8.0  Data Input and Output

The SAAFShield Detecting Unit control logic interface block interprets 

the 4-20 mA signal originating in the SAAFShield Communications 

Module and produces a set of data consisting of each piece of data 

collected by the SAAFShield detecting unit. The block also has some 

failure detection capabilities. If a failure is detected the Fail bit is set 

and a fail code is populated. 

Block Diagram

SAAFShield

Communications

Module

FAL
CumCu
CumAg
IncCu
IncAg
RH
Temp
Error

In

Qui

Rst

Inputs

  Parameter Name  Type 

Description

  In 

DINT 

Physical IO Tag

  Qui 

Boolean  Signal Quality

  Rst 

Boolean  Initialize output to starting values

Notes:  

The range and unit of measure for all metal readings is 0 – 4000 angstroms. 

•   Relative Humidity is measured 0 – 100%. 

•   Temperature is measured -50 – 150º C

Pulse Codes 

   Variable 

Number  

Pulse Level 

Length 

   

of Pulses 

(raw value) 

of Time

   Start Signal 

6.28 mA or 16486 

3 seconds

   Inter-data Pulse  2 

8.58 mA or 22486 

1 second each

   Data Transfer 

N/A 

5 seconds 

Details

  Parameter Name  Type 

Description

  FAL 

Boolean  True if QUI is False

  CumCu 

DINT 

Cumulative Copper reading in angstroms

  CumAg 

DINT 

Cumulative Silver reading in angstroms

  IncCu 

DINT 

Incremental Copper reading in angstroms

  IncAg 

DINT 

Incremental Silver reading in angstroms

  RH 

Real 

Relative Humidity reading

  temp 

Real 

temperature reading

  error 

Real 

error Code

Cycle 

every 15 minutes the SAAFShield Communications Module sends data 

to the analog input (SigIn). It sends the start signal for 3 seconds, waits 

2 seconds, and then begins data transmission. each measurement  

is transmitted for 5 seconds. there is a two second wait followed by 

two inter-data pulses. Then the next measurement sequence is  

transmitted. The chart below (Figure 6) shows an example sequence. 

Note that all data transmitted is set high. When the Communications 

Module has sent all pieces of data, it waits for 15 minutes before  

beginning the cycle.

Steps

  1.  Send one 6.28 mA pulses of 3 seconds.
  2.  Wait 2 seconds.
  3.  Transmit Cumulative copper data in the range of 4-20mA  

    for 5 seconds.
  4.  Wait 2 seconds.
  5.  Send two 8.58 mA pulses of 1 second each with inter-pulse  

    pause of 1 second (set loop to 4mA during pause)
  6.  Wait 2 seconds.
  7.  Transmit Cumulative silver data in the range of 4-20mA  

    for 5 seconds.
  8.  Wait 2 seconds.
  9.  Send two 8.58 mA pulses of 1 second each with inter-pulse  

    pause of 1 second (set loop to 4mA during pause)
 10.  Wait 2 seconds.
 11.  Transmit incremental copper measurement in the range of 4-20mA  

    for 5 seconds.
 12.  Wait 2 seconds.
 13.  Send two 8.58 mA pulses of 1 second each with inter-pulse  

    pause of 1 second (set loop to 4mA during pause)
 14.  Wait 2 seconds.
 15.  Transmit incremental silver measurement in the range of 4-20mA  

    for 5 seconds.
 16.  Wait 2 seconds.
 17.  Send two 8.58 mA pulses of 1 second each with inter-pulse  

    pause of 1 second (set loop to 4mA during pause)
 18.  Wait 2 seconds.

Figure 6. 

Summary of Contents for SAAFShield

Page 1: ...e AAF International SAAFShield Communications Module These instructions must be carefully followed in order to operate the unit safely and correctly If there are any questions regarding the use or car...

Page 2: ...o read compute and transmit corrosion temperature and relative humidity data Ribbon Connector to SAAFShield DU Ribbon Connector to SAAFShield RU Connector for Power and 4 20 mA Output Menu Bottons Up...

Page 3: ...hould be placed after the final particulate filter This will protect it from the majority of particulates and allow it to monitor the condition of the outlet air When the rate of corrosion begins incr...

Page 4: ...rease the setting of that field 5 Use the OK button to select the value and scroll to the next field 6 If Exit EXT field is reached using the OK button press either UP or DOWN to exit from menu system...

Page 5: ...ading Error Real Error Code Cycle Every 15 minutes the SAAFShield Communications Module sends data to the analog input SigIn It sends the start signal for 3 seconds waits 2 seconds and then begins dat...

Page 6: ...of the Environment s Classification This will report the harshest of the classifications for the standard used 6 Transmitting 19 Transmit Relative Humidity measurement in the range of 4 20mA for 5 sec...

Page 7: ...FShield Parts List It is recommended that the following spare parts be stored at the installation site for replacement purposes Consult with your AAF representative to determine actual quantities requ...

Page 8: ...F 3 118 NOV 13 AAF has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice ISO Certified Firm 2013 AAF International The U...

Reviews: