T-M32 / T-M32 ASME Service Manual
Ver. 1.03
61
CONFIDENTIAL
3. Example: Set temperature = 120˚F in a 20-unit system and priority unit is No. 1
(See the table below)
To activate additional T-M32’s
To reduce number of activated T-M32’s
Flow rate
Flow rate
Unit No.
GPM
L/min
Unit No.
GPM
L/min
No.1 ON
0.5
1.9
No.20 OFF
62
234
No.2 ON
3
13
No.19 OFF
58
221
No.3 ON
7
26
No.18 OFF
55
208
No.4 ON
10
39
No.17 OFF
52
195
No. 5 ON
14
52
No.16 OFF
48
182
No. 6 ON
17
65
No.15 OFF
45
169
No. 7 ON
21
78
No.14 OFF
41
156
No. 8 ON
24
91
No.13 OFF
38
143
No.9 ON
27
104
No.12 OFF
34
130
No.10 ON
31
117
No.11 OFF
31
117
No.11 ON
34
130
No.10 OFF
27
104
No.12 ON
38
143
No.9 OFF
24
91
No.13 ON
41
156
No.8 OFF
21
78
No.14 ON
45
169
No.7 OFF
17
65
No.15 ON
48
182
No.6 OFF
14
52
No.16 ON
52
195
No.5 OFF
10
39
No.17 ON
55
208
No.4 OFF
7
26
No.18 ON
58
221
No.3 OFF
3
13
No.19 ON
62
234
No.2 OFF
2.0
7.6
No.20 ON
65
247
No.1 OFF
0.4
1.5