background image

8

Where a separate vent connection is not available and the
vent pipe from the heater must be connected to a common
vent with an oil burning furnace, the vent pipe should enter
the smaller common vent or chimney at a point above the
large vent pipe.

MULTIPLE HEATER MANIFOLD

When horizontally manifolding two or more heaters vent as
shown in Figure 8.  Refer to NFPA 54/ANSI Z223.1 for venting
multiple heaters.

FIGURE 8

WATER LINE CONNECTIONS

This manual provides detailed installation diagrams (see pages
12-17 of this manual) for typical methods of application for the
water heaters.

The water heater may be installed by itself, or with a separate
storage tank, on both single and two-temperature systems.
When used with a separate storage tank, the circulation may be
either by gravity or by means of a circulating pump.  When a
circulating pump is used it is important to note that the flow rate
should be slow so that there will be a minimum of turbulence
inside the heater.

If a water heater is installed in a closed water system, contact
the water supplier or local plumbing inspector on how to control
this situation.

WATER (POTABLE) HEATING

AND SPACE HEATING

1. All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

2. Toxic chemicals, such as those used for boiler treatment,

shall NEVER be introduced into this system.

3. This unit may NEVER be connected to any existing heating

system or component(s) previously used with a non-potable
water heating appliance.

4. When the system requires water for space heating at

temperatures higher than required for domestic water
purposes, a tempering valve must be installed.  Please refer
to installation diagrams on pages 12 thru 17 of this manual
for suggested piping arrangements.

 

CAUTION

A closed system will exist if a check valve (without bypass),
pressure reducing valve (without bypass), or a water meter

(without bypass) is installed in the cold water line between
the water heater and street main (or well).

Excessive pressure may develop in such closed systems,
causing premature tank failure or intermittent relief valve
operation.  This is not a warranty failure.  An expansion tank
or a similar device may be required in the inlet supply line
between the appliance and the meter or valve to compensate
for the thermal expansion of the water.

SYSTEM CONNECTIONS

The system installation must conform to these instructions and
to the local code authority having jurisdiction.  Good practice
requires that all heavy piping be supported.

THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed as shown
in the installation diagrams.

Thermometers are installed in the system as a means of
detecting the temperature of the outlet water supply.

RELIEF VALVE

This water heater is equipped with a combination
temperature-pressure relief valve that complies with the standard
for relief valves and automatic gas shutoff devices for hot water
supply system, ANSI Z21.22.   

FOR SAFE OPERATION OF THE

WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED
OR PLUGGED.

ASME ratings cover pressure relief capacities.  A.G.A. ratings
cover release rate with temperature actuation.

In addition to the appliance relief valve, each remote storage
tank which may be used in conjunction with this appliance shall
also be installed with a properly sized, rated and approved
combination temperature (ANSI) and pressure (ASME) relief
valve(s).

 WARNING

THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE
PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH
MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION,
SYSTEM OR HEATER DAMAGE.  NO VALVE IS TO BE PLACED
BETWEEN THE RELIEF VALVE AND TANK.

Your local code authority may have other specific relief valve
requirements.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO
DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING
OR WATER DAMAGE.  THIS LINE MUST NOT BE REDUCED FROM
THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN
VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN
FREEZING AREAS.  DO NOT THREAD OR CAP THE END OF THIS
LINE.  RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT
THE PURPOSE OF THE VALVE AND IS UNSAFE.  DISCHARGE
LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE
OF BOTH THE VALVE AND LINE.

See SERVICE INFORMATION section for procedure and
precautions.

Summary of Contents for SBD 30 150

Page 1: ...ENCE Printed in U S A 1004 PART NO 196310 001 500 LINDAHL PARKWAY ASHLAND CITY TN 37015 www statewaterheaters com CAUTION TEXT IN BLACK BOLD TYPE OR UNDERLINED CONTAINS INFORMATION RELATIVE TO YOUR SA...

Page 2: ...ence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 documents are available from the Na...

Page 3: ...lure of water heater is due to a corrosive atmosphere Refer to the limited warranty for complete terms and conditions IMPROPER COMBUSTION WARNING ATTICAND OREXHAUSTFANSOPERATINGONTHEPREMISES WITH AWAT...

Page 4: ...As elevation above sea level is increased there is less oxygen per cubic foot of air Therefore the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxy...

Page 5: ...ting leading outside The exhaust inducer is equipped with a gravity controlled damper to reduce the amount of heat loss through the flue improving efficiency FIGURE5 EXHAUSTINDUCER CIRCULATING PUMP A...

Page 6: ...NOT RESULT IN DAMAGE TO THE ADJACENTAREAORTOLOWERFLOORSOFTHESTRUCTURE WHEN SUCH LOCATIONS CANNOT BEAVOIDED ASUITABLE DRAINPANSHOULDBEINSTALLEDUNDERTHEHEATER Such pans should be fabricated with sides a...

Page 7: ...nted in compliance with all local codes the current revision of the National Fuel Gas Code ANSI Z223 1 and with the Category I Venting Tables If any part of the vent system are exposed to ambient temp...

Page 8: ...cessive pressure may develop in such closed systems causing premature tank failure or intermittent relief valve operation This is not a warranty failure An expansion tank or a similar device may be re...

Page 9: ...ION IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLYTINNEDANDCERTIFIEDFORGASSERVICE BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEANONTHEINSIDE TOTRAPANYDIRTORFOREIGNMATERIALINT...

Page 10: ...t pressure tap of automatic gas valve while heater is operating FIGURE10 SINGLEUNITWIRINGDIAGRAM HEATER WIRING All electrical work must be installed in accordance with the latest version of the Nation...

Page 11: ...temperature and pressure relief valve of adequate capacity is installed on the heater The locations shown in the installation diagrams on the following pages are typical The discharge opening of the t...

Page 12: ...LD NOT EXCEED SAFE USE TEMPERATUREAT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FO...

Page 13: ...E TOGGLESWITCHMUSTBECLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOTOPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALLLINETEMPERATURECONTROLINANUNINSULATED TEEBEYONDTHEDISHWASHINGMACH...

Page 14: ...ons shown in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of...

Page 15: ...OTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Page 16: ...ERS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHE...

Page 17: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Page 18: ...n burner before going into lockout After the controller tries three times it will wait one hour before trying to light the unit again This cycle will continue until the main burners are ignited or the...

Page 19: ...tes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go on to the next step 7 Turn gas control knob counterclockwise to ON...

Page 20: ...o faucets to limit hot water temperatures Contact a licensed plumber or the local plumbing authority The water temperature is controlled by a thermostat see Figure 3 which has two sensing elements One...

Page 21: ...ecrease gas pressure and input rate 4 Clock the meter as in step 2 above 5 Repeat steps 3 and 4 until the specified input rate is achieved 6 Turn the gas control knob to PILOT Remove the pressure gaug...

Page 22: ...e inner cover for cleaning inspection or removal of inner parts you obtain two new nipple collars part no 74060 The nipple collars on the heater will usually be damaged when removed New pipe collars w...

Page 23: ...LIMINGUSINGFLO JUGMETHOD UN LIME in the 5 gallon size is recommended for deliming UN LIME with the necessary hoses and fittings to delime your heater is also available as a kit Up N Down Transfer Kit...

Page 24: ...1 800 821 2017 or visit our website at www statewaterheaters com When ordering parts be sure to state the quantity part number and description of the items including the complete model and serial numb...

Page 25: ...engages Prover Switch Ignition Control Board provides power to Silicon Nitride Ignitor Silicon Nitride Ignitor warms up for 20 seconds Ignition Control Board opens Gas Valve Ignition Control Board sh...

Page 26: ...Replace dual bulb controller if differential is too wide greater than 4 F Heater recovery is slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Dra...

Page 27: ...on device check valves etc is installed in the cold water supply the heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operationa...

Page 28: ...28 500 Lindahl Parkway Ashland City TN 37015 Phone 800 821 2017 Fax 800 644 9306 www statewaterheaters com...