background image

                                          

 

TDC-100 Series 

AC Digital High-Resolution Controller 

Installation & Maintenance Manual  

 

 

07/24/20 

www.atcontrols.com 

IOM08032 REVISION 01 

 

Upon  selecting  the  CLOSE  function,  the  TDC-100  will 
begin  moving  the  actuator  to  the  previously  set 

closed

 

position; it is not necessary to make an adjustment if the 
unit  has  been  previously  set  to  the  desired  position.    A 
command signal input of 0V, 1V, 4mA, or 0% automatical-
ly corresponds to the defined 

closed

 position. 

 
 

OPEN

 

 
The OPEN function works the same way as the CLOSE 
function  with  the  exception  that  the  adjust  buttons  are 
used to set the desired 

open

 position.  As with the CLOSE 

function, upon selecting the OPEN function, the actuator 
will move to the previously set 

open

 position.  Once the 

desired  position  is  set,  the  TDC-100  will  automatically 
correspond a command signal input of 10V, 5V, 20mA, or 
100% to the 

open

 position. 

 
 

AUX CLOSE OUTPUT

 

 
The  AUX  CLOSE  OUTPUT  function  is  used  to  set  an 
optional output setting that is associated with the 

closed

 

position - an appropriate relay option module is required 
to use this output.  The adjust buttons are used to set the 
actuator  to  a  desired  position.    Whenever  the  actuator 
position falls between the defined 

closed

 position and the 

Aux  Close  position,  the  Aux  Close  Output  indicator  will 
flash.  Additionally, the TDC-100 will turn on a relay output 
on the optional relay module - the output can be used to 
drive an alarm or merely act as an auxiliary limit switch. 
 
Upon  selecting  the  AUX  CLOSE  OUTPUT  function,  the 
TDC-100 will begin moving the actuator to the previously 
set position.  It is not necessary to make an adjustment if 
the unit has been previously set to the desired position. 

 
 
AUX OPEN OUTPUT

 

 
The  AUX  OPEN  OUTPUT  function  is  used  to  set  an 
optional  output  setting  that  is  associated  with  the 

open

 

position - an appropriate relay option module is required 
to use this output.  The adjust buttons are used to set the 
actuator  to  a  desired  position.    Whenever  the  actuator 
position falls between the defined 

open

 position and the 

Aux  Open  position,  the  Aux  Open  Output  indicator  will 
flash.  Additionally, the TDC-100 will turn on a relay output 
on the optional relay module - the output can be used to 
drive an alarm or merely act as an auxiliary limit switch. 
 
Upon  selecting  the  AUX  OPEN  OUTPUT  function,  the 
TDC-100 will begin moving the actuator to the previously 
set position.  It is not necessary to make an adjustment if 
the unit has been previously set to the desired position. 
 

COMAND TYPE

 

 
The COMMAND TYPE function is used to configure the 
command signal input for either 4-20mA, 1-5V, 0-5V, 0-
10V, 2-10V, or digital so as to match the type of command 
signal being used.  Upon selecting the COMMAND TYPE 
function, the Command Input indicator will turn on steady, 
while the indicator for the selected type will flash.  Use the 
adjust buttons (▲ or ▼) to select the desired input type.  
The  selection  will  be  saved  when  the  MODE  button  is 
pressed, which will also advance the unit to the LOSS OF 
COMMAND function. 
 
 

LOSS OF COMMAND

 

 
When using 1-5V, 2-10V, 4-20mA, or a Digital input type 
for the command signal, the TDC-100 will detect when the 
command  signal  is  lost  or  out  of  range.    A  loss  of 
command  condition  is  detected  whenever  the  input  is 
disconnected, the input becomes less than 0.75V (for 1-
5V input), 1.5V (for 2-10V input) or 3mA, or the input is 
connected  backwards.  An  out  of  range  condition  is 
detected whenever the input becomes greater than 5.25V 
(for 1-5V input), 10.5V (for 2-10V input) or 21mA.  If the 
TDC-100 detects a loss of the command signal, a fault will 
be indicated (see FAULT INDICATORS), and the actuator 
will be moved to one of three preset positions: the 

open

 

position, the 

closed

 position, or the position last attained 

prior  to  losing  the  command  signal.    The  LOSS  OF 
COMMAND  function  is  used  to  set  the  desired  default 
position. 
 
When the LOSS OF COMMAND function is selected, the 
adjust buttons are used to set the default position.  The 
TDC-100 indicates the selected default setting by flashing 
the Open function indicator for the 

open

 default position, 

or it will flash the Close function indicator for the 

closed

 

default  position.    When  neither  indicator  is  on,  then  the 
"last position" default is selected. 
 
When a 0-5V or 0-10V command signal is used, a loss of 
command  signal  cannot  be  detected.    Therefore,  if  the 
unit  is  configured  for  a  0-5V  or  0-10V  command  signal 
(see COMMAND INPUT), the MODE button will not select 
the  LOSS  OF COMMAND  function.  However, the  TDC-
100 can detect when a 0-5V or 0-10V command signal is 
out  of  range  (i.e.,  greater  than  5.25V  or  greater  than 
10.5V)  or  connected  backwards.  When  an  out  of  range 
condition is detected for a 0-5V or 0-10V input, the motor 
is turned off (leaving the actuator in its “last position”) and 
a fault will be indicated (see FAULT INDICATORS). 
 
 
 
 
 

Summary of Contents for TRIAC TDC-100 Series

Page 1: ...ch as a position feedback signal current or voltage auxiliary switches fault relay contact or digital communications A wide range of data is accessible through a digital communications module providin...

Page 2: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 2 07 24 20 www a tcontrols com IOM08032 REVISION 01 OUTLINE TDC 100 117VAC TDC 100A 234VAC TDC 100B 24VAC...

Page 3: ...ed as a direct replacement for those units in nearly any application The simple three button control MODE and allows the user to perform a complete set up from the unit itself without the need for any...

Page 4: ...used auto manual station switches are easily implemented with low voltage low current switches See Special Applications for more details The factory installed jumper between pins 1 and 2 enables norm...

Page 5: ...of 10V 5V 20mA or 100 will position the actuator to the defined open position When the TDC 100 is configured to use a 0 5V 0 10V 1 5V or 4 20mA command the command signal should be connected to the ap...

Page 6: ...unction the TDC 100 will begin moving the actuator to the previously set position It is not necessary to make an adjustment if the unit has been previously set to the desired position COMAND TYPE The...

Page 7: ...ed fault is corrected the unit may display another fault that has not been corrected The following table provides a summary of the Fault indicators which is followed by a description of each fault RED...

Page 8: ...100 automatically compensates for changes in a mechanical brake s performance due to temperature or age Note that the actuator s limit switches should be set outside of the operating range set by the...

Page 9: ...ODULES Various option modules can be plugged into the TDC 100 option module connector J3 Option modules provide additional features such as position feedback signals auxiliary switch outputs or digita...

Page 10: ...and threshold 0 75V 1 5 VDC input 1 5V 2 10 VDC input 3mA 4 20mA input Command Out of Range threshold 5 25V 0 5 VDC 1 5 VDC input 10 5V 0 10 VDC 2 10 VDC input 21mA 4 20mA input FEEDBACK SIGNAL INPUT...

Page 11: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 11 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Input Signal Configurations...

Page 12: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 12 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications...

Page 13: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 13 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications continued...

Page 14: ...or stable command signal Triac output failure Motor buzzes and overheats Perform appropriate remedy then replace the unit Exposure to water from conduit entrance Exposure to water from unsealed actuat...

Reviews: