Basic Information 

Battery chargers model HFK are designed for single phase 230V for batteries from 12 to 96V with current from 25 to 

85Amps, while HFT chargers for three phase 400V for batteries from 24 up to  96V with current from 25 to 120Amps. 

Putting together 2 chargers we can reach up to180A. Working frequency can be either 50 or 60Hz. 

There are many kind of charging curve for Pb, Gel and AGM battery (WUIU, IUIa, IU0U and so on).  

Each curve profile is set with the default factory parameters but the software allows to change the value of these 

parameters by entering into a specific mode.    A desulphation curve is provided for the nominal battery. 

Software release currently available is 5.10 F. 

 

Power-on, end of the charge and power-off 

 

POWER-ON 

: Charger turns on connecting AC Main. Connecting the battery the charger starts automatically the cycle.  

END OF CHARGE

 : When the Display shows  

End

 and green LED is ON the charge is over.  

If a floating charge is set the display shows a letter after End: (ex: 

End5

  pulse floating) 

 

POWER-OFF and BATTERY DISCONNECTION

:  

Charger switches off pressing F button for 2 times (call and confirmation) or unplugging AC Main.  

Battery must be disconnected after the operation described above in order to avoid electric arcs.  

Charger requires normally about 10-20 sec before shutting off completely.   

WARNING: 

before connecting another battery wait for an acoustic sound (2 sec.) and wait for the display shows 

Bat

  

After stopping, a charge cannot be restored. Battery must be disconnected. The charge starts from the beginning.  

 

Display and LED information  

Scrolling parameters using << and >> buttons the display shows many useful technical information such as voltage, 

current, battery capacity, number of performed cycles etc. At start up, the display shows MAIN parameter (called 

navigator), able to provide general information on charger status (for example charger stage or reason of a stop). 

The following are just a piece of information. For having the complete number please ask for the technical manual.  

 

(*) navigator – the display shows one of the following information depending on what is the charger doing 

 

 

Charger is idle 

 

 

Charger is working    

 

Charger Error (some examples) 

bat 

Battery is missing 

 

F xx 

Standard curve 

 

t’ _  Overtemperature 

Stop 

Idle 

 

 

 

 

cur  Under current 

End 

Charge is completed 

 

 

 

  time  Max time exceeded 

 

WARNING

: Sequence and number of phases depends on cycle setting 

 

 

LED 1 – Yellow 

LED 2 – Yellow 

LED 3 – Green 

LED 4 – Red 

Flashing 

Transitional Phase  

Phase 3  constant current (I=K) 

Floating 

Error 

Fixed 

Phase 1   constant current (I=K) 

Phase 2  constant voltage (V=K)  Battery charged  Error 

 

Scrolling parameters on standard mode (set0) with << and >> buttons allows to know all charging information and setting  

 

Info  During the charge 

 

 

Other info 

 

 

Charger Set Up 

( * ) 

Navigator 

 

Completed charges 

 

Battery Ah 

Battery voltage 

 

Partial charges 

 

Battery Voltage 

Battery current 

 

Error code 

 

Charging Current 

Capacity accumulated 

 

Countdown 

 

Charging profile (curve) 

Capacity accumulated: phase 1+2   

 

 

 

Safety timer (h) 

Charging time elapsed 

 

 

 

 

Software release 

 

(*) the parameter “navigator” change continuously providing general charger information. 

 

For verifying that the charger setting is compatible with the battery you are charging and the charger is set in the right way, 

please scrolls the parameters described above (Charger set up) pressing the << (P2 button).

Summary of Contents for HFK Series

Page 1: ...ual De Usuario y Mantenimiento D Bedienungsanleitung A T I B ELETTRON VIA INDUSTRIALE 29 25030 BARBARIGA BS TEL 39 030 9971051 WWW ATIBELETTRONICA IT TD TT Use and Maintenance Manuel d utilisation et Manual De Usuario y Bedienungsanleitung T I B ELETTRONICA SRL 25030 BARBARIGA BS WWW ATIBELETTRONICA IT REV 11 16 ...

Page 2: ...o spegnete l apparecchiatura e non tentate la riparazione ma contattate il nostro ufficio tecnico o il centro di assistenza più vicino Siate precisi nel descrivere il problema riscontrato Non sono consentite riparazioni o sostituzioni se non autorizzate per iscritto dal nostro ufficio tecnico 1 2 Norme di riferimento e di sicurezza Il collegamento elettrico deve essere realizzato da personale spec...

Page 3: ...mente il capitolo Avvertenze e Sicurezza Per procedere alla messa in servizio è necessario seguire le seguenti istruzioni agendo in totale assenza di tensione 3 1 Fase di montaggio 1 Posizionate il carica batteria in un luogo adatto per permettere un adeguato ricircolo d aria Fate in modo che la spina di alimentazione del carica batterie sia ben visibile e facilmente raggiungibile 2 Eseguite la co...

Page 4: ...llarme presente E 1 Mancanza tensione di batteria all accensione tensione inferiore al 40 della tensione nominale La batteria non è collegata al carica batterie la presa spina batteria è danneggiata o un cavo batteria è interrotto o è bruciato il fusibile in uscita all interno del carica batterie E 2 Tensione di batteria inferiore alla soglia minima 63 Vnom E 3 Tensione di batteria inferiore alla ...

Page 5: ...azioni sul Display e Segnalazioni LED Il display fornisce molte informazioni tecniche quali la tensione la corrente la capacità il numero di cariche ecc scorrendo il display con i tasti e All accensione il Display si pone sul parametro unico o navigator che fornisce informazioni generali sullo stato del CB ad esempio se è in funzione o e se è fermo per quale motivo Queste sono solo alcune delle in...

Page 6: ...ione con la password 2222 vedi come fare nel paragrafo successivo Vedrete ora 3 parametri 3 Curva di carica 2 Corrente di carica e 0 Capacità della Batteria Modificateli secondo la batteria che dovete caricare e tornate in modalità standard impostando la password 1111 o riavviare il CB Apparirà prima Set0 e poi il parametro unico bat Se volete rivedere la programmazione basta scorrere i parametri ...

Page 7: ...n Ritardo Accensione E 19 Segnali di Errore bat Batteria Manca la Batteria indica che dovete collegarla Se lo fosse significa Batteria Bassa o Fusibile Uscita Bruciato E 1 bat1 Batteria 1 Sottotensione Batteria Tentata una carica ma la Batteria è sotto i limiti impostati E 3 bat9 Batteria 9 Sovrastensione Batteria E 12 t I t IGBT Sovratemperatura IGBT Attendere raffreddamento E 4 t D1 t Diodo Sovr...

Page 8: ...t the charger In case of failure or malfunctioning turn off the machine and do not try to repair Please call our technical service or service centre nearest to you Be as accurate as possible on describing the problem found Any reparation or replacement of parts must be authorised in writing by our technical department 1 2 Safety and reference rules Specialised personnel must make the electrical co...

Page 9: ...ormation at our offices technical dept about how to modify the intervals of functioning of the pump Charging phases visualisation Charge phases display L1 L2 L3 L4 Display Ac Mains Voltage on the battery charger missing Initial phase of the charge with connected battery having a voltage 2 4 V el Final Charge with battery voltage constant at 2 4 V el phase V1 Final Charge with constant current phas...

Page 10: ...to the charger the battery plug is damaged a battery cable is interrupted or the output fuse inside the charger has burnt E 2 Battery voltage is below the min threshold 63 Vnom E 3 Battery voltage is below the second threshold 65 Vnom after 1 minute E 4 5 6 Intervention of a thermal probe on semiconductors NTC1 NTC2 NTC3 E 7 Maximum charging time exceeded time out error Battery not fitted for the ...

Page 11: ...e cannot be restored Battery must be disconnected The charge starts from the beginning Display and LED information Scrolling parameters using and buttons the display shows many useful technical information such as voltage current battery capacity number of performed cycles etc At start up the display shows MAIN parameter called navigator able to provide general information on charger status for ex...

Page 12: ...After a few sec the Display shows bat and is giving a sound of about 2 sec Charger is ready to charge Enter into EASY mode typing the password 2222 see below Now you can scroll with and 3 parameters 3 Charging profile 2 Current and 0 Battery capacity Modify the parameters according with the battery to re charge and return to standard mode typing code 1111 or restarting The Display shows Set0 and t...

Page 13: ...y not connected It simply means it should be connected If not means battery voltage too low or output fuse blown E 1 bat1 Battery 1 Battery undervoltage Battery is under of the setting range E 3 bat9 Battery 9 Battery overvoltage E 12 t I t IGBT IGBT overheating Charger is waiting for cooling or probe failure E 4 t D1 t Diode Diode 1 overheating Charger is waiting for cooling or probe failure E 5 ...

Page 14: ... d une panne ou d une anomalie arrêtez l équipement et n essayez pas de faire des réparations Veuillez contacter notre bureau d études ou le plus proche centre d assistance spécialisé Nous n acceptons pas de réparations ou remplacements s ils n ont pas étés acceptées par écrit par notre bureau d études 1 2 Normes de sécurité Le branchement électrique doit être réalisé par du personnel spécialisé N...

Page 15: ...ents et Sécurité Pour procéder à la mise en service il est nécessaire de suivre les indications suivantes Les opérations doivent être effectuées en TOTALE absence de tension 3 1 Phase de montage 1 Positionner le chargeur dans un endroit adapté pour permettre une bonne circulation d air Vérifiez que la prise d alimentation du chargeur soit bien visible et facilement utilisable 2 Réalisez le branche...

Page 16: ...bles AC en entrée E 0 Aucun alarme E 1 Faute de tension de batterie pendant la mise en marche du chargeur tension au dessous du 40 de la tension nominale La batterie n est pas branchée au chargeur la prise de la batterie est cassée un câble de la batterie est coupé ou le fusible en sortie dans le chargeur est brûlé E 2 Tension de batterie au dessous de la seuil minimum 63 Vnom E 3 Tension de batte...

Page 17: ...r du message Bat Après un arrêt ce n est pas possible de reprendre la charge La batterie doit être débranchée La charge commence dès le début remise à zéro du cycle Affichage des informations et indications LED Le chargeur par l afficheur fournit nombreuses informations techniques telles que la tension le courant la capacité le nombre de charges etc Tous ca simplement en déplaçant les paramètres à...

Page 18: ... Chargeur est prêt pour être utilisé Entrez dans le mode de programmation avec le mot de passe 2222 voir comment faire dans la section suivante Vous verrez maintenant 3 paramètres 3 la courbe de charge 2 courant de charge et 0 Capacité de la batterie Changez les selon votre nécessité et votre batterie Revenez à la modalité standard en utilisant le mot de passe 1111 ou redémarrez le Chargeur L affi...

Page 19: ...t Batterie Faute de batterie Il faut simplement la brancher Si déjà branchée batterie ayant tension faible ou fusible sortie brulé E 1 bat1 Batterie 1 Batterie ayant une tension trop faible Charge essayée mais batterie ayant valeurs dessous les limitations réglées E 3 bat9 Batterie 9 Surtension batterie E 12 t I t IGBT Surchauffage IGBT Attendre son refroidissement E 4 t D1 t Diode Surchauffage Di...

Page 20: ...ía NO alimenten el cargador En caso de un problema o un mal funcionamiento apagar el aparato y no intentar repararlo sino contactar nuestra oficina técnica o el centro de asistencia más cercano Intentar ser precisos describiendo el problema encontrado No están permitidas reparaciones o sustituciones si no autorizadas por escrito por nuestra oficina técnica 1 2 Normas de seguridad y referencia El e...

Page 21: ...or de batería 3 INSTALACIÓN Lea atentamente el capítulo Advertencias y Seguridad Para pasar a la puesta en marcha es necesario seguir las instrucciones siguientes operando en total ausencia de tensión 3 1 Fase de montaje 1 Posicionar el cargador en un lugar adapto y permitir un adecuado recambio de aire Asegurarse que el interruptor ON OFF sea bien visible y fácilmente alcanzable 2 Conectar los en...

Page 22: ...a se utilice fuera de los parámetros definidos por la especificaciones del producto o por el pedido 4 MANUTENCIÓN La frecuencia de los controles depende del uso y de las condiciones de empleo pero generalmente no tendría que ser superior a tres meses Las operaciones deben efectuarlas personal cualificado que cumpla las normas de seguridad En nuestras oficinas encontrará a su disposición específico...

Page 23: ...de una parada no es posible retomar la carga La batería tiene que ser desconectada La carga reparte dal principio Informaciones sobre el Display y Señales LED El display muestra muchas informaciones tecnicas como la tensión la corriente la capacidad el número de cargas ecc avanzando el display con los teclados y A la activación el Display se pone en el parámetro único o navigator que muestra infor...

Page 24: ...ay que entrar en la Modalidad Programación con la password 2222 véase el párrafo sucesivo Ahora vedran 3 parámetros 3 Curva de carga 2 Corriente de carga y 0 Capacidad de la Batería Hay que modificar según la batería que tienen que cargar y hay que regresar en modalidad estándar configurando la password 1111 o reactivar el Cargador Aparecerá primero Set0 y después el parámetro único bat Si quiren ...

Page 25: ...ación E 19 Indicador de Errores bat Batería Falta la Batería indica que hay que conectarla Mientras si la hay significa que la Batería es Baja o Fusible Salida está Quemado E 1 bat1 Batería 1 Bajo tensión Batería Intentada una carga pero la Batería está debajo los límites programados E 3 bat9 Batería 9 Sobretensión Batería E 12 t I t IGBT Sobrecalentamiento IGBT Esperar el enfriamiento E 4 t D1 t ...

Page 26: ...ntsprechen das Ladegerät nicht benutzen Im Fall von Schaden des Gerätes schalten Sie es aus und versuchen keine Reparaturen auszuführen Sie können sich mit unserer technischen Abteilung in Verbindung setzen um die Betriebsstörung am besten zu beschreiben Keine Reparaturen oder Ersätze ausführen wenn sie nicht von unseren technischen Abteilung schriftlich erlaubt werden 1 2 Hinweise und Sicherheits...

Page 27: ...chnitt Hinweise und Sicherheitsbestimmungen vollkommen durchlesen Die Inbetriebsetzung soll ohne Spannung ausgeführt werden 3 1 Einbauphase 1 Das Gerät in den passenden Ort einstellen um den Luftumlauf zu ermöglichen Den Netzspannungsstecker soll gut sichtbar und leicht erreichbar sein 2 Die Steckdosen und die Stecker müssen mit besonderer Achtung auf die Erdlegung von der Wechselstromseite angesc...

Page 28: ... weniger als 40 von Nennspannung Die Batterie ist nicht mit dem Gerät verbunden die Stecker Steckdose oder die Verkabelung sind fehlerhaft oder die Ausgangsicherung ist verbrannt E 2 Batteriespannung weniger als 63 der Nennspannung auf Start E 3 Batteriespannung weniger als 65 der Nennspannung auf Start nach 1 E 4 5 6 Der Temperaturbegrenzer auf den Halbleitern hat eingegriffen NTC1 NTC2 NTC3 E 7 ...

Page 29: ...adeprozess kurz nach Unterbrechung weitergehen schalten Sie bitte die Batterie ab dann fängt Ladung wieder vom Anfang an Display LED Am Display sind Daten wie z B Spannung Strom Ah Kapazität durch und Tasten visualisiert Display zeigt beim Einschaltung den Hauptparameter Navigator und gibt allgemeine Infos über das Status des LG bzw ein aus Stand by od Fehler mit erforderlichen Gründen Bitte lesen...

Page 30: ... Das LG ist bereit für eine neue Ladung den EASY Mode EASY Betrieb rufen indem Sie das Kennwort 2222 benutzen siehe unten nächsten Paragraf 3 Parameter werden visualisiert 3 Ladekennlinie 2 Ladestrom 0 Ah Batteriekapazität Je nach der gewünschten Batterie die Parameter einstellen und dann den Standard Mode rufen indem Sie das Kennwort 1111 benutzen oder das LG neu starten Das Display zeigt Set0 un...

Page 31: ...t bedeutet es niedriege Batteriespannung oder geöffnete Ausgangssicherung E 1 bat1 Batterie 1 Batterieunterspannung Die Batterie ist ausserhalb der eingestellten Parameter E 3 bat9 Batterie 9 Batterieüberspannung E 12 t I t IGBT IGBT Überhitzung Das Ladegerät ist in Hold mode solange die Temperatur wieder normal ist E 4 t D1 t Diode Diode1 Überhitzung Das Ladegerät ist in Hold mode solange die Tem...

Page 32: ...en EN 61000 6 3 2002 Nome del fabbricante Name of Manufacturer Nom du fabricant Names des Herstellers Indirizzo del fabbricante Adress of manufacturer Adresse du fabricant Addresse des Herstellers Descrizione del materiale Description of goods Description des marchandises Warenbezeichnung Modello Model Modèle Modell Date of issue 01 03 2009 Costruito a Made in Fabbriqué à Hergestellt in Tinti Luca...

Reviews: