20
PREHEAT-X Technical Guide
COMM
CONFIG
COM MODE
S-ALONE
COMMUNICATIONS MODE
This setting configures the Communications Mode. The choices are
(1) BACNET, (2) EBUS, or (3) S-ALONE (default).
EBUS CFG
VCB/VCCX
E-BUS CONFIGURATION
Select the type of controller that the PREHEAT-X is connected to.
NOTE: You must cycle power after changing to apply this setting.
MAC ADDR
0
BACnet
®
- CURRENT MAC ADDRESS
Valid range is 0 to 128. Default is 0.
.
BAC ID
15000
BACnet
®
- CURRENT ID START
Range is 0 to 30000. Default is 15000.
Communication Configuration Screens
Refer to the following map when navigating through the
Communication Configuration Screens. From the COMM
CONFIG Screen, press
<ENTER>
to scroll through the screens
and change setpoints. Use the
<UP>
and
<DOWN>
arrow keys
to change your selections. Press
<ENTER>
to save any changes.
BAC BAUD
38,400
BACnet
®
- CURRENT BAUD RATE
9600, 19200, 38400, 57600, 76800. Default is 38400.
LCD SCREENS
Communication Configuration Screens