A.O. Smith FPSH - 75 Owner'S Manual Download Page 16

16

If the heater is to be shut off and exposed to freezing
temperatures, it must be drained.  Water, if left in the tank and
allowed to freeze, will damage the heater.

Turn off the gas and cold water inlet valve to the heater.

Open a nearby hot water faucet and the heater drain valve.

BE CAREFUL TO GRASP THE DRAIN VALVE HANDLE SO
THAT THE HAND IS NOT EXPOSED TO HOT WATER.  IF
DESIRED, A HOSE MAY BE CONNECTED TO THE DRAIN
VALVE TO CARRY THE WATER AWAY.

 

  WARNING:  The water CAN BE HOT.

The drain valve must be left open during the shutdown period.

• To restart heater, refer to the instructions under OPERATION.

CONDENSATION

Water vapor can condense on the cooler surfaces of the tank
forming droplets, these drip into the fire or run out on the floor.
This is common at the time of startup after installation, during
periods of time when incoming water is very cold, or the heater
may be undersized for the requirements.

Droplets from the bottom of the flue may be due to corrosive
combustion products or improper vent.  Check with your dealer
for more information.

CATHODIC PROTECTION-ANODE

The anode rod is used to protect the tank from corrosion.  Most
hot water tanks are equipped with an anode rod.  The
submerged rod sacrifices itself to protect the tank.  Instead of
corroding the tank, water ions attack and eat away the anode
rod.  This does not affect the water’s taste or color.  The rod must
be maintained to keep the tank in operating condition.

Anode deterioration depends on water conductivity, not
necessarily water condition.  A corroded or pitted anode rod
indicates high water conductivity and should be checked and/or
replaced more often than an anode rod that appears to be intact.
Replacement of a depleted anode rod can extend the life of your
water heater.  Inspection should be conducted by a qualified
technician, and at a minimum should be checked annually after
the warranty period.

A hydrogen sulfide (rotten egg) odor may result if water contains
high sulfate and/or minerals.  Chlorinating the water supply
should minimize the problem.  (See EXTENDED NON-USE
PERIODS).

NOTE:

 Anode must remain installed (except for inspection) to

avoid shortening tank life.  See LIMITED WARRANTY.  Replace
as necessary.

SERVICE AND REPAIR

The A.O. Smith water heater requires no special care other than
the normal maintenance as noted above.  If you are having a
problem with your water heater, before calling for service please
refer to the following TROUBLESHOOTING sections.  If service
becomes necessary, contact your dealer, installer or an
authorized service agent.  Do not attempt to repair the water
heater yourself.  Any work performed by unauthorized personnel
may void the warranty.

If you are having a problem with your A.O. Smith water heater
and are not pleased with the service you received:

First, please contact your dealer or the A.O. Smith authorized
service agent in your area and explain to them why you are
not satisfied.  This will usually correct the problem.

If after working with your dealer or service agent the problem
has not been resolved to your satisfaction, please let us know
by either writing to us at:

A.O. Smith Water Products Company
Service Department
500 Lindahl Parkway
Ashland City, TN 37015-1299

or, going to our website at: 

www.hotwater.com

Please click on: "Contact us",
then click on: "Service"
and leave us a message.

Please be sure to provide the following information when writing
or e-mailing:

• Model Number
• Serial Number
• Date of Original Purchase
• Date Problem Originated
• Explanation of Problem

Also, please be sure to include a daytime telephone number.

TROUBLE SHOOTING

Water heater may exhibit problems that are unrelated to a
malfunction of the water heater itself.  The following information
and tables may serve to answer your question about a problem
that you are having without having to call a service agent.

For your safety, water heater service should be performed only
by a qualified service technician.  Read the GENERAL SAFETY
INFORMATION section first.

WATER HEATING IGNITION SEQUENCE

(Make sure gas and electric power are connected properly)

1) The ignition control module is powered and monitors the

system, waiting for a call for heat from the thermostat.

2) The thermostat calls for heat by reading a resistance value

within a given range directly proportional to water temperature.

3) The Control Module:

a) Check the pressure switches for an open circuit.
b) Energizes the blower.
c)

Checks the pressure switches for a closed circuit to prove
draft.

d) Sends line voltage to the hot surface igniter with a 20-

second warm up period.

e) Opens the gas valve and check the sensing rod for flame.

4) The burner heats the water to the desired thermostat setting.

a) The resistance in the thermostat rises to the value

selected by the temperature control knob.

b) The control module closes the gas valve and 5 seconds

later, removes power from the blower.

5) Cycle is completed.

Summary of Contents for FPSH - 75

Page 1: ...ing instructions as well as the WARNING and CAUTIONS CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE RESIDENTIAL GAS WATER HEATERS OWNER S MANUAL ADIVISION OFA O SMITH CORPORATION www hotwater com GET TO KNOWYOUR WATER HEATER 2 GENERAL SAFETY INFORMATION 3 4 INSTALLATION 4 12 OPERATION 12 14 MAIN...

Page 2: ...ly FPSH 75 with Hot Surface Ignition GET TO KNOW YOUR WATER HEATER A VENT PIPE B ANODE C HOT WATER OUTLET D OUTLET 120 VAC E FLUE BAFFLE F GASSUPPLY G MAINMANUALGAS SHUT OFF VALVE H GROUND JOINT UNION J DIRT LEG K OUTER DOOR L UNION M INLET WATER SHUT OFF VALVE N COLD WATER INLET O INLET DIP TUBE P TEMPERATUREAND PRESSURE RELIEF VALVE Q EMBLEMANDRATING PLATE R INSULATION S VENT TERMINAL T DRAIN VA...

Page 3: ... Go to a neighbor s house leaving your doors open to ventilate the house then call your gas supplier or service agent Keep area clear until a service call has been made At times you may not be able to smell an LP gas leak One cause is odor fade which is a loss of the chemical odorant that gives LP gas its distinctive smell Another cause can be your physical condition such as having a cold or a dim...

Page 4: ... closet having minimum clearances from combustible material of 0 clearance from sides and rear 5 from the front and 12 from the top Standard clearance If clearances stated on the heater differ from standard clearances install water heater according to clearances stated on heater A minimum clearance of 4 must be allowed for access to replaceable parts such as the thermostats drain valve and relief ...

Page 5: ...alve must be installed Please refer to Fig 2 for suggested piping arrangement FIGURE2 CLOSED WATER SYSTEM A closed system will exist if a back flow preventer check valve pressure reducing valve or other similar device is installed in the cold water line between the water heater and the street main or well Excessive pressure may develop due to the thermal expansion of heated water causing premature...

Page 6: ...nual or on water heater With main burner in operation paint pipe joints including flanges pilot gas tubing connections and control inlet and outlet with rich soap and water solution Bubbles indicate gas leak To stop leak tighten flange screws joints and pipe connections Replace part if leak can t be stopped DISCONNECT THE APPLIANCE AND ITS INDIVIDUAL SHUT OFF VALVE FROM THE GAS SUPPLY PIPING SYSTE...

Page 7: ...erving power vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and INSTALLATION OF VENT SYSTEM and with the National Fuel Gas Code and local codes PLANNING THE VENT SYSTEM Plan the route of the vent system from the discharge of the blower to the...

Page 8: ...ent terminal by using the cover plate as a template to mark the hole for the vent pipe to pass through the wall BEWARE OF CONCEALED WIRING AND PIPING INSIDE THE WALL 2 If the Vent Terminal is being installed on the outside of a finished wall it may be easier to mark both the inside and outside wall Align the holes by drilling a hole through the center of the template from the inside through to the...

Page 9: ...sure E Splice field wiring into existing wiring using code authorized method wire nuts etc F Be certain that neutral and line connections are not reversed when making these connections G Ground heater properly This water heater must be grounded on accordance with the National Electric Code ANSI NPA70 and or local codes These must be followed in all cases The water heater must be connected to a gro...

Page 10: ...be supported every 5 feet of vertical run and every 3 feet of horizontal run All piping and fittings must be joined by the proper procedures as described under VENT PIPE PREPARATION FIGURE9 IMPORTANT The vent system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the National Fuel Gas Code ANSI Z223 1 and as listed below 1 Vent Termination m...

Page 11: ... type of cutter is used the flare on the end must be completely removed STEP A NOTE Power saws should be specifically designed to cut plastic pipe B Deburring Use a knife plastic pipe deburring tool or file to remove burrs from the end of small diameter pipe Be sure to remove all burrs from around the inside as well as the outside of the pipe A slight chamfer bevel of about 10 15 should be added t...

Page 12: ...uld not be disturbed immediately after the cementing procedure and sufficient time should be allowed for proper curing of the joint Exact drying time is difficult to predict because it depends on variables such as temperature humidity and cement integrity For more specific information you should contact your solvent cement manufacturer STEPG OPERATION WARNING DO NOTATTEMPTTO OPERATE WATER HEATER W...

Page 13: ...use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATINGINSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to the lowest setting 3 Turn the ON OFF switch on the blower control box to the OFF ...

Page 14: ...xceed the thermostat setting by up to 30 F If you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing the point of use temperature by mixing cold and hot water are available See figure 2 Also available are inexpensive devices that attach to faucets to limit hot water temperatures Contact a licensed plumber or the local plumbi...

Page 15: ...THE DRAFT Operate the water heater for several minutes and check to see if it is venting properly by passing a lit match or paper near the opening of the Air Mixing Box See figure 11 If the draft is proper the match flame will be drawn into the Air Mixing Box If not the combustion products will tend to extinguish the flame If an improper draft exists do not operate the water heater until proper ad...

Page 16: ...a problem with your water heater before calling for service please refer to the following TROUBLESHOOTING sections If service becomes necessary contact your dealer installer or an authorized service agent Do not attempt to repair the water heater yourself Any work performed by unauthorized personnel may void the warranty If you are having a problem with your A O Smith water heater and are not plea...

Page 17: ...into 115 vac outlet Repair service to outlet Replace switch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more than 30 Equivalent feet of 3 inch pipe or85 equivalent feet of 4 inch pipe installed or vent terminal blockage If at least 102 vac less than 30 eq...

Page 18: ...e water heater off for 10 seconds and then back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas control valve Flame signal sensed out of 1 Replace gas control valve prop...

Page 19: ...urnish the ORIGINAL OWNER a replacement A O Smith water heater of equivalent size and current model or a replacement part for any component part which fails in normal use in accordance with the warranty terms and conditions specified below THE A O SMITH REPLACEMENT MODEL OR PART WILL BE WARRANTED FOR ONLYTHE UNEXPIRED PORTION OFTHE ORIGINAL WARRANTY The warranty period will be determined by the or...