PREHEAT-X Technical Guide
Configuration Screens
Refer to the following map when navigating through the
Configuration Screens. From the CONFIG Screen, press
<ENTER>
to scroll through the screens and change setpoints. Use
the
<UP>
and
<DOWN>
arrow keys to change your selections.
Press
<ENTER>
to save any changes.
CONFIG
HEAT STG
X
# OF HEAT STAGES
Select the total number of Heat Stages including the Modulating
Stage. Range is 0-6. Default is 0.
MOD HEAT
YES
MODULATING HEAT
If either the Analog or PWM Modulating Heat output is being used,
this must be set to YES. Default is NO.
LAT CFG
AVERAGE
LEAVING AIR TEMPERATURE SENSOR CONFIGURATION
LAT1:
Use Leaving Air Temperature Sensor 1 as the Controlling Temp.
LAT2:
Use Leaving Air Temperature Sensor 2 as the Controlling Temp.
AVERAGE:
Use the Average of LAT1 & LAT2 as the Controlling Temp.
Default is AVERAGE.
AOUT VLO
X.X
MINIMUM SCR VOLTAGE
This is the Low Voltage setting for the Analog Output. It sets the
voltage level needed for 0%. Range is 0 -10. Default is 0
AOUT VHI
XX.X
MAXIMUM SCR VOLTAGE
This is the High Voltage setting for the Analog Output. It sets the
voltage level needed for 100%. Range is 0 -10. Default is 10.
STG UP
XX
STAGE UP DELAY
If configured for SCR modulation, this is the amount of time (in
seconds) the controller must wait to activate an additional stage of
heat if the Min Off Time is met. Range is 0 - 1200. Default is 180.
STG DWN
XX
STAGE DOWN DELAY
If configured for SCR modulation, This is the amount of time (in
seconds) the controller must wait to deactivate a stage of heat if the
Min Run time is met. Range is 0 - 1200. Default is 180.
MIN RUN
XX
MINIMUM RUN TIME
This is the amount of time (in seconds) a stage of heat must remain
on before it can be deactivated. Range is 0 - 1200. Default is 120.
MIN OFF
XX
MINIMUM OFF TIME
This is the amount of time (in seconds) a stage of heat must remain off
before it can be activated. Range is 0 - 1200. Default is 60.
SCALING
DEG.F
TEMPERATURE SCALE
Fahrenheit (default) or Celsius.
This setting is used only in Stand-Alone Mode.
LCD SCREENS
Configuration Screens