These designs comply with the latest version of the American National
Standard for Gas Water Heaters, Volume III, ANSI Z21.10.3 / CSA 4.3 M 98
as an automatic circulating tank water heater, and automatic storage water
heaters.
Detailed installation diagrams are found in this manual. These diagrams will
serve to provide the installer with a reference for the materials and methods
of piping necessary. It is highly essential that all water, gas piping and
wiring be installed as shown on the diagrams.
Particular attention should be given to the installation of thermometers at
the locations indicated on the diagrams as these are necessary for checking
the proper functioning of the heater.
In addition to these instructions, the equipment shall be installed in
accordance with those installation regulations in force in the local area
where the installation is to be made. These shall be carefully followed in all
cases. Authorities having jurisdiction should be consulted before
installations are made.
In the absence of local codes, the installation must comply with the latest
editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the
National Electric Code, NFPA 70 CAN/CSA 149.1 or .2 and CSA 2C22.1. The
former is available from the CSA International, 8501 East Pleasant Valley
Road, Cleveland, OH 44131, and both documents are available from the
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
FOREWORD
CYCLONE XHE BTH 120 - 250 ROUGH-IN-DIMENSIONS
TEMPERATURE RISE - DEGREES °C - LITERS PER HOUR
Approx.
Input
Liter
Model
kW
Capacity
17°C
22°C
28°C
33°C
39°C
44°C
50°C
56°C
61°C
67°C
72°C
78°C
BTH - 120
37 Nat.
227
1798
1348
1079
898
768
674
598
538
488
450
416
386
BTH - 120
35 L.P.
227
1726
1295
1037
863
738
647
575
519
469
432
397
371
BTH - 150
44 Nat.
379
2158
1616
1295
1079
924
810
719
647
587
538
500
462
BTH - 150
44 L.P.
379
2158
1616
1295
1079
924
810
719
647
587
538
500
462
BTH - 199
58 Nat.
379
2873
2154
1726
1438
1230
1079
958
863
784
719
662
617
BTH - 199
54 L.P.
379
2661
1995
1597
1329
1139
996
886
799
727
666
613
572
BTH - 250
70 Nat.
379
3452
2589
2071
1726
1480
1295
1151
1037
939
863
795
738
Recovery capacities are based on heater performance at 94% thermal efficiency.
Table 1. RECOVERY CAPACITIES - NATURAL GAS / L.P
.
TEMPERATURE RISE - DEGREES °F - GALLONS PER HOUR
Approx.
Input
Gallon
Model
BTU/Hr.
Capacity
30
40
50
60
70
80
90
100
110
120
130
140
BTH - 120
125,000 Nat.
60
475
356
285
237
203
178
158
142
129
119
110
102
BTH - 120
120,000 L.P.
60
456
342
274
228
195
171
152
137
124
114
105
98
BTH - 150
150,000 Nat.
100
570
427
342
285
244
214
190
171
155
142
132
122
BTH - 150
150,000 L.P.
100
570
427
342
285
244
214
190
171
155
142
132
122
BTH - 199
199,900 Nat.
100
759
569
456
380
325
285
253
228
207
190
175
163
BTH - 199
185,000 L.P.
100
703
527
422
351
301
263
234
211
192
176
162
151
BTH - 250
240,000 Nat.
100
912
684
547
456
391
342
304
274
248
228
210
195
GAS VALVE PIPING
BTH-120
1/2" NPT
BTH-150,
199 & 250
3/4" NPT