AAF SAAFShield Installation, Operation And Maintenance Instructions Download Page 3

3

Figure 2. Typical placement for SAAFShield units.

3.0  Placement of SAAFShield Monitors

When determining the reactivity of a room or space within a building, 

the SAAFShield should be placed in a location representative of the air 

that contacts the electronics or materials being protected. If the  

protected items are spread out within the space, then an approach, 

similar to a thermostat should be used. If the protected items are 

concentrated in one area inside the space, then a location as close as 

possible to them is preferred.
When determining the condition downstream of a gas-phase filter or 

scrubber to evaluate media performance and life, the SAAFShield 

should be placed after the final particulate filter. This will protect it from 

the majority of particulates and allow it to monitor the condition of the 

outlet air. When the rate of corrosion begins increasing beyond what is 

normal, it is time to change the media or filter.

4.0  Connecting to SAAFShield Detecting Unit

The SAAFShield Detecting Unit and Communications Module come 

equipped with 26-pin ribbon cable connectors. To connect the CM to 

the DU, first remove the CM cover and locate the ribbon cable connec-

tor at the top of the CM circuit board. (Figure 3)

SAAF™ Side 

Access Housing

SAAFShield

®

 Detect-

ing Unit

SAAFShield

®

  

Reading Unit

(for periodic data 

SAAFShield

®

  

Communications Module

(for continuous  

data transmission)

Computer Room Air 

Conditioning Unit 

(CRAC)

SAAF™  

Recirculation Unit

SAAF™ Deep  

Bed Scrubber

SAAF™  

Pressurization and

Recirculation Unit

Figure 3. 

Summary of Contents for SAAFShield

Page 1: ...e AAF International SAAFShield Communications Module These instructions must be carefully followed in order to operate the unit safely and correctly If there are any questions regarding the use or car...

Page 2: ...o read compute and transmit corrosion temperature and relative humidity data Ribbon Connector to SAAFShield DU Ribbon Connector to SAAFShield RU Connector for Power and 4 20 mA Output Menu Bottons Up...

Page 3: ...hould be placed after the final particulate filter This will protect it from the majority of particulates and allow it to monitor the condition of the outlet air When the rate of corrosion begins incr...

Page 4: ...rease the setting of that field 5 Use the OK button to select the value and scroll to the next field 6 If Exit EXT field is reached using the OK button press either UP or DOWN to exit from menu system...

Page 5: ...ading Error Real Error Code Cycle Every 15 minutes the SAAFShield Communications Module sends data to the analog input SigIn It sends the start signal for 3 seconds waits 2 seconds and then begins dat...

Page 6: ...of the Environment s Classification This will report the harshest of the classifications for the standard used 6 Transmitting 19 Transmit Relative Humidity measurement in the range of 4 20mA for 5 sec...

Page 7: ...FShield Parts List It is recommended that the following spare parts be stored at the installation site for replacement purposes Consult with your AAF representative to determine actual quantities requ...

Page 8: ...F 3 118 NOV 13 AAF has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice ISO Certified Firm 2013 AAF International The U...