Page 6
09/2021
User Manual
Extended Battery Pack 6kVA, 10kVA
3. Installation
3.1. Inspecting the Equipment
■
If a unit was damaged during transport, keep the shipping cartons and
packing material for a claim of transport damage. If you notice damage after
acceptance, make a claim for concealed damage.
■
Check the recharge date of the batteries on the label of the shipping box. If
the date has expired and the batteries have never been charged, do not use
the EBP. Contact your supplier.
■
The packaging is recyclable. After unpacking, please keep it for reuse or dis-
pose of it properly.
■
Check the accessories against the packing list and contact the dealer if any
parts are missing. Accessories includes:
a-TroniX battery cabinet, operating instructions, mains cable, battery cabinet
connection cable and battery connector.
3.2. Battery installation
NOTE:
The unit and the batteries are
heavy.
Always use lifting techniques
appropriate to the weight.
Up to 40 pcs 12V/9A h batteries can be in-
stalled in the a-TroniX Battery Pack Pro. The
output voltage can be 96V, 108V or 120V
through the battery connection.
For operation, two battery strings are con-
nected in parallel which consist of BAT+, N
and BAT-.
Figure 1
on the right shows
the overall chassis:
figure 1