Start up
The electronic control will then attempt to ignite the burner again three consecu-
tive times. If this has not succeeded after three times, the electronic control will
temporarily switch off. The control will automatically reset after an hour and the
above-mentioned cycle will be repeated until a maximum of 9 ignition attempts.
If the burner still has not been ignited, consult
(9 “Errors”)
.