10

insulation Blanket

Do not obstruct water heater air intake

with insulating blanket.
Gas and carbon monoxide detectors

are available.
Install water heater in accordance with

the instruction manual.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Breathing Hazard - Carbon Monoxide Gas

Insulation blankets are available to the general public for external 

use  on  gas  water  heaters  but  are  not  necessary  with  these 

products. The purpose of an insulation blanket is to reduce the 

standby heat loss encountered with storage tank heaters. The 

water heaters covered by this manual meet or exceed the Energy 

Policy Act standards with respect to insulation and standby heat 

loss requirements, making an insulation blanket unnecessary.

Should  you  choose  to  apply  an  insulation  blanket  to  this 

heater, you should follow these instructions. See the Features 

and  Components  section  of  this  manual  for  identification  of 

components mentioned below. Failure to follow these instructions 

can restrict the air flow required for proper combustion, potentially 

resulting in fire, asphyxiation, serious personal injury or death.

• 

do not

 apply insulation to the top of the water heater, as this 

will interfere with safe operation of the exhaust inducer.

• 

do not

 cover the gas valve, thermostat or the Temperature-

Pressure Relief Valve.

• 

do not

 allow insulation to come within 2” (5 cm) of the burners, 

to prevent blockage of combustion air flow to the burners.

• 

do not

  allow  insulation  to  come  within  9  inches  (23  cm) 

of  floor,  (within  2  inches  (5  cm)  of  bottom  cover)  to  prevent 

blockage of combustion air flow to the burners..

• 

do not

 cover the instruction manual. Keep it on the side of 

the water heater or nearby for future reference.

• 

do

  obtain  new  warning  and  instruction  labels  from  the 

manufacturer  for  placement  on  the  blanket  directly  over  the 

existing labels.

• 

do

 inspect the insulation blanket frequently to make certain it 

does not sag, thereby obstructing combustion air flow.

hard water

Where  hard  water  conditions  exist,  water  softening  or  the 

threshold  type  of  water  treatment  is  recommended.  This  will 

protect the dishwashers, coffee urns, water heaters, water piping 

and other equipment.
See the Maintenance Section in this manual for sediment and 

lime scale removal procedures.

circulation pumps

A circulating pump is used when a system requires a circulating 

loop or there is a storage tank used in conjunction with the water 

heater. See Water Piping Diagrams in this manual for installation 

location of circulating pumps.

figure 6.

installation on comBustiBle flooring

These models are approved for installations on combustible flooring 

when installed with nSF Leg Kit number 9003425205. The installed 

height of the water heater will increase by 3" when the leg kit is installed.

figure 7.

1.   Unit needs to be lifted in a way not to damage unit or laid 

on it’s side to access the bottom of the legs.

2.   slide leg extension under leg and the bolt up through the 

bottom hole located in the bottom of the leg.

3.   Once in place, screw nut down and secure.
4.   Front of leg should line up with front of leg extension as 

shown in Figure 7 to make sure weight of unit is distributed 
through the leg extension.

Summary of Contents for BTC 201

Page 1: ...15 Low Lead Content Thank you for buying this energy efficient water heater We appreciate your confidence in our products WARNING If the information in these instructions is not followed exactly a fir...

Page 2: ...Troubleshooting 33 Water Piping Diagrams 34 Manifold Kits 49 Limited Warranty 50 Notes 51 2 Table Of Contents Safe Installation Use and Service 3 APPROVALS 3 General Safety Information 4 Precautions...

Page 3: ...ate of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State...

Page 4: ...ment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or ser...

Page 5: ...system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at the...

Page 6: ...water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the gas fir...

Page 7: ...manual resetting of high limit control preceded by higher than usual water temperature is evidence of high limit switch operation The following is a possible reason for high limit switch operation A m...

Page 8: ...60 F 33 C 70 F 39 C 80 F 44 C 90 F 50 C 100 F 56 C 110 F 61 C 120 F 67 C 130 F 72 C 140 F 78 C BTR C 151 150 000 NAT 32 Gal 80 GPH 727 485 364 291 242 208 182 162 145 132 121 112 104 44 kW Hr NAT 121...

Page 9: ...CONSTRUCTION MODEL A RIGHT SIDE B LEFT SIDE C BACK D CEILING BTR C 151 201 0 0 0 12 30 5 cm Locating the Water Heater Property Damage Hazard All water heaters eventually leak Do not install without ad...

Page 10: ...ion to come within 9 inches 23 cm of floor within 2 inches 5 cm of bottom cover to prevent blockage of combustion air flow to the burners DO NOT cover the instruction manual Keep it on the side of the...

Page 11: ...rating label under any circumstances Note Due to the input rating reduction at high altitudes the output rating of the appliance is also reduced and should be compensated for in the sizing of the equi...

