53
Filter Replacement
Monthly filter inspection is required to
maintain optimum unit efficiency.
It is strongly recommended that filter media
be replaced monthly. Filters are located
upstream of the evaporator coil. Open access
panel and pull filters straight out to inspect
all of the filters. Replace filters with the size
indicated on each filter or as shown in the
tables below. Arrow on the replacement
filters must point towards the blower.
Table 10 - 23-35 tons, Pre Filters
Feature 6A
Quantity/Size
Type
0
No Pre Filters
A
9/20” x 20” x 2”
Pleated, 30% Eff, MERV 8
Table 11 - 45-70 tons, Pre Filters
Feature 6A
Quantity/Size
Type
0
No Pre Filters
A
18/20” x 20” x 2”
Pleated, 30% Eff, MERV 8
Table 12 - 23-35 tons, Unit Filters
Feature 6B
Quantity/Size
Type
0
9/20” x 20” x 2”
Pleated, 30% Eff, MERV 8
A
9/20” x 20” x 4”
Pleated, 30% Eff, MERV 8
B
9/20” x 20” x 4”
Pleated, 65% Eff, MERV 11
C
9/20” x 20” x 4”
Pleated, 85% Eff, MERV 13
D
9/20” x 20” x 4”
Pleated, 95% Eff, MERV 14
Table 13 - 45-70 tons, Unit Filters
Feature 6B
Quantity/Size
Type
0
18/20” x 20” x 2”
Pleated, 30% Eff, MERV 8
A
18/20” x 20” x 4”
Pleated, 30% Eff, MERV 8
B
18/20” x 20” x 4”
Pleated, 65% Eff, MERV 11
C
18/20” x 20” x 4”
Pleated, 85% Eff, MERV 13
D
18/20” x 20” x 4”
Pleated, 95% Eff, MERV 14
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
Summary of Contents for SA-023
Page 2: ......
Page 20: ...20 Figure 2 One Piece Single Unit Lifting Details ...
Page 21: ...21 Figure 3 Two Piece Single Unit Coil Section Lifting Details ...
Page 22: ...22 Figure 4 Two Piece Single Unit Fan Section Lifting Details ...
Page 23: ...23 Figure 5 One Piece Dual Unit Lifting Details ...
Page 24: ...24 Figure 6 Two Piece Dual Unit Coil Section Lifting Details ...
Page 25: ...25 Figure 7 Two Piece Dual Unit Fan Section Lifting Details ...
Page 28: ...28 Figure 10 Dual unit with splices after being bolted together ...
Page 63: ...63 ...