background image

                                          

 

TDC-100 Series 

AC Digital High-Resolution Controller 

Installation & Maintenance Manual  

 

 

07/24/20 

www.atcontrols.com 

IOM08032 REVISION 01 

 

POSITION OUT CAL

 

 
The POSITION OUT CAL function is used to calibrate an 
optional  feedback  transmitter  output.  An  appropriate 
transmitter option module is required to use this feature. 
When the POSITION OUT CAL function is first selected 
(by  pressing  the  MODE  button  while  in  the  LOSS  OF 
COMMAND function), the CLOSE indicator will flash, and 
the voltage or current associated with the 

closed

 position 

will  appear  at  the  option  module  output.   If  desired,  the 
output can be adjusted (using the adjust buttons) to any 
value from 0 to 10V (for a voltage output) or 4 to 20mA 
(for a current output).  The new setting is saved when the 
MODE button is pressed. 
 
Pressing the MODE button again will leave the unit in the 
POSITION  OUT  CAL  function  except  that  the  OPEN 
indicator  will  flash,  and  the  output  voltage  or  current 
associated with the 

open

 position will appear at the option 

module output.  Like the 

closed

 setting, the output can be 

adjusted to any voltage (from 0 to 10V) or current (from 4 
to 20mA), and the new setting is then associated with the 

open

 position. 

 
 

FAULT INDICATORS

 

 
 

The TDC-100 detects various fault conditions that 

prohibit  the  unit  from  controlling  the  actuator.    A 
combination of the three Fault indicators (red, yellow, and 
green) will turn on or flash to indicate a specific detected 
fault. If an appropriate relay option module is installed, the 
Fault relay output on the option module will also turn off 
(indicating a fault) when any of the Fault indicators turn on 
or flash.  A communications option module can read the 
specific condition(s) causing  the  fault.    Note  that  a  fault 
condition  DOES  NOT  disable  the  motor  outputs  when 
manually controlling the actuator with the adjust buttons; 
while useful for troubleshooting, care should be exercised 
when  operating  the  motor  under  a  fault  condition.    The 
OVERRIDE  mode  can  also  operate  the  motor  when  a 
fault condition exists - see OVERRIDE MODE for details.  
 
Note  that  the  indicators  may  not  indicate  all  the  fault 
conditions  that  may  exist.  This  means  that  when  the 
indicated fault is corrected, the unit may display another 
fault  that  has  not  been  corrected.  The  following  table 
provides  a  summary  of  the  Fault  indicators  which  is 
followed by a description of each fault. 
 
 
 
 
 
 
 
 

RED 

YEL 

GRN 

FAULT 

Flash 

Flash 

OFF 

Motor 1 No Motion (Stall) 

Flash 

OFF 

Flash  Motor 2 No Motion (Stall) 

Flash 

Flash 

Flash  Double No Motion (Stall) 

OFF 

OFF 

Flash  Feedback Alarm 

OFF 

Flash 

OFF 

Loss of Command 

OFF 

ON 

OFF 

Command Out of Range 

OFF 

Flash 

Flash 

Feedback Alarm and 
Loss of Command 

OFF 

ON 

Flash 

Feedback Alarm and 
Command Out of Range 

 
 

Motor 1 No Motion (Stall) 

- A fault condition is detected 

when  no  actuator  motion  is  detected  while  the  Motor  1 
output  is  turned  on.    The  fault condition  will  disable  the 
Motor  1  output  only,  and  the  fault  is  cleared  when  the 
TDC-100  detects  a  motion  greater  than  1.5

  in  either 

direction.    The  fault  can  be  cleared  if  1)  the  command 
signal  commands  a  Motor  2  operation,  2)  manual 
operation  with  the  adjust  buttons  results  in  a  motion 
greater  than  1.5

,  or  3)  a  mechanical  manual  override 

forces the 1.5

 motion, provided the mechanical motion is 

monitored by the feedback pot. 
 

Motor 2 No Motion (Stall)

 - A fault is detected when no 

actuator  motion  is  detected  while  the  Motor  2  output  is 
turned on.  The fault can be cleared in the same manner 
as a Motor 1 Stall (see above). 
 

Double  No  Motion  (Stall)

  -  If  the  TDC-100  detects  no 

actuator motion in either direction, both motor outputs will 
be  disabled.    The  command  signal  cannot  clear  this 
condition; only manual operation or a mechanical override 
can  clear  the  fault.    Alternatively,  the  TDC-100  can  be 
powered  off  and  then  on  to  temporarily  clear  the  fault; 
however,  this  practice  should  be  avoided  without 
permanently correcting the cause of such a fault. 
 

Feedback Alarm

 -  A fault condition is detected whenever 

the feedback signal is out of range (that is, less than 5% 
of  the  potentiometer  value  or  more  than  95%  of  the 
potentiometer  value),  or  when  any  of  the  potentiometer 
connections are broken.  Normal operation resumes when 
the potentiometer is reconnected or back in range. 
 

Loss  of  Command 

-  If  the  command  signal  is 

disconnected,  the  fault  indicator  will  remain  on  until  the 
signal  is  reconnected.  See  LOSS  OF  COMMAND  for 
details. 
 

Command Out of Range

 – If the command signal goes 

out  of  range,  the  fault  indication  will  remain  on  until the 
signal  is  back  in  range.  See  LOSS  OF  COMMAND  for 
details. 
 

Summary of Contents for TRIAC TDC-100 Series

Page 1: ...ch as a position feedback signal current or voltage auxiliary switches fault relay contact or digital communications A wide range of data is accessible through a digital communications module providin...

Page 2: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 2 07 24 20 www a tcontrols com IOM08032 REVISION 01 OUTLINE TDC 100 117VAC TDC 100A 234VAC TDC 100B 24VAC...

Page 3: ...ed as a direct replacement for those units in nearly any application The simple three button control MODE and allows the user to perform a complete set up from the unit itself without the need for any...

Page 4: ...used auto manual station switches are easily implemented with low voltage low current switches See Special Applications for more details The factory installed jumper between pins 1 and 2 enables norm...

Page 5: ...of 10V 5V 20mA or 100 will position the actuator to the defined open position When the TDC 100 is configured to use a 0 5V 0 10V 1 5V or 4 20mA command the command signal should be connected to the ap...

Page 6: ...unction the TDC 100 will begin moving the actuator to the previously set position It is not necessary to make an adjustment if the unit has been previously set to the desired position COMAND TYPE The...

Page 7: ...ed fault is corrected the unit may display another fault that has not been corrected The following table provides a summary of the Fault indicators which is followed by a description of each fault RED...

Page 8: ...100 automatically compensates for changes in a mechanical brake s performance due to temperature or age Note that the actuator s limit switches should be set outside of the operating range set by the...

Page 9: ...ODULES Various option modules can be plugged into the TDC 100 option module connector J3 Option modules provide additional features such as position feedback signals auxiliary switch outputs or digita...

Page 10: ...and threshold 0 75V 1 5 VDC input 1 5V 2 10 VDC input 3mA 4 20mA input Command Out of Range threshold 5 25V 0 5 VDC 1 5 VDC input 10 5V 0 10 VDC 2 10 VDC input 21mA 4 20mA input FEEDBACK SIGNAL INPUT...

Page 11: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 11 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Input Signal Configurations...

Page 12: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 12 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications...

Page 13: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 13 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications continued...

Page 14: ...or stable command signal Triac output failure Motor buzzes and overheats Perform appropriate remedy then replace the unit Exposure to water from conduit entrance Exposure to water from unsealed actuat...