Page 12: ...37 kPa from static to dynamic pressure to provide good performance Pressure drops that exceed 1 5 W C 0 37 kPa may cause rough starting noisy combustion or nuisance outages Increases or spikes in sta...

Page 13: ...al expansion tank installed See Water Line Connections on page 19 and the Water Piping Diagrams beginning on page 34 Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valv...

Page 14: ...ems and Thermal Expansion on page 13 If you do not understand these instructions or have any questions regarding the Temperature Pressure Relief Valve call the toll free number listed on the back cove...

Page 15: ...which the appliances are installed through openings not furnished with doors are considered a part of the unconfined space Makeup air requirements for the operation of exhaust fans kitchen ventilatio...

Page 16: ...uare inches 645 cm2 Outdoor Air Through One Opening Figure 14 Alternatively a single permanent opening commencing within 12 inches 300 mm of the top of the enclosure shall be provided See Figure 14 Th...

Page 17: ...aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 Outdoor Air Through Two Vertical Ducts The illustrations shown in thi...

Page 18: ...Number of Heaters Combined Input btu hr Manifold and Common Vent Diameter Inches 2 300 000 8 7 7 7 7 6 6 6 3 450 000 9 9 9 8 8 7 7 7 4 600 000 10 10 10 9 9 8 8 7 MODEL 201 Input 182 000 and 199 900 b...

Page 19: ...nections The water piping installation must conform to these instructions and to all local code authority having jurisdiction Good practice requires that all heavy piping be supported Read and observe...

Page 20: ...eat to this fitting Do not allow pipe dope to contact the plastic tube during installation Tube Inlet Installation Figure 18 TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE...

Page 21: ...LECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION If any of the original wire as supplied with the appliance must be replaced use only type 105 C thermoplastic...

Page 22: ...ne be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap must be incorporated in the piping see Figure 20 The sedimenttrapmustber...

Page 23: ...Gas Line Leak Testing on page 22 and repair any leaks found Start Up Initial Start Up Required Test Equipment U tube manometer pressure gauge or digital manometer Recommended range 20 W C 5 kPa Note...

Page 24: ...ressure to each water heater within the minimum and maximum supply pressure requirements listed in Table 3 on page 8 with all gas fired appliances connected to a common gas main firing at full capacit...

Page 25: ...to the Silicon Nitride Igniter 11 From the time the Silicon Nitride Igniter s power is shut off the Ignition Control Board waits 3 more seconds to monitor the Flame Sensor 12 If the Flame Sensor does...

Page 26: ...26 Sequence of Operation Flow Chart Description of this flow chart can be found in the SEQUENCE OF OPERATION section found on page 25 Figure 23...

Page 27: ...er through the heater where the thermostat senses the drop in water temperature and activates main burner operation of the appliance If the storage tank temperature control is out of calibration repla...

Page 28: ...heater storage tank be drained and flushed every 6 months to reduce sediment buildup The water heater should be drained if being shut down during freezing temperatures See Features And Components in...

Page 29: ...ve handling instructions on label of product being used Tank Cleanout Procedure The following practices will ensure longer life and enable the unit to operate at its designed efficiency 1 Once a month...

Page 30: ...flush with cool water If irritation persists get medical attention If swallowed give 1 or 2 glasses of water or milk and call physician Get immediate medical attention for eyes Keep out of reach of ch...

Page 31: ...e thermostat calling for heat It is possible that the high limit E C O has functioned to shut off the appliance See High Limit page 7 High Limit Switch for reset procedure Contact your service agent i...

Page 32: ...s bacteria is nontoxic to humans d An excess of active hydrogen in the tank This is caused by the corrosion protective action of the anode Hot water odor may be eliminated or reduced in some water hea...

Page 33: ...call a qualified service agency Delime heater Ticking or metallic sounds Expansion and contraction normal Pounding or water hammer Air chambers in piping have become waterlogged Thermal expansion tank...

Page 34: ...s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CI...

Page 35: ...ostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Page 36: ...and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BAL...

Page 37: ...mp between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VA...

Page 38: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 39: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 40: ...t should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 41: ...EMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SU...

Page 42: ...VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES C...

Page 43: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Page 44: ...than the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT...

Page 45: ...r than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL...

Page 46: ...RE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED...

Page 47: ...emperature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEM...

Page 48: ...Temperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE...

Page 49: ...49 Manifold Kits MANIFOLD KITS TWO UNIT MANIFOLD KIT PART NO 9003426205 THREE UNIT MANIFOLD KIT PART NO 9003427205 FOUR UNIT MANIFOLD KIT PART NO 9003428205 MODEL DIMENSIONS A 151 201 45 0...

Page 50: ...also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES s t s o c r e h t o l l a r o f e l b i s...

Page 51: ...51 Notes...

Page 52: ...www hotwater com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 Copyright 2012 A O Smith Water Heater Company All rights reserved...

Reviews: