Table 7 - Thermistor Temperature vs. Resistance Values
°C
°F
kΩ
°C
°F
kΩ
-40
-40
2889.60
75
167
12.73
-35
-31
2087.22
80
176
10.79
-30
-22
1522.20
85
185
9.20
-25
-13
1121.44
90
194
7.87
-20
-4
834.72
95
203
6.77
-15
5
627.28
100
212
5.85
-10
14
475.74
105
221
5.09
-5
23
363.99
110
230
4.45
0
32
280.82
115
239
3.87
5
41
218.41
120
248
3.35
10
50
171.17
125
257
2.92
15
59
135.14
130
266
2.58
20
68
107.44
135
275
2.28
25
77
86.00
140
284
2.02
30
86
69.28
145
293
1.80
35
95
56.16
150
302
1.59
40
104
45.81
155
311
1.39
45
113
37.58
160
320
1.25
50
122
30.99
165
329
1.12
55
131
25.68
170
338
1.01
60
140
21.40
175
347
0.92
65
149
17.91
180
356
0.83
70
158
15.07
Summary of Contents for CB-024
Page 40: ...40 Refrigerant Piping Diagrams Figure 12 A C only piping AHU above CU ...
Page 41: ...41 Figure 13 A C only piping AHU below CU ...
Page 42: ...42 Figure 14 Modulating hot gas reheat piping AHU above CU ...
Page 43: ...43 Figure 15 Modulating hot gas reheat piping AHU below CU ...
Page 44: ...44 Figure 16 Hot gas bypass piping AHU above CU ...
Page 45: ...45 Figure 17 Hot gas bypass piping AHU below CU ...
Page 46: ...46 Figure 18 Modulating hot gas reheat with hot gas bypass piping AHU above CU ...
Page 47: ...47 Figure 19 Modulating hot gas reheat with hot gas bypass piping AHU below CU ...
Page 48: ...48 Figure 20 Heat pump piping AHU above CU ...
Page 49: ...49 Figure 21 Heat pump piping AHU below CU ...
Page 50: ...50 Figure 22 Heat pump with modulating hot gas reheat piping AHU above CU ...
Page 51: ...51 Figure 23 Heat pump with modulating hot gas reheat AHU below CU ...