TROUBLESHOOTING
Fault & Alert Messages
DISPLAYED MESSAGE
CONDITION/INDICATES
CHECK/REPAIR
“Energy Cut Out (ECO)”
(Fault Condition)
The control system has detected excessive water
temperature inside the water heater. The ECO high
temperature limit switch activates at 202°F/94°C.
See ECO High Temperature Limit Switch description
on page 37.
Possible Causes:
Plug/socket connection problems
Wiring connection problems
Contactor(s) stuck closed
Contactor coils being energized in standby mode
Defective Immersion Temperature Probe
Water piping problems
•
Check the J5 plug/socket connections at the
CCB ensure they are mating properly and pro-
viding good contact. Check the pins inside the
J5 plug/socket for wear or damage. See CCB
illustration and socket identification on pages 42
- 44. Replace damaged plug connectors/wiring
harness as necessary.
•
Check for pinched or broken wiring between the
Immersion Temperature Probe and the J5 plug/
socket connection on the CCB - repair or
replace damaged wiring as necessary. See
CCB illustration and socket identification on
pages 42 - 44.
•
Check ECO continuity and for 120 VAC to and
from the ECO - see pages 37 - 40. Replace
Immersion Temperature Probe if ECO switch
contacts remain open at normal operating tem-
peratures.
•
Ensure the contactors are not stuck closed - see
page 31.
•
Ensure the contactor coils are not being ener-
gized during standby mode - see pages 32 &
33.
•
Check water system piping; ensure heat is not
being added to the water inside the water heater
being serviced by any other heating appliances
or heat sources.
•
Call the toll free technical support phone num-
ber on the back cover of this manual for further
assistance if the problem has not been cor-
rected after performing the procedures outlined
here.