Page 30 of 60 / IM 798 AE Self-Contained Unit Ventilator
Figure 63B - 10-pin Plug MicroTech II™ Wiring Diagram
2
Figure 63C - 4-pin Plug MicroTech II Control Wiring Diagram
3
Shield
P6 (10-pin)
Connector
Unit Ventilator
xBO-2
xBO-1
BO-6
BO-6
P6 (10-pin)
Connector
Wall Sleeve
Wire
Caps
601A
602A
603A
604A
605A
External Output
Option 1 Device
(by others)
External Output
Option 2 Device
(by others)
External Output
Option 3 Device
(by others)
Lights On/Off
Signal or
Motorized Water
Valve Open/Close
Fault Indication
or
Pump Restart
Signal
Auxiliary Heat
Signal
or
Exhaust Fan
On/Off Signal
Comm
Comm
606A
608A
610A
24vac Supply
24vac Comm
601
602
603
604
605
606
608
610
Communication
Module
(4-pin)
Male Connector
Unit Ventilator
Optional Building Automation System (BAS)
Wiring: Use twisted shielded pair (Connect Air W221P-2544 or equiv.).
Daisy-chain and tie shield to earth ground at one point only.
The polarity of the signal must always be maintained throughout the network.
Always c to + and – to –. The shield connection must be
continuous throughout the entire network and must be connected
to earth ground at one (and only one) point.
Use Belden 8471, NEMA Level 4, or Echelon-approved equivalent wire.
Since the LonWorks communication wiring is polarity insensitive, no polarity
must be observed when making connections via the unshielded twisted-pair
wiring.
Note: The N2 Bus can use either solid or stranded wires of the following types:
3-wire twisted cable, 2 twisted-pair telephone cable, or two twisted pair
with a shield.
The wiring is polarity sensitive.
The polarity of the signal must always be maintained throughout the network.
Always c to + and – to –. The shield connection must be
continuous throughout the entire network and must be connected
to earth ground at one (and only one) point.
LonWorks
®
FTT–10 (A)
FTT–10 (B)
BACnet
®
Metasys
®
GND
3
2
1
(4-pin)
Female Connector
Wall Sleeve
Black
Red
GND
N2–
N2+
GND
RT–
RT+
(By others)
(By others)
(By others)
Note: Not all external input options are available for all models.
Step 4 – Wall Sleeve Electrical Connections