IOM D-025 ARISENSE

 

 

 

8.  PERIODIC MAINTENANCE 

 

 

Please  note  that  the  periodic  maintenance  of  the  air  valve  is  an  integral  part  of  the  proper  pipeline  maintenance 
regime; it should be maintained at least once a year in accordance with the quality and composition of the fluid in the 
system.   
 

Important:

 Before performing any work on the air valve make sure that all workers on site are familiar with the safety 

instructions as appear in Chapter 1 of this document and with all the relevant local and general safety instructions, 
standards and work regulations.  
 

Please note

 that maintaining the D-025 ARISENSE product consists of two separated procedures: Maintaining the Air 

Valve Component and maintaining the Arisense component. 
 

 
8.1. Releasing Pressure 

 

 

Shut the isolating valve located on the riser under the air valve 

 

Open the Ball Valve to release pressure and drain the air valve [1] 

 

Important: Discard liquid in compliance with local regulations 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

     1

Summary of Contents for D-025

Page 1: ...scription of the A R I D 025 ARISENSE industrial combination air valve installation operation and maintenance processes The D 025 ARISENSE air valve is designed for systems that operate within the pressure and temperature framework of the model s specifications table Please consult A R I for products designed for other hazardous liquids systems ...

Page 2: ...mediately A R I assumes that all users understand the risks involved within this Disclaimer and or in any document enclosed hereto A R I accepts assumes no liability whatsoever whether caused by accessing and or relying upon this Disclaimer and or in any document enclosed hereto including without limitation any links procedures or materials A R I shall NOT assume any liability for any costs direct...

Page 3: ... that the product s outlet port is not directed toward electrical elements pumps or people o The pressurized fluid and or gas that can be discharged from the product may create high noise levels Take this into consideration when installing the product in areas sensitive to noise 8 Always open and close valves slowly and gradually 9 Please note that the maximum working pressure indicated at the pro...

Page 4: ...from the system and before releasing the residual pressure do NOT o loosen or unscrew the product bolts o remove any protection cover o open any service port 4 Before any maintenance or non regular operation shut off the Isolation valve and release the residual pressure A For air valves with pressure release outlet slowly open the pressure release plug or the ball valve and make sure that all pres...

Page 5: ...operations 2 Make sure that all the tools ladders lifting devices etc used during the maintenance procedures are taken away from the product area and stored 3 Remove grease and fat material residues in order to avoid slipping 4 In order to return the product to regular operation follow the First Start up Operation instructions as detailed in your user manual ...

Page 6: ...lve on an Isolating Valve at 45 to Air Valve outlet Two Air Valves on an Air Trap with separate Isolating Valves Air Valve outlets face outward and the Isolating Valves at 45 to Air Valve outlets Two Air Valves on a shared Isolating Valve Air Valves outlets face outward and the Isolating Valve at 45 to Air Valve outlets Underground Installations Underground installations require a venting pipe fro...

Page 7: ...pelines up to 12 300mm in diameter D the Air Trap diameter d should be the same as the pipeline diameter For larger pipelines of up to 60 1500mm in diameter D the Air trap diameter d should be 60 of the pipeline diameter For larger than 60 1500mm pipelines D the Air trap diameter d should be 35 of the pipeline diameter The Air trap length H should allow easy access to the air valve from below and ...

Page 8: ...d using these hoist rings 4 Install an isolating valve below the air valve connected by a Riser to the crown of the pipe 5 Mount the air valve carefully on the rubber gaskets of the isolating valve 6 Place washers on each of the bolts nuts that connect the air valve flange to the isolating valve flange 7 Tighten all the bolts and nuts using the crossover method a The closure tightness of the bolts...

Page 9: ...y work on the air valve make sure that all workers on site are familiar with the safety instructions as appear in chapter 1 of this document and with all the relevant local and general safety instructions standards and work regulations 3 1 Required tools and materials Flat tip screwdriver Phillips head screwdriver 8mm combination spanner 6 mm Allen key Plastic head hammer Small bowl with kitchen t...

Page 10: ...nscrew the four bolts of the battery compartment cover 2 and remove the cover 3 3 3 Insert the SIM card Insert the SIM card to its designated socket at the lower part of the battery compartment 4 5 Remark if the battery connector is already connected reassemble the compartment cover and the red outlet elbow 4 5 2 3 1 2 3 ...

Page 11: ...ct the battery s orange female connector 6 to the Arisense white male connector 7 Reassemble the battery compartment cover 8 and the red outlet elbow The Arisense is initialized and ready to be configured and connected to the communication network 6 7 8 ...

Page 12: ...it This is the basic ARISENSE unit its communication module transmits Leak Overflow Tilt Tamper Vandalism Pit level and Low battery alerts The Partner unit is a single air valve unit that can be connected to a master unit only Master Unit The master unit can be connected to up to 5 partner units via its RF communication module and at the same time it is connected to the Server via its Cellular com...

Page 13: ...missions Make sure that the Bluetooth communication of your Smartphone is switched on Launch the app on your mobile device by clicking the ARISENSE icon applicable for software version 1 0 0 15 Picture 1 ARISENSE icon 1 Connecting the Arisense Application to the Air Valve The Welcome screen appears Picture 2 Welcome screen General Note At any stage of the application operation you can return to th...

Page 14: ...ons of the app Basic and EXPERT The following description is for a BASIC USER type I Basic User Picture 3 User Type Selection Screen Setting Password Once the User Type is selected the set password screen appears Set your password it should contain four characters Letters Numbers or a Mixture of letters and numbers Picture 4 Set Password Screen ...

Page 15: ...s set it will be required at every entry to the application o Once set the password cannot be changed again On the main screen select the first button IDENTIFY Picture 5 Main Screen Basic User Select the CONNECT button CONNECT BLUE Picture 6 Connection screen ...

Page 16: ...ation at the bottom of the unit Picture 7 Magnet designated location Note The Air Valve model is for illustration only Wait until a confirmation message is received on the screen The message will list the ID number of the unit you are connecting to Select the Identified unit Picture 8 Identified Unit Screen ...

Page 17: ...ing message Wait until the ID number of the unit you are connecting to appear on screen and the Green LED on the upper left side of the screen is turned on Your Smartphone application is connected now to the Arisense air valve Picture 10 Connected Screen Return to the Home screen ...

Page 18: ... versions regional clock etc You can change the valve type by clicking on the image and selecting from the list of images that open Picture 11 Unit Settings screen Note The Air Valve picture is for illustration only III Setting the Antenna Type Click on the UPDATE button next to the Antenna Type entry of the SETTING screen and select the type of Antenna connected to your Arisense unit Picture 12 S...

Page 19: ... you can see the status of all the unit sensors by a LED display Green okay no alert Red Alert activated Shut off communication with the unit is disconnected and needs to be reconnected Picture 13 Sensor Status Screen V Unit Registration REGISTER To register the unit click REGISTER Picture 14 Master Unit Registration Screen ...

Page 20: ...e email address associated with the customer and click on the REGISTER button if it is a master unit or the AUTO REGISTRATION button if it is a partner unit Once registered you will be notified on the cell phone screen If the unit is already registered in the system or the registry fails for some other reason you will be notified Picture 15 Possible messages after attempting unit registration To r...

Page 21: ...Unit Cellular communication test will be performed Partner Unit The quality of the RF transmission between the partner and a selected master unit will be checked You must type in the master unit number or select a master unit from the drop down list and press START Note If you check the box you can select the same master from the drop down list next time At the end of the test you will receive a n...

Page 22: ...d User VIII Expert User Unit Registration REGISTER In the Partner Unit registration you can choose between automatic registration and registration for a specific master unit of your choice and you also can force registration or removal even if there is no transmission at the moment goes into effect as soon as there is transmission Note If you check the box you can select the same master from the d...

Page 23: ... app on your mobile device by clicking the ARISENSE icon applicable for software version 1 0 0 15 1 Connecting and using the Arisense Technician Unit RT communication For the RT communication make sure to select it on the welcome screen Turn on the technician s unit RT by long pressing the power button until two lights green and blue start to flash if a switch exists under the power button you nee...

Page 24: ...application operation you can return to the main screen by clicking on the ARISENSE icon at the top of the screen I User Selection User Selection On the Welcome Screen choose between 2 versions of the app Basic and EXPERT The following description is for a BASIC USER type Picture 4 User Type Selection Screen ...

Page 25: ...rd Screen Very Important o Once the password is set it will be required at every entry to the application o Once set the password cannot be changed again On the main screen select the first button IDENTIFY Picture 6 Main Screen Basic User Note With the first use of the technician unit Bluetooth connections must first be accessed under Settings Search for visible devices and confirm the IWEPTool Th...

Page 26: ... your device select IWEPTool with the Unit Code as shown on the unit see Picture 1 If your device is not listed click on Scan for devices Picture 8 List of Paired Devices After your cellular device connects to the technician unit a notification will appear at the bottom of the screen and a blue light will turn on in the technician unit Now click on the bottom window SCAN DEVICE The device will sea...

Page 27: ...s point move a magnet near the valve at the designated location at the bottom of the unit until a confirmation message is received on the screen The message will list the ID number of the unit you are connecting to Picture 10 Magnet designated location ...

Page 28: ...e message will list the ID number of the unit you are connecting to Select the Identified unit Picture 11 Connected unit message Confirm the message Now a green colored LED will light up on the screen indicating that your device is connected to the unit Photo 12 Green LED light is lit ...

Page 29: ...ct screen at work completion II Unit Information SETTINGS Screen of the Arisense Technician Unit application RT Clicking SETTINGS will take you to a screen where information about the unit is displayed such as valve type software versions regional clock etc You can change the valve type by clicking on the image and selecting from the list of images that open Picture 14 Unit Settings screen Note Th...

Page 30: ...ou can see the status of all the unit sensors by a LED display Green okay no alert Red Alert activated Shut off communication with the unit is disconnected and needs to be reconnected Picture 15 Sensor Status Screen IX Unit Registration REGISTER To register the unit click REGISTER Picture 16 Master Unit Registration Screen ...

Page 31: ...he email address associated with the customer and click on the REGISTER button if it is a master unit or the AUTO REGISTRATION button if it is a partner unit Once registered you will be notified on the cell phone screen If the unit is already registered in the system or the registry fails for some other reason you will be notified Photo 17 Possible messages after attempting unit registration To re...

Page 32: ...e User Type is selected the set password screen appears Set your password it should contain four characters Letters Numbers or a Mixture of letters and numbers Picture 18 Set Password Screen Very Important Once the password is set it will be required at every entry to the application Once set the password cannot be changed again ...

Page 33: ...lular communication test will be performed Partner Unit The quality of the transmission between the partner and a selected master unit will be checked You must type in the master unit number or select a master unit from the drop down list and press START Note If you check the box you can select the same master from the drop down list next time At the end of the test you will receive a notification...

Page 34: ...ou also can force registration or removal even if there is no transmission at the moment goes into effect as soon as there is transmission Note If you check the box you can select the same master from the drop down list next time 1 Flood Indicating option for underground Air Valve installations The Arisense electronic system includes an option for issuing a Flood Indication for Air Valves installe...

Page 35: ...ESHOOTING Symptom Possible Causes Remedy Valve leaking from Clamp area O ring is not in place debris in sealing area or Clamps are not properly tightened Open the bolt separate and remove the two Clamps Check the placement and integrity of the O ring Check for debris clean and close the Clamps Valve leaking from the Discharge Outlet A Low pressure B Debris caught in sealing mechanism or Rolling Se...

Page 36: ...tor 1 from the Arisense white male connector 2 and pull out the used battery 3 Insert a new battery to the battery compartment the capacitor should go in first 4 Make sure that the new battery is seated correctly within its compartment Reconnect the new battery s orange female connector to the Arisense white male connector and then reassemble the compartment s cover and the air valve red elbow out...

Page 37: ... site are familiar with the safety instructions as appear in Chapter 1 of this document and with all the relevant local and general safety instructions standards and work regulations Please note that maintaining the D 025 ARISENSE product consists of two separated procedures Maintaining the Air Valve Component and maintaining the Arisense component 8 1 Releasing Pressure Shut the isolating valve l...

Page 38: ...er Phillips head screwdriver 8mm combination spanner 6 mm Allen key Plastic head hammer Small bowl with kitchen type liquid soap 8 2 1 Remove the ARISENSE Air Release Outlet Unit Using the Phillips screwdriver unscrew 1 2 3 and remove 4 the two bolts connecting the ARISENSE black Air Release Outlet 1 2 3 4 ...

Page 39: ...39 IOM D 025 ARISENSE Using the Flat screwdriver 1 remove the ARISENSE black Air Release Outlet 2 3 8 2 2 Removing the Operating Valve Body Unscrew and remove the Operating Valve Body 1 2 1 2 3 1 2 ...

Page 40: ...40 IOM D 025 ARISENSE 8 2 3 Removing the Float Hold the Operating Valve Body turn it to the side 1 and remove the Clamping Stem 2 and the Float 3 together with the Rolling Seal 1 2 3 ...

Page 41: ...r Pay attention to the sealing area inside the Body Visually check the condition of the Rolling Seal 1 2 If any cracks or tears are found remove it from the Float and replace it If replacement is necessary slide out and remove the Rolling Seal Assembly 3 Take a new Rolling Seal Assembly and dip the tail end into the liquid soap solution 4 1 2 3 4 ...

Page 42: ...al Assembly into the groove on the Float 5 Gently pull the Rolling Seal Assembly until it is partially inserted into the Float grove Use the 4 5mm Roll Pin Punch to push the Rolling Seal Assembly to the middle of the Float 6 and align the middle of the Rolling Seal Assembly tail with the midline of the Float 7 5 6 7 ...

Page 43: ... make sure that the insertion direction and the end of the seal are as depicted on pictures 1 and 2 Insert the Float halfway into the Body 1 insert the Clamping Stem into the Rolling Seal groove of the Body make sure that it is inserted in the direction depicted on picture 2 Push the Float and the Clamping Stem together downwards into the Body until they are locked 3 1 2 1 2 3 ...

Page 44: ...ower plug of the ARISENSE black air release outlet 1 and 2 then thoroughly but gently wash and clean the components under clean running water 8 2 7 Reassembling the ARISENSE Unit Reassemble the ARISENSE Unit in reverse order of paragraphs 8 2 7 8 2 6 8 2 5 8 2 4 8 2 3 8 2 2 and 8 2 1 1 2 ...

Page 45: ...n spanner 6 mm Allen key Plastic head hammer Small bowl with kitchen type liquid soap 8 3 1 Removing the clap Insert the Allen screwdriver into the Allen screw head and turn counterclockwise to open 1 Remove Screw and Nut 2 and repeat the procedure for the other side of the clamp Pull out to remove Clamps from both sides of the valve body 3 1 2 3 ...

Page 46: ...lace the entire assembly on a clean flat surface 2 8 3 3 Cleaning Thoroughly wash and clean the inside of the Air Valve Body the Float 1 and the Base 2 under clean running water to remove all grime 1 2 8 3 4 Reassembling the Air Valve Reassemble the Air Valve in reverse order of paragraphs 9 3 2 and 9 3 1 1 2 ...

Page 47: ...NG 1 Discharge Elbow 2 Body 3 Leak Detector Case 4 Screws 5 Leak Detector Cover 6 Rolling Seal Assembly 7 Clamping Stem 8 Float 9 Screws 10 Battery Cover 11 Battery Cover Seal 12 Battery 13 O Ring 14 Electronics Case 15 Ring Float 16 Ring Float Connector ...

Page 48: ...48 IOM D 025 ARISENSE 1 O Ring 2 Body 3 Domed Nut 4 Stopper 5 Spring 6 Float Stem Washer 7 O Ring 8 Clamp Assembly 9 Base 10 Tap 11 Flange ...

Page 49: ...ompleting the Air Valve installation on the pipeline The external antenna installation procedure shown in the following pictures is valid for all Arisense Air Valves models 10 1 Measure the required length of the corrugated conduit tube from the air valve s antenna connector to the installation point of the antenna on the manhole wall 1 Cut the tube length accordingly 10 2 Insert the antenna cable...

Page 50: ...ir valve s connector fasten the thread with hand power only 1 10 5 Attach the conduit tube to the air valve s body heat and shrink the coupler sleeve with a heat gun 1 2 3 10 6 Seal the connection of the conduit tube to the air valve s body with silicon 1 1 1 2 3 1 ...

Page 51: ...the Discharge Elbow 1 for specific instructions please refer to the Arisense installation IOM 10 8 Seal the connection of the conduit tube to the antenna bracket with silicon 1 10 9 Drill Holes in the manhole s wall according to the installation blueprint and connect the antenna bracket with suitable stainless steel bolts to the manhole wall under the manhole cover 1 1 1 1 ...

Page 52: ...d secure it with suitable brackets to the manhole wall b If possible install the antenna outside of the manhole in such case make sure that the antenna is installed in a safe and protected place 10 11 Configure the cellular application of the Arisense for external antenna usage and check communication ...

Reviews: