A.O. Smith BTH 120-250(A) Installation & Operating Instructions Manual Download Page 29

29

CHECKLIST AND SERVICE INFORMATION

IMPORTANT

The installer may be able to observe and correct certain problems which
might arise when the unit is put into operation or when it is re-fired after a
prolonged shutdown. HOWEVER, it is recommended that only qualified
servicemen, using appropriate test equipment, be allowed to service the
heater.

BE SURE TO TURN OFF THE ELECTRICITY WHENEVER POSSIBLE OR
APPROPRIATE WHILE CHECKING EQUIPMENT.

 

WARNING

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS
PERSONAL INJURY OR DEATH.

CAUTION:  LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND
DANGEROUS OPERATION.

VERIFY PROPER OPERATION AFTER SERVICING.

BURNER OPERATIONAL PROBLEMS

1. Refer to TROUBLESHOOTING.

NOT ENOUGH OR NO HOT WATER

1. Be certain the electrical disconnect switch serving the water heater

is in the ON position.

2. Check the fuses.

The electrical disconnect switch usually contains fuses.

3. The capacity of the heater may have been exceeded by a large

demand for hot water.

Large demands require a recovery period to restore water
temperature.

4. Colder incoming water temperature will lengthen the time required to

heat water to the desired temperature.

If the heater was installed when incoming water temperature was
warm, colder water creates the effect of less hot water.

5. Look for hot water wastage and leaking or open hot water faucets.

6. Sediment or lime scale may be affecting water heater operation.  Refer

to MAINTENANCE for details.

7. The heater’s temperature high limit sensor has activated. Press the

reset button on the thermostat.

8. Burner may not be firing at proper rate.

Check gas pressure. Adjust to obtain required manifold pressure.

9. Burner fan wheel may be dirty.

Clean fan wheel with a stiff brush.

10. Condensate hose may be blocked where it connects to the exhaust

elbow.

Verify the condensate drains from the unit without restriction.

WATER IS TOO HOT

1. Refer to WATER TEMPERATURE CONTROL.

WATER HEATER MAKES SOUNDS

1. Sediment or lime scale accumulations cause rumbling and pounding

noises when the heater is operating.

The sounds are normal, however, the tank bottom should be

cleaned.  Refer to MAINTENANCE for details.

2.

Some of the electrical components of the water heater make sounds
which are normal.

• Contacts click or snap as the heater starts and stops.
• Transformers often hum.

WATER LEAKAGE IS SUSPECTED

1.

Check to see if the water heater drain valve is tightly closed. Also
check the cleanout opening for leakage.

2.

The apparent leakage may be condensation which forms on cool
surfaces of the heater and piping.

3.

If the outlet of the relief valve is leaking it may represent:

• Excessive water pressure.
• Excessive water temperature.
• Faulty relief valve.

Excessive water pressure is the most common cause of relief valve
leakage. It is often caused by a “closed system”. If a check valve is in the
inlet system it will not permit the expanded hot water volume to equalize
pressure with the main. The relief valve must release this water or the
water heater or plumbing system will be damage d. Refer to MAINTENANCE-
RELIEF VALVE section in this manual.

When such a condition is encountered, local codes or inspection agency
should be consulted to determine which system is acceptable in your area.
See CLOSED SYSTEM section in this manual also.

TROUBLE-SHOOTING

1. Verify that the allowable vent length has not been exceeded and that

the blower inlet screen has been removed if direct venting.

2. Verify that the condensation, which WILL be present in the heater and

exhaust vent, will drain.

3. Check supply wire polarity - hot to hot and neutral to neutral and no

"stray" current in neutral.

4. Heater is properly grounded.

Checking these four (4) items first will often result in a timely solution to the
service call.

 WARNING

JUMPING OUT COMPONENTS AND/OR CIRCUITS DURING
TROUBLESHOOTING CAN CAUSE SERIOUS PROBLEMS WITH THE
UNIT’S OPERATING SEQUENCE AND IGNITION SAFETY. IF YOU DO NOT
HAVE THE PROPER TEST EQUIPMENT, I.E. A VOLT-OHM METER AND A
MICROAMMETER, DO NOT ATTEMPT TO TROUBLESHOOT OR REPAIR
A.O. SMITH EQUIPMENT.

ALTERING THE CONTROLLER AND/OR CONTROLLER WIRING IN ANY
WAY COULD RESULT IN INTERNAL DAMAGE TO THE MODULE
CIRCUITS, POSSIBLY ALTERING THE IGNITION SEQUENCE ALLOWING
GAS VALVES TO OPEN BEFORE THE HOT SURFACE IGNITER IS UP TO
IGNITION TEMPERATURE.

NOTE:  ANY BYPASS OR ALTERATION OF THE UNITS SAFETIES WILL
RESULT IN VOIDING THE APPLIANCE WARRANTY.

Before performing any troubleshooting familiarize yourself with the particular
appliance.

Refer to the SEQUENCE OF OPERATION and the connection diagram located
on page 15 before continuing.

Make sure the appliance is connected to a 120V AC power supply, manual
gas valve is in the ON position, and all electrical connections are secure
before continuing to troubleshoot this appliance.

 

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING
ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY HEATED
WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE.

Summary of Contents for BTH 120-250(A)

Page 1: ...FORE INSTALLING AND USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do n...

Page 2: ... ProtectionAssociation 1 Batterymarch Park Quincy MA02269 FOREWORD CYCLONE XHE BTH 120 250 ROUGH IN DIMENSIONS TEMPERATURE RISE DEGREES C LITERS PER HOUR Approx Input Liter Model kW Capacity 17 C 22 C 28 C 33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C BTH 120 37 Nat 227 1798 1348 1079 898 768 674 598 538 488 450 416 386 BTH 120 35 L P 227 1726 1295 1037 863 738 647 575 519 469 432 397 371 BTH 150 4...

Page 3: ...tion WATER TEMPERATURE CONTROL TABLE OF CONTENTS ROUGH INDIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Requirement 4 Circulating Pump 4 INSTALLATIONINSTRUCTIONS 4 13 Required Ability 4 Insulation Blankets 4 5 Locating The Heater 5 Clearances 5 Hard Water 6 Air Requirements 6 Mechanical Exhausting of Room Air 6 Unconfined Space 6 Conf...

Page 4: ...n Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch 103 Kpa and 173 Kpa Flow pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure reducing or flow regulating control valve should be used in the 180 F 82 C line ...

Page 5: ...quality water pressure and the environment in which the water heater is installed Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped drain pan These devices are available f...

Page 6: ...UNLESS RUBBER ISOLATION PIPE HANGERSARE USED THIS PREVENTSANY VIBRATIONS FROM BEING ALCOVE HARDWATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protect the dishwashers coffee urns water heaters water piping and other equipment See MAINTENANCE section for details of tank cleanout procedure AIR REQUIREMENTS KEEP APPLIANCE AREA ...

Page 7: ...RMINATE EXHAUST OVER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD ON DIRECT VENT INSTALLATIONS EXHAUST VENT HOOD MUST BE LOCATED 1 30 5cm MINIMUM FROM ANY OPENING IN BUILDING ON DIRECT VENT INSTALLATIONS EXHAUST VENT HOOD MUST BE LOCATED 4 122cm MINIMUM FROM ANY OPENING IN BUILDING ...

Page 8: ... the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and CLEARANCES and with National Fuel Gas Code and local Codes IMPORTANT Plan th...

Page 9: ... wall Align the holes by drilling a hole through the center of the template from the inside through to the outside The template can now be positioned on the outside wall using the drilled holes as a centering point for the template 3 A MASONRY SIDE WALLS Chisel an opening approximately 1 2 1 3 cm larger than the marked circle B WOODEN SIDE WALLS Drill a pilot hole approximately one quarter inch ou...

Page 10: ...tions should be sealed with a plumbing roof boot or equivalent flashing 3 The intake vent termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust vent terminal must be oriented facing downward and th...

Page 11: ...90 elbows with the 4 inch venting is six 6 on the intake and six 6 on the exhaust A 90 elbow is equal to five 5 equivalent feet 1 5m of pipe One 1 90 elbow is equal to two 2 45 elbows Any venting configuration using less than 50 equivalent feet should use 3 inch venting See Table 2 The 3 inch venting terminals provided must be used with the 4 inch venting by adding 4x3 reducing couplings at the ve...

Page 12: ...h is considered normal for low pressure systems Note that fittings such as elbows and tees will add to the pipe pressure drop CAUTION DO NOT USE FLEXIBLE GAS PIPING TABLE 3 MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR Based upon a Pressure Drop of 0 5 inch Water Column and 0 6 Specific Gravity Gas and max gas pressure of 0 5 psig WARNING THE HEATER IS NOT INTENDED FOR OPERATIONAT HIGHER ...

Page 13: ...ter is too small ask the gas company to install a larger meter having adequate capacity GAS PRESSURE REGULATION Main line gas pressure to the water heater should be between a maximum 14 0 3 45Kpa W C and a minimum as shown in Table 4 that is for Natural Gas 5 0 1 25Kpa W C for BTH 120 250 or 4 5 1 12Kpa W C for BTH 150 199 or for L P Gas 11 0 2 74Kpa W C The inlet gas pressure must not exceed the ...

Page 14: ...TER TANK IS FILLED WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNECTIONS This manual provides detailed installation diagrams see back section of this manual for typical methods of application for the water heaters The water heater may be installed ...

Page 15: ...y return to Step 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted next to connector CN1 Line input connection When 120 VAC input power is properly connected to the Main Control Board the green LED will illuminate If an error is made when connecting 120...

Page 16: ... Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner improperly adjusted 9 Adjust burner 10 Dirty burner 10 Clean burner GAS VALVE LED FLASHING This condition results from a failure to establish burner ignition after three successive trials In such cases 1 Investigate the possible cause and remedy any observations 2 Momentaril...

Page 17: ...ntrol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring shorted 2 Repair wiring 3 Defective probe 3 Replace probe PossibleCause Remedy 1 Temp Probe unplugged 1 Check connectors 2 Temp probe wiring damaged 2 Repair wiring 3 Water in tank too hot 3 Normal condit...

Page 18: ...ect orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OFTHIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICALWORKAREREQUIRED Before attempting start up thoroughly study and familiarize yourself with the exact sequence of operation and all other details on the specific heater being us...

Page 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life ...

Page 20: ...LATIONS WARNING BTH HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL CENTER 800 527 1953 FOR REQUIREMENTS Some gas utility companies derate their gas for altitude making it unneccessary to install high altitude orifices Call the local gas or utlity company to verify BTU cont...

Page 21: ...alve when finished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures may also require draining the heater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Op...

Page 22: ...and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TOAN OPEN DRAIN FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT THE VALVE DURING THIS CHECKING OP...

Page 23: ...OT WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALLINACCORDANCE...

Page 24: ...DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATUREATFIXTURES SEEWATERTEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METERWITHCHECKVALVEPROVISIONSFORTHERMAL EXPANSION OF WATER ...

Page 25: ...IT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 4 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER...

Page 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 4 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BO...

Page 27: ...TANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 5 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD ANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK ...

Page 28: ...ter heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added ...

Page 29: ...o see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the relief valve is leaking it may represent Excessive water pressure Excessive water temperature Faulty relief valve Excessive water pressure is the most common cause of relief valve ...

Page 30: ...a W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for BTH 120 250 or 4 5 1 1 kPa W C for BTH 150 199 or for L P Gas 11 0 2 74 kPa W C pressure Also the manifold pressure should rise during the three 3 second trial for ignition to the manifold pressure value for the individual unit listed in Table 4 that is for Natural Gas 4 0 1 kPa W C...

Page 31: ... to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICEAND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but a...

Page 32: ...32 A O SMITH WATER PRODUCTS COMPANY 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E MAIL parts hotwater com ...

Reviews: