background image

16

discharge opening must not be blocked or reduced in size under any 

circumstances. Excessive length, over 30 feet (9.14 m), or use of 

more than four elbows can cause restriction and reduce the discharge 

capacity of the valve.

No valve or other obstruction is to be placed between the 

Temperature-Pressure Relief Valve and the tank. Do not connect 

discharge piping directly to the drain unless a 6” (15.2 cm) air gap is 

provided. To prevent bodily injury, hazard to life, or property damage, 

the relief valve must be allowed to discharge water in adequate 

quantities should circumstances demand. If the discharge pipe is 

not  connected  to  a  drain  or  other  suitable  means,  the  water  flow 

may cause property damage.

CAUTION

• 

Temperature-Pressure Relief Valve discharge

  pipe must terminate at adequate drain.

Wa

ter Damage Hazard

t&p valve discharge pipe requirements:

•  Should not be smaller in size than the outlet pipe size of the valve, or

 

  have any reducing couplings or other restrictions.

•  Should not be plugged or blocked.
•  Should not be exposed to freezing temperatures.
•  Should be of material listed for hot water distribution.
•  Should be installed so as to allow complete drainage of both the

 

  Temperature-Pressure Relief Valve and the discharge pipe.

•  Must terminate a maximum of six inches above a floor drain or external

 

  to the building. In cold climates, it is recommended that the discharge 

  pipe be terminated at an adequate drain inside the building.

•  Should not have any valve or other obstruction between the relief

 

  valve and the drain.

DANGER

• 

Burn hazard.

• 

Hot water discharge.

• 

Keep clear of Temperature-

  Pressure Relief Valve

  discharge outlet.

The Temperature-Pressure Relief Valve must be manually operated at 

least twice a year. Caution should be taken to ensure that (1) no one 

is in front of or around the outlet of the Temperature-Pressure Relief 

Valve discharge line, and (2) the water manually discharged will not 

cause any bodily injury or property damage because the water may be 

extremely hot. If after manually operating the valve, it fails to completely 

reset and continues to release water, immediately close the cold water 

inlet to the water heater, follow the draining instructions in this manual, 

and replace the Temperature-Pressure Relief Valve with a properly 

rated/sized new one.

note:

 The purpose of a Temperature-Pressure Relief Valve is to 

prevent excessive temperatures and pressures in the storage tank. 

The T&P valve is not intended for the constant relief of thermal 

expansion. A properly sized thermal expansion tank must be installed 

on all closed systems to control thermal expansion, see Closed Water 

Systems and Thermal Expansion on page 14 and 15.

If you do not understand these instructions or have any questions 

regarding the Temperature-Pressure Relief Valve call the 

toll free number listed on the back cover of this manual for  

technical assistance.

hIGh altItude InstallatIon

This heater is approved for operation up to 5,300 feet (1,615 m) 

without alteration. High altitude models are available from the factory 

for elevations between 5,300 feet (1,615 m) and 10,100 feet (3,079 

m).  For  elevations  above  10,100  feet  (3,079  m)  the  input  rating 

should be reduced at the rate of 4 percent for each 1,000 feet (305 

m) above sea level which requires replacement of the burner orifice 

in accordance with National Fuel Gas Code (ANSI Z223.1/NFPA  54).  

Contact your local gas supplier for further information.

Failure to replace standard orifice with a high altitude orifice when 

installed above 10,100 feet (3,079 m) could result in improper and 

inefficient operation of the appliance, producing carbon monoxide 

gas in excess of safe limits, which could result in serious injury or 

death. Contact your gas supplier for any specific changes which 

may be required in your area. 

Gas pIpInG

Fire and Explosion Hazard

Do  not   use  water heater with any

gas other than the gas shown on

the rating plate.

Excessive  pressure to gas control

valve can cause serious injury or death
Turn off gas lines during installation.

Contact qualified installer or 

service agency.

Make sure the gas supplied is the same type listed on the model 

rating plate. The inlet gas pressure must not exceed 14 inch  water 

column (3.5 kPa) for natural and propane gas (L.P.). The minimum 

inlet gas pressure shown on the rating plate is that which will permit 

firing at rated input.

All gas piping must comply with local codes and ordinances or with the 

National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper or brass 

tubing and fittings (except tin lined copper tubing) should not be 

used.
If the gas control valve is subjected to pressures exceeding 1/2 psi 

(3.5 kPa), the damage to the gas control valve could result in a fire 

or explosion from leaking gas.
If the main gas line Shuttoff serving all gas appliances is  

used,  also  turn  “off”  the  gas  at  each  appliance.  Leave  all 

gas  appliances  shut  “off”  until  the  water  heater  installation 

 

is complete.

Summary of Contents for Gphe 50

Page 1: ...L DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER RESIDENTIAL GAS WATER HEATERS For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER POWER VENTED GAS MODELS W HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED MOBILE HOMES MODEL GPHE 50 SERIES 100 Low Lead Content 500 Tennessee Walt...

Page 2: ...y alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoid the risk of injury The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California...

Page 3: ...3 GENERAL SAFETY INFORMATION ...

Page 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk ...

Page 5: ... Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local codes the National Electrical Code NFPA 70 4 If after reading this manual you have any questions or do not understand any portion of the instructions call the local gas utility or the manufacturer whose name appears on the rati...

Page 6: ... feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructions Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation...

Page 7: ...ng 4 Places Shown DD Plastic Top EE On Off Switch FF Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shuttoff Valve H Ground Joint Union J Sediment Trap K Outer Door L Union M Inlet Water Shuttoff Valve N Cold Water Inlet O Inlet Dip Tube P Temperature Pressure Relief Valve HH Bushing II Nipple JJ ...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1A ...

Page 9: ...nship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use then special precautions must be taken In addition to using lowest possible temperature setting that satisfies demand of application a Mixing Valve should be installed at w...

Page 10: ...stalled Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shuttoff device used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to...

Page 11: ...orine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater The results can be hazardous and also cause product failure INSULATION BLANKETS Insulation blankets are available to the general public for external use on gas water heaters but are not necessary w...

Page 12: ...e size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air should be provided to replace the exhausted air When an exhaust fan is installed in the same space with a water heater sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan Undersized openin...

Page 13: ... a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 18 27 for complete venting installation instructions FIGURE 9 The confined space should be provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing with...

Page 14: ...de requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water system to be a closed system CHEMICAL VAPOR CORROSION CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILURE ...

Page 15: ...on 6 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along the length of the insulation to ensure that it is fully seated around the pipe Also ensure that the base of the insulation is flush with the water heater Once seated secure the insulation with duct tape electrical tape or equivalent 7 Repeat steps 5 and 6 for the hot water outlet pipe 8 Add...

Page 16: ...excessive temperatures and pressures in the storage tank The T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems and Thermal Expansion on page 14 and 15 If you do not understand these instructions or have any questions regarding the Temperature Pre...

Page 17: ...tem by closing its individual manual Shuttoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping to the gas control valve of water heater can be accomplished by either of two methods shown in Figures 12 and 13 FIGURE 12 GAS PIPING WITH FLEXIBLE CONNECTOR FIGURE 13 GAS PIPING WITH ALL BLAC...

Page 18: ... These PVC parts should be assembled with ASTM D 2564 grade cement Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may be rotated to a different orientation as needed for the specific installation requirements Note the rotational orientation of each part by ma...

Page 19: ... L Clearance above paved sidewalk or paved driveway located on public property 7 feet 2 13 m F Clearance to outside corner 2 feet 60 cm M Clearance under veranda porch deck or balcony 12 inches 30 cm G Clearance to inside corner 18 inches 45 cm In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is lo...

Page 20: ...of vent pipe Check system for signs of sagging or other stresses in joints as a result of misalignment of any components in system If any of these conditions are found they must be corrected in accordance with venting instructions in this manual before completing installation and putting water heater into service NOTE A For water heaters in locations with high ambient temperatures above 100 F it i...

Page 21: ... tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 6 Make sure the ON OFF switch is in the OFF position and that the outer harness is connected from the blower control box to the connector on the bottom side of the gas valve 7 If the outer harness is not fact...

Page 22: ...line This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLATIONS FIGURE 18 Cut a length of PVC pipe about 3 5 inches 8 9 cm longer than wall thickness at the opening Glue vent terminal to this section of pipe Slide the wall plate over the pipe to stop agains...

Page 23: ...tallation of a snorkel it is necessary to use two 90 elbows that shall be considered along with the additional vent pipe when calculating maximum equivalent feet of venting INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed the equivalent feet of pipe as listed in Table 1 Provide support for...

Page 24: ...C cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4 Make sure the VAA and vent pipe is supported securely to a permanent fixture stud or wall Use standard support straps not supplied with kit that may be found at a local hardware store Failure to pr...

Page 25: ...A and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for Vertical Vent with 3 or 4 inch Pipe Installation of VAA with 3 4 inch Pipe for Horizontal Vent Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths...

Page 26: ... above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC or CPVC surfaces A chemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10 20 by weight virgin PVC mater...

Page 27: ...d make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and prepares the PVC or CPVC for the solvent cementing step Move quickly and without hesitation to the cementing procedure while the surfaces are still wet with primer E Application of solvent cement Apply...

Page 28: ...28 ...

Page 29: ... located in an area where the general public does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing the COOLER button decreases temperature and pressing the HOTTER button increases the temperature Setting water heater temperature at 120 F 49 C Approx mark on...

Page 30: ...eriod of time generally two weeks or more Hydrogen gas is extremely flammable and explosive To prevent the possibility of injury under these conditions we recommend the hot water faucet located farthest away be opened for several minutes before any electrical appliances which are connected to the hot water system are used such as a dishwasher or washing machine If hydrogen gas is present there wil...

Page 31: ...rod which will slowly deplete due to electrolysis prolonging the life of the water heater by protecting the glass lined tank from corrosion Adverse water quality hotter water temperatures high hot water usage and water softening methodscanincreasetherateofanoderoddepletion Oncetheanoderod is depleted the tank will start to corrode eventually developing a leak Certain water conditions will cause a ...

Page 32: ...ure Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death DRAINING AND FLUSHING It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup The water heater should be drained if being shut down during freezing temperatures See Typical Installation ...

Page 33: ...oose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances water lines or ground seepage should also be checked To check where threaded portion enters tank insert cotton swab between jacket opening and fitting If cotton is wet follow Draining instructions in th...

Page 34: ...Sheet 34 Wire Screen 3 35 Wire Screen 4 36 Wall Plate 4 37 Flexible Tubing REPAIR PARTS LIST Nowthatyouhavepurchasedthiswaterheater shouldaneedeverexistfor repairpartsorservice simplycontactthecompanyitwaspurchasedfromor direct from the manufacturer listed on the rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on reque...

Page 35: ...he water heater 3 Ensure maximum number of elbows or maximum equivalent feet of vent or intake air pipe have not been exceeded per the installation instructions in the manual that came with the water heater 4 Ensure there are no obstructions in the vent or intake air pipe 5 Open igniter circuit 1 Check wiring to the hot surface igniter assembly replace igniter assembly if wiring is damaged or worn...

Page 36: ...er open or shorted 1 Turn off power to the water heater Ensure all FV sensor wiring the ignitor assembly plug and the ignitor assembly socket on the bottom of the Intelli Vent control are making good contact Repair or replace any worn damaged components that are not making good connection 2 Replace the FV sensor 15 Self diagnostic check has detected the presence of fl ammable vapors from the FV fl...

Page 37: ...37 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES ...

Page 38: ...38 TROUBLESHOOTING GUIDELINES NOTES ...

Page 39: ...n of it in a modified form or any attempt to repair tank leaks or parts will void this warranty servIce and laBor responsIBIlItY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLACEMENT WATER HEATER OR PART THEREOF THEOWNERISRESPONSIBLEFORALLOTHERCOSTS Such costs may include but are not limited to a Labor charges for service removal or reinstallation of the water heater or part th...

Page 40: ...40 Copyright 2013 A O Smith Corporation All rights reserved 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com ...

Reviews: