REMEDY

COMPLAINT

                CAUSE

                     USER

                     SERVICEMAN

*Water not hot enough.

Thermostat set too low.

Set thermostat dial to a higher

temperature.

Thermostat out of calibration. Call serviceman

Recalibrate thermostat.  If thermostat cannot

be recalibrated, replace.

*Insufficient hot water

Thermostat set too low.

Set thermostat dial to a higher

*See WATER TEMPERATURE

temperature.

CONTROL WARNING (on

Page 5).

Thermostat out of calibration. Call serviceman.

Recalibrate thermostat.  If thermostat cannot

be recalibrated, replace.

Main manual gas shutoff

Open main manual gas shutoff

valve partially closed.

valve to fullest extent.

Heater too small for demand.

Space usage to give heater time

to restore water temperature.

Thermostat differential is

Call serviceman.

Replace dual bulb controller if differential is

too wide.

greater than 4°F.

Heater recovery is slower.

Call serviceman.

Check gas input. If incorrect, adjust gas

pressure or replace main burner orifice.

Drafthood not installed or

Call serviceman.

Install drafthood or baffles as furnished

one or more flue baffles.

with unit.

Water temperature too hot.

Thermostat set too high.

Set thermostat to a lower setting.

Heater makes sounds: sizzling. Condensation on outside

of tank, normal.

Rumbling.

Sediment accumulation on

Drain  a  quantity  of water through

Delime heater.

bottom of tank.

drain valve. If rumbling persists,

call a serviceman.

Ticking or metallic sounds.

Expansion  and  contraction-

normal.

Pounding.

Air chambers in piping have

Drain piping system and refill.

become waterlogged.

Heater must be off while this is

being done.

Combustion noises.

Too much primary air.

Adjust shutters.

Overfired heater; Incorrect

Call serviceman.

Check and correct as necessary.

burners or orifice for type

of gas used.

Water leaks.

Drain valve not closed

If drain valve cannot be closed

 tightly.

tightly, replace.

If  leakage  source  cannot

Shut  off  gas  supply  to  heater

Repair or in case of suspected tank leakage,

be corrected or identified,

and close cold water inlet valve

be certain to confirm before replacing heater.

call serviceman.

to heater.

Gas odors.

Heater is overfired.

Shut off gas supply to heater

Check for sooted flue passage.

and call a serviceman.

Check for obstructed vent line.

Check backdraft or lack of draft.

Possible gas leaks.

Shut off gas supply to heater and
call gas company at once.

OPERATIONAL CHECKLIST

This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” should be used as an on-the-job
troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction.  Because
improper piping and wiring can result in unsatisfactory system performance, it is suggested that the installation be examined
before using the checklist.  Be sure to refer to the correct piping and wiring diagram for the type of system that is installed.

The system should be filled with water, purged of air, valves properly set and utilities connected and ready to operate.

Summary of Contents for BTI 120

Page 1: ...000 Printed in U S A 0803 SUPERSEDESPARTNO 194780 000 ADIVISION OFA O SMITH CORPORATION McBEE SOUTH CAROLINA USA www hotwater com CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE...

Page 2: ...96 91 88 82 35 269 LPH 1209 1088 870 806 725 622 604 544 484 435 403 396 363 345 335 311 BTI 154 154 000 81 80 GPH 410 369 295 273 246 211 205 184 164 148 137 134 123 117 113 105 45 307 LPH 1551 1396...

Page 3: ...ent Parts 29 Sequence of Operation Flow Chart 30 Operational Checklist 31 Limited Warranty 32 Page Page FOREWORD These designs comply with ANSI Z21 10 3 as an automatic circulating or automatic storag...

Page 4: ...FOR SAFE OPERATION LIQUID PETROLEUM MODELS Water heaters for propane or liquefied petroleum gas LPG are different from natural gas models A natural gas heater will not function safely on LP gas and no...

Page 5: ...ements Also due to the input rating reduction required at high altitudes the output rating of the appliance is also reduced and should be compensated for in the sizing of the equipment for application...

Page 6: ...es are high a water pressure reducing or flow regulating control valve should be used in 1800 F 82 C line to the dishwashing machine and should be adjusted to deliver water between these limits The Na...

Page 7: ...51mm 2 51mm 12 305mm BTI 250 A 2 51mm 2 51mm 2 51mm 12 305mm BTI 275 A 2 51mm 2 51mm 2 51mm 12 305mm BTI 310 A 3 76mm 3 76mm 3 76mm 12 305mm BTI 366 A 3 76mm 3 76mm 3 76mm 12 305mm BTI 400 A 3 76mm 3...

Page 8: ...nspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 Determine that there is no blockage or restriction leakage corrosion and other defi...

Page 9: ...ches 154 000 1 Ft 6 6 6 6 6 6 6 6 154 000 2 Ft 6 6 6 6 6 6 6 6 154 000 3 Ft 6 6 6 6 6 6 6 6 Number of Combined Input BTI 154 Heaters in Thousands of Btu hr Manifold and Common Vent Diameter Inches 2 3...

Page 10: ...I 310 Input 310 000 Btu hr Total Vent Height Feet Vent Connector Size 6 inches 6 8 10 15 20 30 50 100 Input Btu hr Rise Vent Connector Diameter Inches 310 000 1 Ft 9 8 8 8 7 7 6 6 310 000 2 Ft 8 8 8 7...

Page 11: ...system as a means of detecting the temperature of the outlet water supply RELIEF VALVE This water heater is equipped with a combination temperature pressure relief valve that complies with the standa...

Page 12: ...s resistant to the action of liquefied petroleum gases BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEAKAGE Use soap and water solution or other material acceptable for the purpose in locating...

Page 13: ...iction AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION If any of the original wire as supplied with the appliance must be replaced use only type 1050 C th...

Page 14: ...RATURE CONTROL WARNING ON PAGE 23 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES GENERAL The type size and lo...

Page 15: ...OULD NOT EXCEED SAFE USE TEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROL WARNING ON PAGE 25 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARYTO OBTAINADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR H...

Page 16: ...OGGLESWITCHMUSTBECLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOTOPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALLLINETEMPERATURECONTROLINANUNINSULATED TEEBEYONDTHEDISHWASHINGMACHINE...

Page 17: ...s shown in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of th...

Page 18: ...NOTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARYTURBULENCEIN THETANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Page 19: ...ERS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25 IF HIGHER PREHE...

Page 20: ...TER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIEDTO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATUR...

Page 21: ...154 70 BTI 180 70 BTI 199 70 BTI 200 A 72 BTI 250 A 72 BTI 275 A 72 BTI 310 A 73 BTI 366 A 73 BTI 400 A 73 MANIFOLD KITS TWO UNIT MANIFOLD KIT PART NO 195686 THREE UNIT MANIFOLD KIT PART NO 195687 FO...

Page 22: ...filled with water and all air is expelled FILLING 1 Close the heater drain valve by turning handle clockwise 2 Open a nearby hot water faucet to permit the air in the system to escape 3 Fully open th...

Page 23: ...d then shuts off power to the Silicon Nitride Ignitor 11 From the time the Silicon Nitride Ignitor s power is shut off the Ignition Control Board waits 3 more seconds to monitor the Flame Sensor 12 If...

Page 24: ...tes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go on to the next step 7 Turn gas control knob counterclockwise to ON...

Page 25: ...that attach to faucets to limit hot water temperatures Contact a licensed plumber or the local plumbing authority The water temperature is controlled by a thermostat fig 3 which has two sensing eleme...

Page 26: ...ncrease gas pressure and input rate Counterclockwise to decrease gas pressure and input rate 4 Clock the meter as in step 2 above 5 Repeat steps 3 and 4 until the specified input rate is achieved 6 Tu...

Page 27: ...rs on the heater will usually be damaged when removed New pipe collars will insure that the seal is such as to prevent leakage of flue products when properly installed NOTE Anode rod inspection may ne...

Page 28: ...lied with the kit 2 Remove the container s cap and cut the plastic membrane located in the 3 4 IPT opening in the cap Take care to not damage the threads 3 Find the 3 4 male adapter apply teflon tape...

Page 29: ...hat incorporates a diagnostic system to assist in troubleshooting the appliance The indicator codes on the ignition module are as follows 1 flash System lockout retries or cycles exceeded 2 flashes Pr...

Page 30: ...engages Prover Switch Ignition Control Board provides power to Silicon Nitride Ignitor Silicon Nitride Ignitor warms up for 20 seconds Ignition Control Board opens Gas Valve Ignition Control Board sh...

Page 31: ...metallic sounds Expansion and contraction normal Pounding Air chambers in piping have Drain piping system and refill become waterlogged Heater must be off while this is being done Combustion noises T...

Page 32: ...heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acc...

Reviews: