6.4.
User Setting Menu
Menu Description
:
:
:
:
User Setting Menu
Menu Item
Description
SUMMER SETPOINT
SUMMER SETPOINT
is used as tank temperature setpoint when the ambient temperature is
higher than the setpoint for enabling the auxillary heater.
Setting Range:
35-60
o
C
Default Value:
47
o
C
Please refer to “Summer Tank Temperature Setting” section for detailed setting method.
WINTER SETPOINT
WINTER SETPOINT
is used as tank temperature setpoint when the ambient temperature is
lower than the setpoint for disabling the auxillary heater.
Setting Range:
35-60
o
C
Default Value:
53
o
C
The setting process is similar as “Summer Tank Temperature Setting”.
AUTO ON/OFF SETTING
AUTO ON/OFF SETTING
is used to set the automatic operation time of the hot water system
if the automatic operation function is enabled.
Please refer to “Timer Setting” section for detailed setting method.
AUTO ON/OFF ENABLE
AUTO ON/OFF ENABLE
is used to enable or disable the hot water system automatic
operation.
Setting Options:
ON/OFF
Default Option:
OFF
The setting process is similar as “Summer Tank Temperature Setting”.
CURRENT TIME SETTING
AUTO ON/OFF ENABLE
is used to set the clock time of the central controller.
Please refer to “Time Setting” section for detailed setting method.
USER PUMP ON INTVL
USER PUMP ON INTVL
is the parameter used to control the operaion interval of the user
pump.
Setting Range:
0~90 Minutes
Default Value:
30 Minutes
The setting process is similar as “Summer Tank Temperature Setting”.
USER PUMP ON TIME
USER PUMP ON TIME
is the parameter used to control the operaion time of the user pump.
Setting Range:
0~90 Minutes
Default Value:
20 Minutes
USER SETTING
MODIFY BACK HELP
WINTER SETPOINT 53℃
AUTO ON/OFF ENABLE OFF
CURRENT TIME SETTING
AUTO ON/OFF SETTING
Picture 6.5 User Setting Menu
SUMMER SETPOINT 47℃