![A.O. Smith IT - 300 Installation, User And Service Manual Download Page 33](http://html.mh-extra.com/html/a-o-smith/it-300/it-300_installation-user-and-service-manual_3045015033.webp)
IT 300
Installation, Service and User Manual
33
4
Maintenance
4.1 Preparation for
maintenance
4.2 Water-side
maintenance
4.2.1
Warning
Maintenance may only be carried out by a competent person.
At each service, the water heater undergoes maintenance on water side. The
maintenance must be carried out in the following order.
1. Preparation for maintenance
2. Water-side maintenance
3. Finalizing maintenance
Note
Before ordering spare parts, it is important to write down the installation type, water
heater model and the full serial number of the water heater. These details can be
found on the rating plate. Only by ordering with this information can you be sure
receiving the correct spare parts.
The preparation for maintenance consists out of testing and checking if all
components are still working properly, complete the following steps:
1. Test the operation of the overflow valve of the protected cold supply setup. The
water should discharge out.
2. Check the drainage pipes from the discharge points of all valves and remove any
scale deposits that may be present.
3. Drain the water heater.
Water-side maintenance consists of descaling and cleaning the tank and checking
the anodes.
Descaling and cleaning the tank
Scale and lime build-up prevent effective conduction of the heat to the water.
Periodic cleaning and descaling prevents build-up of these deposits. This increases
the service life of the water heater, and also improves the heating process.
Take the rate of scale formation into account when deciding on the service interval.
Scale formation depends on the local water composition, the water consumption and
the water temperature setting. A water temperature setting of maximum 60°C is
recommended for the prevention of excessive scale build-up.
To guarantee a good, watertight seal around the cleaning opening, replace the
gasket, washers, bolts and, if necessary, the lid with new parts before reassembly.
Spare parts are obtainable from the supplier/manufacturer.
To simplify descaling and cleaning of the tank, the water heater is equipped with a
cleaning opening.
Summary of Contents for IT - 300
Page 4: ...IT 300 4 ...
Page 6: ...IT 300 Installatie Service en Gebruikershandleiding 6 ...
Page 8: ...IT 300 Installatie Service en Gebruikershandleiding 8 ...
Page 12: ...IT 300 Installatie Service en Gebruikershandleiding 12 ...
Page 22: ...IT 300 Installation Service and User Manual 22 ...
Page 24: ...IT 300 Installation Service and User Manual 24 ...
Page 28: ...IT 300 Installation Service and User Manual 28 ...
Page 38: ...IT 300 Notice d installation Mode d emploi Notice d entretien 38 ...
Page 40: ...IT 300 Notice d installation Mode d emploi Notice d entretien 40 ...