AAF HermanNelson IM 725 Installation Manual Download Page 7

IM 725 (1-02)

7

Installing Louvers

Typical Installation Methods

If the fresh air opening has not yet been made, see figures 5 through
12 for the recommended locations and the job-specific plans for the
exact location. Follow local codes.

Cut the wall opening so that it is slightly larger than the louver being
installed. For dimensions, see Table 1. If the opening is already there,
measure to be sure there is a minimum of 3/8" (9mm) clearance around
all sides. For masonry installations, a lintel must be installed above all
louvers.

In thick wall applications, the portion of the wall between the louver
and the unit is the outside air plenum. Line this plenum area with 3/8"
(9 mm) mortar or other suitable material. In some applications, the job
specifications require a metal sleeve connection between the louver
and the unit. If using such a sleeve, properly caulk it to ensure a
weather-tight seal. This is critical in preventing freeze-ups, cold
drafts, and air infiltration. Be sure the wall is smooth, square, and
provides a suitable mating surface.

See figure 13. Before setting the louver, construct a sloping, sealed
cement mortar base to drain unwanted moisture to the outside. Be sure
the mortar base is 1" (25mm) thick at the unit and tapers toward the
louver. The mortar at the unit also acts as a backing against which the
open cell gasket of the unit itself can seal. This is critical in preventing
water leaks and air leaks under the unit. Be sure the sealed cement
mortar base is smooth and flush with the interior wall.
If it is not possible to construct a sloping mortar base, then field-
supplied flashing is required. See figure 14. The flashing should

terminate flush with the exterior of the building. Place a bead of caulk
under the flashing to prevent moisture from wicking back to the unit.
Do not caulk the joint between the louver and the flashing. This joint
is designed to let unwanted moisture escape.

Personal injury hazard. Avoid contact with 

sharp edges

.

See figures 5 through 12. Before setting the louver, be sure the drain
lip  or weep holes are at the bottom, and the bird screen is towards the
unit. See figures 3 and  4. Place a heavy bead of caulk along the top and
the two vertical sides of the louver, leaving the bottom uncaulked so
that if moisture gets into the area between the louver and the unit, it can
drain to the outside, unrestricted.

If the louver is supplied with flanges, (see figure 4) place an additional
bead of caulk on the inside of the top and side flanges that come in
contact with the building facade. Do not caulk the bottom flange. Place
the louver in the opening and push it tight against the supplied
building, fastening it to the exterior of the building using fasteners (by
others) appropriate to the installation. Seal the top and sides with a
waterproof caulk to make it weather-tight. Do not caulk the bottom of
the louver; doing so might trap unwanted moisture behind the flange.
(See figure 16)

If the louver is supplied with no flanges, (see figure 3) place the louver
in the opening so that it is recessed a minimum 1/16" (2mm) beyond
the building facade or as directed in the architectural plans. If specified
in the plans, secure the louver in the wall using mechanical fasteners
(supplied by others) appropriate to the installation. (See figure 15 for
suggested fastening). With the louver solidly in place, run a bead of
caulk around the perimeter of the louver to seal it weather-tight. Do not
plug the weep holes (horizontal louver) or the drip line (vertical
louver). This might restrict the flow of unwanted moisture to the
outside (see figure 16)
See figure 14. If flashing was used instead of the sloping mortar base,
caulk the flashing where it meets the inside of the opening between the
louver and the unit. This helps prevent moisture from getting under the
flashing and into the room.

CAUTION

!

Louver

No
Caulk

Unit Gasket

Wall

Unit

1" (25mm)

Floor

Caulk
(By
Others)

Flashing
(By
Others)

Figure 14 - Typical Louver Installation with Flashing

Unit Gasket

Sealed Cement
Mortar;
Pitch Away
From Unit

Floor

Wall

Unit

Louver

No
Caulk

1" (25mm)

Figure 13 - Typical Louver Installation with Sloping Sealed Cement Mortar
Base

Table 1 - Recommended Wall Openings For Wall Louvers (for figures 18 - 20)

R e c o m m e n d e d

Maximum Number of

VentiMatic

Wall Openings

VentiMatic Shutters

Shutter(s)

B

C

For Wall Louvers

Which Can Be Mounted Air Capacity

On Standard Louver

M a x i m u m

L e n g t h

H e i g h t 24" Shutter 36" Shutter

c f m

L / s

2 4 "

2 7 "

24

5

8

"

10

7

8

"

(610)

(659)

(613)

(267)

1

0

5 0 0

2 3 6

3 6 "

3 9 "

36

5

8

"

10

7

8

"

(914)

(991)

(918)

(267)

0

1

7 5 0

3 5 4

4 8 "

5 1 "

48

5

8

"

10

7

8

"

(1219) (1295) (1222)

(267)

2

0

1000

4 7 2

6 0 "

6 3 "

60

5

8

"

10

7

8

"

(1524) (1600) (1527)

(267)

1

1

1250

5 9 0

7 2 "

7 5 "

72

5

8

"

19

7

8

"

(1829) (1905) (1832)

(495)

0

2

1500

7 0 8

Summary of Contents for HermanNelson IM 725

Page 1: ...al Ceiling Models AHF AHB AHV and AHR Before beginning installation please read this publication in its entirety Develop a thorough understanding before starting the installation procedure This manual...

Page 2: ...instructions plus the job specific AAF HermanNelson submittal drawings provided for specific dimensions unit arrangements controls and electrical details pipe stub up locations etc Pre Installation C...

Page 3: ...Caulking Materials Bird Screen Sealed Cement Mortar Pitched Away from Unit Toward Louver 1 Minimum Vertical or Horizontal Blade Wall Intake Louver Recessed Without Flange Horizontal Blade Shown Lintel...

Page 4: ...ge Without Grille Louver drain lip Grille Louver with weep hole Vertical Blade Louver Horizontal Blade Louver Flange Flange Outside Air Outside Air Outside Air Bird Screen On Side Toward Unit Vertical...

Page 5: ...sing Arrangement AV or AL With Accessory Closed Pipe Tunnel Piping Floor Line Lintel By Others Intake Louver Not Less Than 3 Not More Than 28 Insulated Closure Plate Accessory Provide Drainage 1 25mm...

Page 6: ...t required Lintel By Others Piping Floor Line Sealed Cement Mortar Pitch Away From Unit Important Gasket sealing surface is required see figure 13 14 on page 7 Seal under unit required Louver Lintel B...

Page 7: ...ing the bottom uncaulked so that if moisture gets into the area between the louver and the unit it can drain to the outside unrestricted If the louver is supplied with flanges see figure 4 place an ad...

Page 8: ...hod for fastening louver without flange inside wall opening Figure 18 Louver Details Dimensions As Directed By Architect 3 4 19mm Approx 7 178mm Cement Mortar Steel Interior Wall Grille Optional See N...

Page 9: ...refusing to honor a damage claim The form required to file such a claim will be supplied by the carrier CONCEALED LOSS OR DAMAGE Concealed loss or damage means loss or damage which does not become app...

Page 10: ...ting One Coil E LH Heating RH Cooling F RH Heating LH Cooling G RH Electric Heating LH Cooling R LH Single Coil S RH Single Coil 9 Controls 15 MicroTech w Unit Mounted Sensor 16 Part Load Variable Air...

Page 11: ...8 203mm 8 203mm Knockout Opening Between Pipe Tunnel End Compartment Rear Entry Area or Draftstop Opening Knockouts 30 762mm 61 2 165mm 1 25mm 7 178mm 1 25mm 10 254mm 231 2 597mm Outdoor Air Intake O...

Page 12: ...onstruction and the washers provided in the brown envelope with these instructions figure 25 Envelope also contains allen wrench to provide access to unit Push the unit ventilator tight to the wall st...

Page 13: ...all water piping to coils properly can result in improper unit operation and possible coil freeze ups Proper ventilation is required for brazing When brazing be sure to protect unit ventilator compone...

Page 14: ...turn R H Connections L H Connections R H Connections R H Connections 133 4 349 mm Table 4 Heating Only Coil Position Combinations In Air Stream one coil per position Note X indicates Available Face an...

Page 15: ...D E F U 1 2 3 4 Figure 38 Chilled Water and Hot Water Unit Cooling Coils S W V 5 6 7 Heating Coils 65 66 67 Figure 39 Chilled Water and Steam Unit Cooling Coils S W V 5 6 7 Heating Coils 68 69 78 79 F...

Page 16: ...g Cooling Coils V S W 5 6 7 Heating Coils 12 13 L H Connections A B S R J 115 8 295 mm 133 8 340 mm 155 8 397mm 137 8 352 mm R S E F J 137 8 352 mm 95 8 244 mm R S G E J Figure 50 Direct Expansion and...

Page 17: ...1 4 32mm 31 4 83mm 23 8 61mm 33 16 81mm X X Y Z 311 16 94mm 29 16 66mm 3 4 19mm 3 4 19mm 7 8 22mm Figure 51 2 way EOC Valve Notes 1 See label furnished on 2 way valve to determine direction of flow th...

Page 18: ...eturn Return Balancing and Shutoff Valve Shutoff Valve Supply Supply 2 way EOC Valve Unit Coil Unions A B Return Return Shutoff Valve Supply Unit Coil Union Shutoff Valve Supply 3 way EOC Valve Union...

Page 19: ...eam connections may be same end as cooling coil connections but are recommended to be opposite end to facilitate piping When using AAF MicroTech controls they must be opposite end Figure 64 Same End C...

Page 20: ...ection stub from the weight of the valve and to provide the installing contractor with maximum flexibility in making the field piping connections Refer to AAF HermanNelson factory instruction sheet sh...

Page 21: ...n Unit End Compartment 14 13 13 4 6 7 8 15 9 14 4 6 7 15 9 15 15 14 13 4 6 7 8 15 11 Figure 72 Opposite End Drain Connection 78 79 Coils Left Hand Steam Supply and Right Hand Steam Return Shown Contro...

Page 22: ...is required for brazing When brazing be sure to protect unit ventilator components from overheating damage melting insulation also damage to valves wiring electronics sensors etc During brazing bleed...

Page 23: ...essures raised coil frosting reduced see figure 79 UVfansmustcontinuetorunforsettimeperiodduringunoccupied mode after satisfaction of the space sensor dissipates residual lowevaporatorcoilsurfacetempe...

Page 24: ...d under design conditions 95 F outside air 80 F 67 F DB WB indoor air Refer to condensing unit manufacturer s guidelines Before adjusting refrigerant charge verify that the unit ventilator is operatin...

Page 25: ...eriodicfilterchangeoutprogramshould beestablished Filtersareincludedinallunits AAF HermanNelson single usefiltersarestandardonallbutelectricheatunits whichcome withpermanentwiremeshfilters Permanentwi...

Page 26: ...ded by AAF Thejunctionboxhas1 25mm and2 51mm knockouts located 10 1 2 267mm from right end of unit 3 Provide ground wire from grounding screw in switch junction box to switch ground terminal 4 Wire fi...

Page 27: ...nted sensor is specified Room air is continuously drawn through the sampling chamber to insure fastaccurateresponsetotemperaturechangeswithintheroom 6 Time Clock Accessory This device automatically cy...

Page 28: ...Right End 19 20 YEL 36 37 BRN Left End Compartment BLK WHT RED GRN ORG BLU PNK GRY First Unit ORG BLU PNK GRY Additional Unit ORG BLU PNK GRY Last Unit Attach Wires 2 Twisted Conductor Shielded Belde...

Page 29: ...int adjustment Mounting Procedure For Standard Electrical Box 1 Feed the cable from the electrical box 2 Strip 1 4 of installation from the end of wires 3 Connect wires to appropriate colored leads Se...

Page 30: ...end panel End Panel Figure 94 Install End Panels With Provided Hardware 1 End Panel Shown Fit Front Alignment Bar Into Welded Notches Permitting Alignment Of Storage Accessories With The Unit Ventilat...

Page 31: ...DISCONNECT ALL ELECTRIC POWER IN CLUDING REMOTE DISCONNECTS BEFORE SERVICING FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH CAUTION USE COPPER CONDUCTORS ONLY...

Page 32: ...Digital Ready With Damper Actuators 3 10 K NTC Sensors 3 Terminal Strips 75 VA 24 volt Tfmr Wired w o UV Controller 23 Field Mounted Controls By Others 20 Part Load Variable Air MicroTech for Remote...

Page 33: ...e 100 Arrangement AT Unit Mounted Plenum With Front Discharge Double Deflection Grille 41 2 114mm Max Recess 165 8 422mm 36 914mm 36 914mm Grille Finish Is Clear Anodized Aluminum Air Flow NOTE 1 For...

Page 34: ...h other to en sure they are compatible with the specific installation 2 Duct collars shipped loose for field installation not by AAF HermanNelson 3 It is important also to verify there is sufficient c...

Page 35: ...air ducts to handle 100 of the total cfm to accommodate economizer or morning warm up operation If a supply air duct with improper duct work is placed too close to the unit discharge it will result i...

Page 36: ...ach or hang the ceiling off of the unit ventilator Flexible Boot 5 Feet Same Size As Unit Discharge Accoustically Lined Insulated Ductwork to Prevent Sweating Heat Loss or Heat Gain Unit Ventilator In...

Page 37: ...ondensate piping from the drain trap must be sloped to facilitate properdrainage Theclearplastictrapshouldbeclampedandremovable for cleaning It may be necessary to manually fill the trap at system sta...

Page 38: ...l Data Motor Data and Unit Amp Unit CFM L s ESP Motor Unit Current Series Nom in H2O PA HP Watts 115V 208V 230V 265V S07 750 354 0 0 0 2 0 50 1 4 164 1 8 1 0 0 9 0 8 H07 0 21 0 45 52 5 112 5 1 2 239 2...

Page 39: ...reakers or other damages due to the inadequacy or interruption of electrical service 5 Controls supplied by others and improper operations hook up of such that impact unit operation or performance 6 D...

Page 40: ...s previous catalogs bulletins with regard to AAF HermanNelson unit ventilator products Illustrations cover the general appearance of AAF HermanNelson unit ventilator products at the time of publicatio...

Reviews: