Installation
20
Instruction manual GWV
3
is
3.3
Environmental
conditions
Caution
An open appliance may not be used in rooms where chemical substances
are stored or used due to the risk of explosion and corrosion of the appliance.
Some propellants, bleaching agents and degreasing agents etc. disperse
vapours that are explosive and/or cause accelerated corrosion. If the appliance
is used in a room in which such substances are present, the warranty will be
void.
The appliance is suitable for both open and closed combustion.
For closed combustion, the air supply required is independent of the room in
which it is installed. In this event, there are no additional ventilation
requirements. Appliance types possible here are C13 and C33.
The appliances can also be installed as open appliances and may then only
be placed in an open boiler room. The appliance type is B23.
3.3.1
Air humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. The table
shows the environmental conditions that must be adhered to for correct
functioning of the electronics present in the appliance to be guaranteed.
Air humidity and ambient temperature specifications
3.3.2
Maximum floor loading
Allow for the weight of the appliance and the storage tank with respect to the
maximum floor loading; refer to the tables.
Specifications of the weight of the appliance, with respect to the maximum floor
loads.
Specifications of the weight of the storage tank, with respect to the maximum
floor loads.
Air humidity and ambient temperature
Air humidity
max. 93% RV at +25°C
Ambient temperature
Functional: 0 < T < 60°C
Weight of the appliance (kg)
GWV 120
225
GWV 150
250
GWV 200
300
Weight of the storage tank filled with water (kg)
ST 400
505
ST 500
630
ST 600
855
ST 750
965
ST 1000
1315
Summary of Contents for GWV - 120
Page 2: ...www aosmithinternational com your installer ...
Page 4: ...4 Instruction manual GWV gis ...
Page 8: ...Table of contents 8 Instruction manual GWV ...
Page 12: ...Introduction 12 Instruction manual GWV 1 gis ...
Page 40: ...Installation 40 Instruction manual GWV 3 is ...
Page 42: ...Conversion to a different gas category 42 Instruction manual GWV 4 is ...
Page 46: ...Filling 46 Instruction manual GWV 5 gis ...
Page 58: ...Starting and running 58 Instruction manual GWV 9 gis ...
Page 60: ...Shutting down 60 Instruction manual GWV 10 gis ...
Page 72: ...Service program 72 Instruction manual GWV 12 is ...
Page 86: ...Troubleshooting 86 Instruction manual GWV 13 gis ...
Page 88: ...Maintenance frequency 88 Instruction manual GWV 14 is ...
Page 98: ...Appendices 98 Instruction manual GWV 17 is ...
Page 100: ...Instruction manual GWV 100 ...
Page 102: ...0307 971 4 0 UK Index Instruction manual GWV ...