Safety Instructions:
This manual contains important instructions for the GV-Boost GVB-8-Pb-**V and GVB-8-Li-**.*V
solar charge controllers that shall be followed during installation and maintenance. Various models
of the GVB are available to charge different battery types as follows:
•
GVB
‐
8
‐
Pb
‐
12V:
12V Lead-Acid/AGM/Gel/Sealed/Flooded
•
GVB
‐
8
‐
Pb
‐
24V:
24V Lead-Acid/AGM/Gel/Sealed/Flooded
•
GVB
‐
8
‐
Pb
‐
36V:
36V Lead-Acid/AGM/Gel/Sealed/Flooded
•
GVB
‐
8
‐
Pb
‐
48V:
48V Lead-Acid/AGM/Gel/Sealed/Flooded
•
GVB
‐
8
‐
Li
‐
**.*V:
Custom Lithium Variation
Consult your battery charging specifications to ensure that the GVB is compatible with your chosen
batteries.
Carefully follow these instructions.
CAUTION for the GVB-8-Pb-**V
(lead-acid Versions only):
Internal temperature Compensation. Risk of Fire, use Within 0.3 m (1 ft) of Batteries.
lead-
acid batteries can create explosive gases. short circuits can draw thousands of amps from a
battery. Carefully read and follow all instructions
supplied with the battery.
DO NOT SHORT CIRCUIT
the solar array when plugged into the controller.
do not measure short
Circuit Current
of the array while connected to the controller. this will destroy the controller, and
such damage will not be covered under warranty.
LITHIUM WARNING:
take caution when working with lithium systems. The controllers use the
CC/CV charging profile
indicated on the controller. Check the specifications of the battery pack to
ensure that the CV voltage is correct. Further check that the power supplied by the solar array
and controller is within the battery specified design limits.
LITHIUM BMS WARNING:
recommend using a lithium battery with a Battery management system
capable of disconnecting the solar charge controller in the event that any cell in the pack is
outside of its rated temperature, current, or voltage range. Failure to do so may result in property
damage, injury or death. Highly recommends the use of a Bms with cell balancing. Cell
balancing is mandatory for lithium-iron phosphate systems.
Use only 10-30 AWG copper conductors suitable for a minimum of 60 degrees C. If operation at
high power or at high ambient temperatures is expected, wire with a higher temperature rating
may be necessary.
Inspection
&
Maintenance
Inspect the controller at least once per year to ensure proper performance.
•
Check for animal or insect damage.
•
Inspect for corrosion / water damage.
•
Inspect the security of all connections.