradual introduction of European
Chimney Standards chimneys will be specified
according to their performance designation as
defined in BS EN 1443 that covers the General
Requirements for chimneys. The minimum
performance designation required for use with solid
fuel burning stoves is T450 N2 S D3.

The flue and chimney installation must be carefully
checked by a competent person before fitting the
stove to ensure it is suitable and will work safely.

If the chimney is old (i.e. built of brick or stone
without a liner) or being opened up for reuse
additional checks and smoke testing as described in
Appendix E of the Approved Document J 2002
Edition should also be carried out to ensure the flue
and chimney are in good operating condition.

Unless the existing flue is in good condition with
suitable access for collection and removal of debris.
If the flue size is more than 225mm (9 inches)
diameter or 200 x 200mm square, a suitable lining of
150mm (6 inches) diameter should be fitted, or if the
flue length is over 5.5 metres one size larger than the
appliance outlet should be fitted. This should be a
double skin stainless steel flexible flue liner that is
independently certified for use with solid fuel.
Details of suitable linings for use with solid fuel are
given in the Official HETAS guide that can be
viewed on their website at www.hetas.co.uk

It is also important that suitable flue pipe
complying with the Building Regulations is used to
connect the stove to the flue in the chimney and that
suitable access is provided into the flue for regular
inspection and sweeping of the flueways.

The installer should comply with the Building
Regulation requirements in respect of providing a
Notice Plate giving details on the chimney, flue
lining, hearth and fireplace installation. Approved
Document J of the Building Regulations for
England and Wales is available from:
The Stationery Bookshops and can also be 
viewed at the ODPM website at
www.safety.odpm.gov.uk/bregs/brads.htm

Details on the relevant Building Regulations and
BS British Standards are given in the "General

Precautions" section page 16 of these instructions.
A chimney may comply with the regulations but
still be subject to down draught and similar
problems. A chimney terminating above the ridge
level is generally less likely to suffer such
problems.

Chimneys should be as straight as possible.
Horizontal runs should be avoided except where
the rear outlet of the appliance is used, in which
case the horizontal section should not exceed
150mm (6'') in length.

If the fire appears to be working hard but produces
very little output to the room it is likely that
excessive draw is present in the chimney, and that
heat is being sucked out of the appliance and up the
chimney. If this is the case we recommend the
fitting of a draught stabiliser in preference to a flue
damper, in the interest of safety and efficiency.

We do not recommend the use of a damper when
burning solid fuel.

FOR ALL APPLIANCES

Access for cleaning the flue should be incorporated
in the system other than through the appliance (e.g.
a soot door or access through register plate).
Purpose-made soot doors and inspection lengths
are available from manufacturers of all systems.

Ensure that the whole length of the flue can be
reached from the soot door.

Note: if the appliance is fitted with a draught
stabiliser or if one is fitted to the flue pipe or
chimney in the same room as the appliance, then
the permanent air entry opening (or openings)
should be increased by 300mm

2

for each kW of

rated output.

For advice on flues and chimneys contact;
NACE (National Association of Chimney
Engineer): telephone 0800 0924019
www.nace.org.uk
or
NACS (National Association of Chimney
Sweeps): telephone 01785 811732
www.chimneyworks.co.uk

20

Nouveau 7 Multifuel Stoves

INSTALLATION

Summary of Contents for Nouveau 7

Page 1: ...Nouveau 7 Multifuel Stove Operating Installation Manual PLEASE RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Nouveau 7 Multifuel Stove Rev 2 August 2004 AFS1120...

Page 2: ...confident in the reliability of our product that we offer a Lifetime Guarantee Should you have any questions about our Nouveau Multifuel Stoves that are not covered in this manual please contact the...

Page 3: ...ire 11 Over Firing 13 Cleaning Annual Maintenance 13 14 Accessories 15 INSTALLATION Page General Precautions 16 Handling 16 Hearth 16 Combustible Materials 16 Firebox Liner Panels 17 Throat Plate Insp...

Page 4: ...E BURNED IN THIS APPLIANCE TO USE THESE FUELS WILL INVALIDATE THE APPLIANCE GUARANTEE IF IN DOUBT CONTACT THE SOLID FUEL ASSOCIATION TELEPHONE NUMBER 0800 600 000 www solidfuel co uk THE USE OF SPARE...

Page 5: ...rly installed and operated a house fire may result installation must comply with the Building Regulations and conform to all relevant fire safety standards Arada Ltd produce a variety of appliances ra...

Page 6: ...HECK LIST Part Description Visual Aid not to scale Nouveau 7 Multifuel 1 Grate Bars 5 2 Fuel Retainers 2 3 Throat Plate 1 4 Flue Spigot 1 5 5 Hot Plate 1 5 6 Ashpan 1 7 Operating Tool 1 8 Rear Liners...

Page 7: ...DATA Nouveau 7 Multifuel Room Heater with Domestic Hot Water with add in boiler type 1 2 Max Output to Room kW Max Output to Water kW 4 4 3 2 6 4 Height mm 620 Width mm 476 Depth mm 365 Height to Cent...

Page 8: ...ating the door knob if hot with operating tool anti clockwise to increase the the air inlet clockwise to reduce the air inlet or seal the ash door completely AARROW AIRWASH SYSTEM The air wash has an...

Page 9: ...e tool which is used for riddling and setting multifuel grate position and for emptying the ash pan Fig 4 Fig 4 RIDDLING Use the operating tool for setting the grate in the coal burning position or th...

Page 10: ...feet supplied Care should be taken whilst assembling the feet so as not to damage the painted surface of the fire The feet are positioned in each corner of the fire and fixed using the washers and scr...

Page 11: ...reheat Blazebrite Taybrite Sunbrite Doubles Singles Anthracite Large Nuts and Welsh Dry Steam Coal Large Small Nuts Approval does not cover the use of other fuels either alone or mixed with the suitab...

Page 12: ...he area is well ventilated during this time OVERNIGHT BURNING The appliance will bur overnight provided Sufficient fuel is placed in the firebox The controls are set correctly Excess draught is not pr...

Page 13: ...and could easily start a fire or cause an injury Replace the ash pan and close ash door Close the fire down CLINKER The formation of clinker suggests that the unit is being over fired Any clinker for...

Page 14: ...shut down period DOOR GLASS The door glass should remain clear during normal daytimeburning Howeverundercertainconditions such as burning at a low rate with damp wood or overnight burning the glass m...

Page 15: ...erchangeable canopy Fig 7 Remove the front clamps Tilt the canopy as shown in stage 1 Engage the rear clips and pull fully forward Fit the front clamps and tighten Fit the required blanking plates as...

Page 16: ...RTH The fire should be installed to stand on a constructional hearth of non combustible materials not less than 125mm 5 thick conforming to Building Regulations Dimensions of the hearth should project...

Page 17: ...to the front facing up The projecting lugs sit on top of the side liners The long centre tab on the back edge rests on the rear liners The shorter turn down tabs against the vertical face Replace the...

Page 18: ...ing end marked L onto the low section of the comb The upper bar is fitted in a similar manner but with the end marked L inserted in the rear channel and the end marked H seated on the high section of...

Page 19: ...umes from the stove outlet to the outside air To ensure a good updraught it is important that the flue gases are kept warm and that the flue size suits the stove The termination of the outlet at the t...

Page 20: ...Document J of the Building Regulations for England and Wales is available from The Stationery Bookshops and can also be viewed at the ODPM website at www safety odpm gov uk bregs brads htm Details on...

Page 21: ...Nouveau 7 Multifuel Stoves 21 INSTALLATION...

Page 22: ...ATED FLUES TYPICAL METAL INSULATED CHIMNEY SYSTEM TO BE INSTALLED TO THE CHIMNEY MANUFACTURERS INSTRUCTIONS IN COMPLIANCE WITH BUILDING REGULATIONS AND BS7566 PTS 1 4 A is minimum clearance for non in...

Page 23: ...n and calculations for individual heating systems should be carried out by a qualified heating engineer In many cases your supplier will be able to offer advice and assistance Direct Systems Stainless...

Page 24: ...om the expansion tank should be 28mm diameter copper Pipes in unheated spaces must be lagged FINAL CHECK Before handing over the installation to the customer it is strongly recommended that the applia...

Page 25: ...appliances only c If clay or concrete flue liners used confirm that they are correctly jointed with socket end uppermost and state jointing materials used d If an existing chimney has been refurbished...

Page 26: ...2 AFS1019 AFS001 AFS010 AFS008 AFS058 AFS009 2 Throat Plate 3 Grate Bar Set 4 Hot Plate 5 Operating Tool 6 Ashpan 7 Flue Spigot Part Description Visual Aid not to scale Nouveau 7 Part No Pictures show...

Page 27: ...35 AFS1077 9 Side Liner 10 Back Liner Set 11 Glass Replacement Kit Complete with Gasket 12 Glass Clips 13 Hinge kit Comprises 2 Hinges 4 Fixings Per Set 14 Airwash Part Description Visual Aid not to s...

Page 28: ...040 AFS997 16 Main Doors Assembly Complete with Handle Glass Gaskets Clips and Seal 17 Nouveau Feet Including Fixings 18 Cast Fire Door Locking Assembly 19 Aarrow Fires Gauntlet Gloves Part Descriptio...

Page 29: ...nnually by a qualified heating engineer The Manufacturers decision shall be final If your appliance proves to be defective as a result of faulty materials or workmanship during guarantee we will repai...

Page 30: ...s manual please contact your Aarrow retailer Please keep all repair receipts safely Please ensure you have this manual available when an engineer visits as they will complete the service record chart...

Page 31: ...labour incurred in its replacement Documentation must be retained and produced in the event of a warranty claim This guarantee specifically does not cover accidental damage misuse wear tear The use of...

Page 32: ...al No I ve checked it and it s O K Assembled by Checked by Date of Purchase Name and address of supplier Please ensure installer completes INSTALLATION CHECK LIST details on page 25 of this manual If...

Reviews: