A.O. Smith COF-199 Installation Setup Manual Download Page 2

2

TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION
RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFORE
USING APPLIANCE.

This is a typical Duraclad oil-fired heater for commercial water heating

FIGURE 1

applications. The principal components of the heater are shown and

identified here. The identification plate illustrations on page 4 interpret

certain markings into useful information. Use these references to identify

the heater and its components

FEATURES AND SPECIFICATIONS

TABLE 2  RECOVERY CAPACITIES, based on 80% efficiency

       TANK

APPROX

U.S Gallons/Hr. and Litres/Hr at TEMPERATURE RISE INDICATED

        CAPACITY

EFF.

40F°

50F°

60F°

70F°

80F°

90F°

100F°

110F°

120F°

130F°

140F°

Model

Btuh

KW

U.S.Gal. Litres

%

22.2C°

27.7C°

33.3C°

38.8C°

44.4C°

50C°

55.5C°

61.1C°

66.6C°

72.2C°

77.7C°

COF

199,000

86

80

GPH

477

381

318

272

238

212

191

173

159

147

136

199

58

326

LPH

1804

1443

1203

1031

902

802

722

656

601

555

516

COF

245,000

86

80

GPH

587

469

391

335

293

261

235

213

196

181

168

245

72

326

LPH

2221

1777

1481

1269

1111

987

889

808

740

683

635

COF

315,000

84

80

GPH

754

604

503

431

377

335

302

274

251

232

216

315/315A

92

318

LPH

2856

2285

1904

1632

1428

1269

1142

1039

952

879

816

COF

385,000

75

80

GPH

922

738

615

527

461

410

369

335

307

284

263

385/385A

113

284

LPH

3491

2793

2327

1995

1745

1551

1396

1269

1164

1074

997

COF

455,000

75

80

GPH

1090

872

727

623

545

484

436

396

363

335

311

455/455A

133

284

LPH

4125

3300

2750

2357

2063

1833

1650

1500

1375

1269

1179

COF

700,000

69

80

GPH

1677

1341

1118

958

838

745

671

610

559

516

479

700/700A

205

261

LPH

6347

5077

4231

3627

3173

2821

2539

2308

2116

1953

1813

*  All tanks are tested at 320 psig working pressure.
** Based on No. 2 fuel oil with a heat content of 140,000 Btu's per gallon at 80% thermal efficiency. Above 2,000 altitude, input
    ratings should be reduced 4% for each 1000' above sea level.

ALL DIMENSIONS IN INCHES/mm
*Model numbers followed by the suffix "A" indicates the optional A.S.M.E. tank construction.

TABLE 1 NOMINAL MODEL DIMENSIONS

                        

COF - 199       COF - 245

 COF - 315/315A

 COF - 385/385A

COF - 455/455A

COF - 700/700A

Dim.

Inches

mm

Inches

mm

Inches

mm

Inches

mm

Inches

mm

Inches

mm

A

74 1/2

1,892

74 1/2

1,892

74 1/2

1,892

73 3/4

1,873

73 3/4

1,873

73 3/4

1,873

B

36 3/4

933

36 3/4

933

36 3/4

933

36 3/4

933

36 3/4

933

36 3/4

933

C

27 3/4

705

27 3/4

705

27 3/4

705

27 3/4

705

27 3/4

705

27 3/4

705

D

2

51

2

51

2

51

2

51

2

51

2

51

E

            3/4 NPT                 3/4 NPT                  3/4 NPT                    3/4 NPT                   3/4 NPT                     3/4 NPT

F

8

203

8

203

8

203

8

203

8

203

10

254

G

26 5/8

676

26 5/8

676

26 5/8

676

24 3/4

629

24 3/4

629

30 3/16

767

H

74 1/2

1,892

74 1/2

1,892

74 1/2

1,892

73 3/4

1,873

73 3/4

1,873

79 3/16

2,011

J

            1 1/2 NPT            1 1/2 NPT                1 1/2 NPT               1 1/2 NPT             1 1/2 NPT                   1 1/2 NPT

K

            1 1/2 NPT            1 1/2 NPT                1 1/2 NPT               1 1/2 NPT             1 1/2 NPT                   1 1/2 NPT

L

22 3/4

578

22 3/4

578

22 3/4

578

23 7/16

595

23 7/16

595

28 7/8

733

Approx.

Shipping

553

251

554

252

554

252

624

283

700

318

739

335

Weight STD.

Lbs

 Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Approx.

Shipping

657

298

742

337

747

339

822

373

Weight ASME

---

---

---

---

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Model

Summary of Contents for COF-199

Page 1: ...MMERCIAL OIL FIRED WATER HEATER FOR HOT WATER SUPPLY Installation Service Maintenance MODELS COF 199 THRU 700A CAUTION TEXTPRINTEDOROUTLINEDINREDCONTAINSINFORMATIONRELATIVE TO YOUR SAFETY PLEASE READ...

Page 2: ...0 2750 2357 2063 1833 1650 1500 1375 1269 1179 COF 700 000 69 80 GPH 1677 1341 1118 958 838 745 671 610 559 516 479 700 700A 205 261 LPH 6347 5077 4231 3627 3173 2821 2539 2308 2116 1953 1813 All tank...

Page 3: ...listed by Underwriters Laboratories Inc Accordingly the burner bears one of the UL labels indicating periodic inspection of the production of this equipment All ASME tanks are built to the standards...

Page 4: ...HEATER NEVER TOUCH ELECTRICAL COMPONENTSWITHWETHANDSOFWHENSTANDINGINWATER WHEN REPLACING FUSESALWAYS USE THE CORRECT SIZE FOR CIRCUIT If it is necessary to reset the safety control depress red button...

Page 5: ...These materials are corrosive at very low concentration levels with little or no odor to reveal their presence Products of this sort should not be stored near the heater Also air which is brought in c...

Page 6: ...10 254 These models are factory supplied with a flue reducer which should be installed on the top cover In venting systems where a continuous or intermittent back positive draft is found to exist the...

Page 7: ...shutoff system actuated by high water temperature CLOSED WATER SYSTEM A closed system will exist if a back flow preventer check valve pressure reducing valve or other similar device is installed in th...

Page 8: ...100 30 4 7 2 1 31 9 4 100 30 4 3 0 9 50 15 2 100 30 4 8 2 4 26 7 9 100 30 4 4 1 2 45 13 7 100 30 4 9 2 7 21 6 4 83 25 2 5 1 5 40 12 1 100 30 4 10 3 0 16 4 8 64 19 5 Two Stage Supply and Return Lines...

Page 9: ...ainst electrical shock from the heater or water system 3 All burners have intermittent ignition as defined by UL ignition is on during the time the burner is on and off when the burner is off 4 Do not...

Page 10: ...includes a circulating pump it may need to be lubricated before operated The tube of lubricant supplied with the pump includes directions for use Field installed circulating pumps should be all bronze...

Page 11: ...hermostat temperature dial fig 17 is accessible by taking off the access cover and removing the control cover The dial is adjustable and may be set for 120 48 9 C to 180 F 82 2 C water temperature but...

Page 12: ...g condition To check a relief valve lift the lever at the end of the valve several times The valve should seat properly and operate freely If water does not flow remove the valve and inspect for obstr...

Page 13: ...is the standard 5 gallon container for UN LIME or it is available as a deliming kit with UN LIME hose and fittings Contact your dealer distributor or the A O Smith Water Products Company Figure 18 il...

Page 14: ...n the motor oil cups SOOT REMOVAL Soot must be removed semi annually from the heater and flow passages to insure efficient operation of the heater A TYPICAL HEATER FLUEWAYAND FLUE BAFFLE FIGURE19 1 Re...

Page 15: ...ATION WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES...

Page 16: ...SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUP...

Page 17: ...ED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER S...

Page 18: ...URES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTU...

Page 19: ...CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP CONTROL SHOULD BE SET AT 185 F 85 C NOTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE...

Page 20: ...units with the higher water flow may have a shortened life Unions and T P valves shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by comp...

Page 21: ...water pressure Excessive water temperature Faulty relief valve Excessive water pressure is the most common cause of relief valve leakage It is often caused by a closed system If a check valve is in th...

Page 22: ...n must be reset before trying again for ignition When this occurs allow about 5 minutes for safety heater to cool before depressing the red safety button Depress red button one time only If burner doe...

Page 23: ...ting screws slightly and shift Noisy fuel pump in different positions until noise is eliminated Operation Retighten mounting screws Air in inlet line Check all connections Use only good flare fittings...

Page 24: ...l at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater...

Page 25: ...L COF 199 245 315 385 455 700 AND COF 315A 385A 455A 700A SERIES 940 941 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 WWW HOTWATER C...

Page 26: ...519 Wiring Diagram 195056 000 195056 000 195056 000 195056 000 195056 000 195056 000 17 Gasket Skirt Ring 76443 76443 76443 76443 76443 76443 18 Insulation Foil Faced 41175 41175 41175 41175 41175 411...

Page 27: ...27 NOTES...

Page 28: ...28...

Page 29: ...pr sent manuel pour r duire au minimum le risque d incendie ou d explosion et pr venir les blessures la mort ou les dommages mat riels Ne pas entreposer ni utiliser d essence ou d autres vapeurs et l...

Page 30: ...838 745 671 610 559 516 479 700 700A 205 261 LPH 6347 5077 4 231 3627 3 173 2821 2 539 2 308 2116 1953 1813 Tous les r servoirs sont test s une pression de service de 320 lb po2 Bas sur l utilisation...

Page 31: ...ur porte l une des tiquettes UL qui atteste que cet appareil a subi des inspections p riodiques au cours de sa fabrication Tous les r servoirs ASME sont conformes aux normes de la section IV du code d...

Page 32: ...ECTRIQUE DU CHAUFFE EAU OU PROXIMIT DE CELUI CI NE JAMAIS TOUCHER DES COMPOSANTS LECTRIQUES AVEC LES MAINS MOUILL ES OU AVEC LES PIEDS DANS L EAU LORS DU REMPLACEMENT DE FUSIBLES UTILISER TOUJOURS LE...

Page 33: ...les produits chimiques pour piscines le chlorure de calcium le chlorure de sodium les cires et les produits chimiques industriels peuvent provoquer une telle corrosion Ces substances sont corrosives...

Page 34: ...315A 8 203 2 COF 385 385A 8 203 2 COF 455 455A 8 203 2 COF 700 700A 10 254 Ces mod les sont livr s avec un raccord de r duction d vent installer sur le couvercle sup rieur S il se produit un refoulem...

Page 35: ...st me en circuit ferm se forme si un dispositif antiretour clapet de retenue un d tendeur de pression ou un dispositif similaire est install dans la conduite d eau froide entre le chauffe eau et la ca...

Page 36: ...ompe 3 8 po de 1 2 po de pi m diam ext diam ext pi m diam ext diam ext 1 0 3 66 20 1 100 30 4 6 1 8 36 10 9 100 30 4 2 0 6 55 16 7 100 30 4 7 2 1 31 9 4 100 30 4 3 0 9 50 15 2 100 30 4 8 2 4 26 7 9 10...

Page 37: ...r sultant d un contact avec le chauffe eau ou la tuyauterie 3 Tous les br leurs disposent d un allumage intermittent tel que d fini par UL l allumage est actif pendant que le br leur est en marche et...

Page 38: ...utilis e il peut tre n cessaire de la lubrifier avant de la mettre en marche Le tube de lubrifiant fourni avec la pompe contient le mode d emploi Seules les pompes de circulation tout bronze sont rec...

Page 39: ...17 L un des capteurs se trouve pr s du sommet du r servoir et l autre pr s du centre Le thermostat est r gl en usine sa position la plus basse Le cadran de r glage du thermostat est accessible en ret...

Page 40: ...ermique Pour ce faire actionner plusieurs fois le levier l extr mit de la soupape Celle ci devrait tre bien appuy e et fonctionner sans entrave Si l eau ne circule pas enlever la soupape et v rifier s...

Page 41: ...uple et des raccords Pour plus de d tails communiquer avec le fournisseur le distributeur ou directement avec A O Smith Water Products Company La figure 18 pr sente la plupart des tapes de d tartrage...

Page 42: ...paliers et 10 12 gouttes dans le godet huileur du moteur ENL VEMENT DE LA SUIE Enlever la suie tous les six mois du chauffe eau et du conduit des gaz de combustion afin d assurer un fonctionnement eff...

Page 43: ...ER LA TEMP RATURE DE CONSIGNE NE DOIT PAS D PASSER LES VALEURS CONSID R ES COMME S CURITAIRES POUR LES APPAREILS UTILISATEURS VOIR LASECTION R GLAGE DE LA TEMP RATURE DE L EAU PAGE 11 SI UNE TEMP RATU...

Page 44: ...APPAREILS UTILISATEURS VOIR LASECTION R GLAGE DE LA TEMP RATURE DE L EAU PAGE 11 SI UNE TEMP RA TURE DE PR CHAUFFAGE PLUS LEV E EST N CESSAIRE AU NIVEAU DU SURCHAUFFEUR AJOUTER UN ROBINET ANTI BOUILLA...

Page 45: ...APPAREILS UTILISATEURS VOIR LA SECTION R GLAGE DE LA TEMP RATURE DE L EAU PAGE 11 SI UNE TEMP RA TURE DE PR CHAUFFAGE PLUS LEV E EST N CESSAIRE AU NIVEAU DU SURCHAUFFEUR AJOUTER UN ROBINET ANTI BOUIL...

Page 46: ...TURE DE PR CHAUFFAGE PLUS LEV E EST N CESSAIRE AU NIVEAU DU SURCHAUFFEUR AJOUTER UN ROBINET ANTI BOUILLANTAGE DANS LES CONDUITES D EAU QUIALIMENTENT DES APPAREILS RACCORDER LA CONDUITE DE CIRCULATION...

Page 47: ...EN T NON ISOL PLAC AU DEL DU T DE PR L VEMENT DU LAVE VAISSELLE DANS LABOUCLE DE D SINFECTION R GLER LA TEMP RATURE DE CONSIGNE 185 F 85 C NOTA3 AJUSTER LE ROBINET TOURNANT DE MANI RE CE QUE LE D BIT...

Page 48: ...teur Les dimensions indiqu es s appliquent l espace minimal occup par les chauffe eau Pr voir de l espace pour l entretien l avant des appareils DANGER LA TEMP RATURE DE CONSIGNE NE DOIT PAS D PASSER...

Page 49: ...ses causes Pression de l eau trop lev e Temp rature de l eau trop lev e Soupape de d charge d fectueuse Une fuite la sortie de la soupape de d charge est habituellement caus e par une pression trop le...

Page 50: ...iron cinq minutes pour laisser le dispositif de s curit se refroidir avant d enfoncer le bouton rouge Enfoncer le bouton rouge une seule fois V rifier la chambre de combustion si le br leur ne fonctio...

Page 51: ...us de montage de la pompe mazout et placer la pompe dans diff rentes positions jusqu l limination du bruit Resserrer les crous de montage Fonctionne Air dans la conduite d alimentation V rifier tous l...

Page 52: ...e remplacement du chauffe eau ou des pi ces d fectueuses Tous les autres frais sont la charge du propri taire Ces frais peuvent inclure sans s y limiter a Les frais de main d uvre pour l entretien la...

Page 53: ...5 315 385 455 et 700 ET MOD LES COF 315A 385A 455A et 700A S RIE 940 941 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 T L PHONE 1 800 433 2545 T L COPIEUR 1 800 433 2515 WW...

Page 54: ...56 000 195056 000 17 Joint anneau de la jupe d isolation 76443 76443 76443 76443 76443 76443 18 Isolation rev tement m tallique 41175 41175 41175 41175 41175 41175 19 Chemise 193062 193062 193062 1930...

Page 55: ...27 NOTES...

Page 56: ...28...