background image

15

OPERATING SEQUENCE

1.  The EMC modulation controller has four modes of operation: 

Initialization, Standby, Running/Modulation, and Service. The 

internal MCB  micros control these modes through a sequence 

of steps (or States) which are further described in the “UIM 

Operating Procedures” section.

2.  When power is applied to the system, it enters the initialization 

mode and the following automatic functions are performed:

 

•  A. O. Smith opening screen is displayed.

 

•  The system goes through a calibration indicated by the 

green running LED blinking and then staying on; next the 

red service LED and yellow standby LEDs come on, next 

the service and runnings LEDs blink ON and OFF.

 

•  Stored values are recalled from memory.

 

•  Configuration dipswitches are read.

 

•  Pending faults are recalled

 

•  Micros on all boards start running (indicated by a flashing 

Yellow LED near each micro)

 

•  Input sensors are read

3.  After  initialization  is  complete  (approximately  10  seconds)  

system turns green LED off and goes to standby mode (yellow 

“Standby” LED on), unless a previously stored fault has been 

recalled,  which  will  send  system  into  service  model  (red 

“Service” LED on). In standby mode display shows temperature 

screen and in fault mode current error screen is displayed.

4.  The  system  then  compares  the  temperature  read  from  the 

controlling probe (inlet or tank) to the setpoint temperature.  If 

the temperature is less than the operating setpoint minus the 

setpoint differential temperature and the enable/disable input 

is closed then a call for heat is established and the system 

shifts to the run mode (green “Running” LED turns on).

5.  The heating sequence begins by applying power to the pump.
6.  After a few seconds the blower is turned on for 30-second 

pre-purge period of combustion chamber.

7.  The  igniter is turned on.
8.  After the igniter has reached a minimum of 2.8 amps, the gas 

valve is energized to allow gas flow to burner.

9.  After an additional one second, the system checks status of the 

flame through the flame rod (sensor). If the flame is not verified 

within 4 seconds, the gas valve is immediately shut off followed 

by 15-second inter-purge period, then the system returns to 

step 7, if the “Trial for Ignition” dipswitch is set for three (3) tries. 

If the dipswitch is set for one (1) trial, the system will declare 

an error and boiler will require resetting the control. 

10.  Boiler  will  remain  running  until  set  point  is  satisfied.  Once 

satisfied, blower will continue for 15-second post purge period.

11.  Once set point has have been satisfied, the boiler pump will 

continue to run for the programmed post-circulate cycle.

12.  The  control  now  enters  the  idle  state  as  displayed  by  the 

“Standby”  LED.  The  control  will  continue  to  monitor  heat 

demand and state of other system devices. Upon a drop of 

water temperature below the set parameters, the control will 

return to step 5 and repeat the entire operating cycle. Note: 

Any fault detection, during standby or running modes, will halt 

the heating sequence and shift the system to the service mode 

where the detected fault will be displayed.

NOTE:  In  standby  and  running  modes  the  system  constantly 

monitors  the  signals  and  the  internal  operation  for  faults. Any 

detected fault will halt the heating sequence and shift the system 

to the service mode, where the detected fault will be displayed.

TEMPERATURE SETPOINTS (SYSTEM CONTROL ALGORITHM)

The boiler has a hysteresis type control, which means that it will 

begin  heating  the  water  when  the  temperature  sensed  by  the 

control  probe  (inlet  or  tank)  falls  below  the  operating  setpoint 

minus the differential setpoint. It will stop heating the water when 

the temperature rises to the operating setpoint. 

UIM OPERATING PROCEDURES

FIGURE 4.  UIM, USER INTERFACE MODULE

The UIM receives commands from user and displays operational 

information to user via an LCD (liquid crystal display) up to eleven 

LED’s, and five touch switches.  The LCD provides information 

to user by use of 10 menu-activated screens. Within each of the 

screens, helpful information can be displayed by pressing “Help” 

button. The LED’s visually inform user about the mode the system 

is in. The touch switches allow user to control operation of system. 

The operation of these parts is described in the following section:

UIM Screens:

On all screens a double vertical bar appears on right side of display 

each time a key is touched to indicate that a key has been activated. 

On several screens an indicator “>” appears on left side of display 

to indicate active line. The “Up/Down” keys are used to move the 

indicator to the desired line and the “Select” key is pressed to select 

the line. Also, on most of the screens, up/down arrows appear on 

the right side of the screen to indicate that there is additional lines 

either above or below the displayed four lines.

• 

Menu Screen:

  Displayed when the user presses the “Menu” key.  This screen 

is the selection point for the other 9 screens.

MCB - Three position Dipswitch SW2:

This dipswitch is similar to the FCB dipswitches described below, but with only three switches being used: the number of blower speeds 

(switch #3), Hi Gas option (switch #2) and a spare (switch #1).  Only the blower speed and Hi Gas options are the required selection, 

within the MCB, see Figure 2.

     Dipswitch Function

Dipswitch Position

     SW2 P1: Spare:

            NOT USED

        NOT USED

     SW2 P2: Hi Gas pressure switch:

            On = Yes

        Off = No

     SW2 P3: Number of Blower Speeds:

            NOT USED

        NOT USED

Example of Dipswitch configuration: 

No High Gas, 1 blower speed.

Summary of Contents for VB 1500

Page 1: ...one in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and s...

Page 2: ...ning Procedure Mechanical Removal of Deposits 22 Replacement Parts 22 LIMITED WARRANTY 23 TABLE OF CONTENTS 2 safe installation use and service 3 APPROVALS 3 GENERAL SAFETY 4 INTRODUCTION 5 INSTALLATI...

Page 3: ...hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...etup and instructions before lighting Failure to implement the proper setup will result in improper and inefficient operation of the appliance resulting in production of increased levels of carbon mon...

Page 5: ...ion The installation must conform to all instructions contained in this manual and the local code authority having jurisdiction These should be carefully followed in all cases Authorities having juris...

Page 6: ...e horizontally vented gas fueled heating appliance or equipment The sign should read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECT...

Page 7: ...DB F3 7 5 AMP FUSE MCB II F1 24VDC GENERATION MCB II K6 RELAY COIL MCB II MR HIGH LIMIT FLOW SWITCH LWCO SWITCH OPTIONAL LOW GAS SWITCH HIGH GAS SWITCH OPTIONAL EXTERNAL ENABLE OPTIONAL POWER ACC PROV...

Page 8: ...LE EXT ENABLE DISABLE COM NO COM NC NO COM COM NC ON OFF POWER RELAY NO COM G W W BK BK BK BK BK W 24VAC HOT W BK 24VAC RTN G GROUND F CAT 5 CABLE R G BK W MCB II DETAIL A Part of J BOX VB VW 1500 200...

Page 9: ...W UNITS COME EQUIPPED WITH PUMP VB UNITS DO NOT 24VAC COM PUMP RELAY A BK F 0 WIRING DIAGRAM TRANSFORMER 120 24 VAC MODULATING CONTROL BOARD II MCB II J20 or J21 J16 1 2 6 7 J24 F1 7 5A 24VAC J3 1 2 3...

Page 10: ...and permit pressure to be established by the pressure reducing valve 2 Vent all high points in system to purge system of air Provisions should be made to permit manual venting of radiators or convecto...

Page 11: ...water temperature or 20 F 11 C differential whichever has the higher inlet temperature is attained b If the inlet water temperature is greater than 120 F 49 C and the 20 F 11 C differential is not pre...

Page 12: ...12 LIGHTING AND OPERATING INSTRUCTIONS...

Page 13: ...efully adjust the low fire gas setting to achieve the CO2 level prescribed in above reference table Note The rotation of the Low Fire adjustment is opposite of the High Fire as follows Clockwise rotat...

Page 14: ...t will operate with the voltage and current level provided Pump MCB 120VAC required on systems that do not have an external pump Provides electrical power to directly operate a pump or the coil of an...

Page 15: ...idle state as displayed by the Standby LED The control will continue to monitor heat demand and state of other system devices Upon a drop of water temperature below the set parameters the control wil...

Page 16: ...when the fault state is exited Hard Fault State See Fault Description section for list of soft and Auto Reset faults The pump remains on for the selected post circulate time to cycle the hot water ou...

Page 17: ...soft lockout condition will occur and burner will be shut off This fault condition is automatically cleared when temperature drops below high limit setpoint minus high limit differential AUTO HIGH LI...

Page 18: ...nwards in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of...

Page 19: ...the MCB and reading the resistance across the two active pinsontheconnectoratthe end of the probe cable The value should be approximately 0 ohms when the temperature of the probe is less than 220 F L...

Page 20: ...unction of the servo pressure regulator Replace the valve and add a gas filter in front of the new valve preventative maintenance This is a pre mix burner system The flame is not supposed to be direct...

Page 21: ...to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber coupling on the blower adaptor in order to move the blower 4 Loosen the seven bolts on the blower adapter at...

Page 22: ...xist As the water is heated these tend to drop out depositing as scale or lime This scale must be removed before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime r...

Page 23: ...his boiler under state or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts...

Page 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: