PD.01, PD.03, PD.05, PD.07are to set frequency, direction, Acc/Dec time
of PLC stages. See Figure 7-25:
One
Ten
Hun
Thou
Frequency setting
0:Preset freuency i
1:Determined by P0.02
Running direction selection
0:Forward
1:Reverse
2:Determined by running
command
Acc/Dec time selection
0:Acc/Dec 1
0:Acc/Dec 2
0:Acc/Dec 3
0:Acc/Dec 4
Reserved
Figure 7-25 PLC Stage i setting ( i=1
~
7 )
One’s place:
0: select MS frequency i, e.g. i=3, means the frequency forstage 3 is MS
frequency 3, see P8.00~P8.06.
1: the frequency is determined by P0.02
7.15 Constant-pressure water supply ( PE )
7.16 Protection ( PL )
0: Disabled
The overload protection is disabled. Be careful to use this function
because the inverter will not protect the motor in case of overload;
1: Common motor ( with low speed compensation )
Since cooling conditions of common motor deteriorates at low speed, the
motor thermal protection threshold should also be adjusted. The “Low
Speed” here refers to the operating frequency lower than 30Hz.
PD.08 Stage 4 run time
Range: 0
~
6500s ( min )
【
20.0s
】
PD.09~PD.30 Reserved
Reserved
PE.00~ PE.20 Reserved
Reserved
PL.00 Motor overload protection
Range: 0, 1, 2
【
0
】