20
Factory Restore
- Restore option clears all
present values, restores configuration to the
defaults and restarts the controller.
(Advanced) Inputs
The Inputs menu shows all analog inputs,
their current value and any calibration
offset.
(Advanced) Limits
The Limits menu allows setting of minimum
and maximum values.
OCC MAX CLG
Occupied
maximum
cooling
space
temperature setpoint. Default is 78°F and
range is 55-92°F.
OCC MIN CLG
Occupied
minimum
cooling
space
temperature setpoint. Default is 68°F and
range is 55-90°F.
OCC MAX HTG
Occupied
maximum
heating
space
temperature setpoint. Default is 72°F and
range is 55-90°F.
OCC MIN HTG
Occupied
minimum
heating
space
temperature setpoint. Default is 65°F and
range is 53-90°F.
UNOCC MIN CLG
Unoccupied
minimum
cooling
space
temperature setpoint. Default is 68°F and
range is 55-90°F.
UNOCC MAX HTG
Unoccupied
maximum
heating
space
temperature setpoint. Default is 72°F and
range is 55-90°F.
HEAT OAT HIGH
Auxiliary heating outside air temperature
lockout. Heat pump heating will still be
available. Default is 70°F and range is 50-
150°F.
COMP OAT LOW
Compressor cooling outside air temperature
lockout. Default is 40°F and range is 0-50°F.
OAT HIGH
Description. Default is 150°F and range is
110-160°F.
OAT LOW
Description. Default is -40
°F
and range is -
50-40
°F
.
SAT HIGH
Maximum supply air temperature. Default is
200°F and range is 120-250°F. Disable all
outputs.
SAT LOW
Minimum supply air temperature. Default is
40°F and range is 32-60°F. Disable all
outputs.
MIN DGTL COMP
Minimum allowable capacity of the variable
capacity scroll compressor. Default is 50%,
range is 20-80% and value must be 5% less
than the maximum variable capacity scroll
compressor capacity setpoint.
MAX DGTL COMP
Maximum allowable capacity of the variable
capacity scroll compressor. Default is 100%
and range is 25-100% value must be 5%
greater than the minimum variable capacity
scroll compressor capacity setpoint.
COMP1 MIN OFF (SECS)
Compressor minimum off time. Default is
120 seconds and range is 120-600 seconds.
COMP1 MIN ON (SECS)
Compressor minimum on time. Default is
120 seconds and range is 0-600 seconds.
HEAT MIN OFF
Description. Default is 120 units and range
is -120-600 units.