In addition to the appliance relief valve, each remote storage tank
which may be used in conjunction with this appliance shall also
be installed with a properly sized, rated and approved combination
temperature (ANSI) and pressure (ASME) relief valve(s).

  

WARNING

THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE
PRESSURE OR TEMPERATURE INTO THE STEAM RANGE,
WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION,
SYSTEM OR HEATER DAMAGE.  NO VALVE IS TO BE PLACED
BETWEEN THE RELIEF VALVE AND TANK.

Your local code authority may have other specific relief valve
requirements.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO
DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING
OR WATER DAMAGE.  THIS LINE MUST NOT BE REDUCED FROM
THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN
VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN
FREEZING AREAS.  DO NOT THREAD OR CAP THE END OF THIS
LINE.  RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT
THE PURPOSE OF THE VALVE AND IS UNSAFE.  DISCHARGE
LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE
OF BOTH THE VALVE AND LINE.

See SERVICE INFORMATION section for procedure and
precautions.

The type, size and location of the relief valve(s) must be in
accordance with local codes.  The location of the relief valve shown
in Figure 3 is typical.  The heater has a factory installed high
temperature limit switch.

For circulating heaters, the separate storage vessel must have a
temperature and pressure relief valve installed.  This valve shall
comply with the standard for relief valves and automatic gas shut-
off devices for hot water supply systems.

GAS PIPING

Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation codes
for your area.

FIGURE 3

CIRCULATING RETURN LINE CONNECTIONS
TEMPERED WATER LOOP, IF USED, CONNECT TO POINT "A".
STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO
COLD WATER INLET.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE,
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT
WATER SYSTEM MUST BE PROVIDED.

WARNING
TEMPERATURE SETTING SHOULD NOT
EXCEED SAFE USE TEMPERATURE AT
FIXTURES.  SEE TEMPERATURE REGULATION
ON PAGE 11.   IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN
ADEQUATE  BOOSTER OUTPUT, ADD AN
ANTI-SCALD VALVE FOR HOT WATER
SUPPLIED TO FIXTURES.

SINGLE TEMPERATURE

Size the main gas line in accordance with Table 1.  The figures
shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop,
which is considered normal for low pressure systems.  Note:
Fittings such as elbows, tees and line regulators will add to the
pipe pressure drop.  Also refer to the latest version of the National
Fuel Gas Code. For Canadian installations consult Canadian
Installation Code CAN/CSA B149.1-00.

  

WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER
THAN 10.5" W.C.(2.61 kPa) - NATURAL GAS,  or 13.0" W.C.(3.23
kPa) -PROPANE GAS SUPPLY GAS PRESSURE.  EXPOSURE TO
HIGHER SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS
VALVE WHICH COULD RESULT IN FIRE OR EXPLOSION.  IF
OVERPRESSURE HAS OCCURRED SUCH AS THROUGH
IMPROPER TESTING OF GAS LINES OR EMERGENCY
MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVE MUST
BE CHECKED FOR SAFE OPERATION.  MAKE SURE THAT THE
OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE
SAFETY  VENT VALVES ARE PROTECTED AGAINST BLOCKAGE.
THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE
HEATER.  VENT BLOCKAGE MAY OCCUR DURING ICE STORMS.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM
CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING MAY CAUSE
IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE
INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS
PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY
LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR
DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG.
4).  THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT
SUBJECT TO FREEZING CONDITIONS.  INSTALL IN
ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS
SUPPLIERS.  REFER TO THE LATEST VERSION OF THE NATIONAL
FUEL GAS CODE.  For Canadian installations consult Canadian
Installation Code CAN/CSA B149.1-00.

VACUUM RELIEF

VALVE

* INSTALL PER

LOCAL CODES

Summary of Contents for BT- 65

Page 1: ...TENANCE LIMITED WARRANTY Thank you for buying this energy efficient water heater from A O Smith Water Products Company We appreciate your confidence in our products ADIVISION OFA O SMITH CORPORATION M...

Page 2: ...itions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 in Canada CAN CSA B 149 1 00 Both are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 For C...

Page 3: ...ERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILUREAND RISK OFASPHYXIATION Spray can propellants cleaning solvents refrigerator and air conditioning refrigerants swimming pool chemicals calciu...

Page 4: ...TER DIRECTLY ON A CARPETED FLOOR A FIRE HAZARD MAY RESULT Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches 76 mm in any d...

Page 5: ...E LATEST EDITION OF THE NATIONALFUELGAS CODE ANSI Z223 1 NFPA54 FOR CANADACONSULT CAN CSA B149 1 00 KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS GASOLINEANDOTHERFLAMMABLES VAPORSAND LIQ...

Page 6: ...nt connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace the vent pipe should enter the smaller common vent or chimney at a point...

Page 7: ...IONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED WARNING TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE TEMPERATURE REGULATION ON PAGE 11 IF HIG...

Page 8: ...ptable for the purpose in locating the leaks DO NOT USE MATCHES CANDLES FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE FIGURE4 GASPIPINGANDDIRTLEGINSTALLATION DISCONNECTTHE HEATERAND ITS MANUALGA...

Page 9: ...FOR STEPS TO BE TAKEN Before lighting the pilot and operating the heater the following conditions must exist Entire system filled with water Air purged from all lines and no leaks gas and water All ga...

Page 10: ...l If you don t smell gas go to next step 6 Remove or open inner door located below gas control unit 7 Find pilot follow metal tube from gas control The pilot is located in front of the burner or on th...

Page 11: ...of use to exceed the thermostat setting by up to 30 F 17 C If you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing point of...

Page 12: ...cteristics 1 Provide complete combustion of gas 2 Cause rapid ignition and carryover of flame across entire burner 3 Give reasonably quiet operation during ignition burning and extinction 4 Cause no e...

Page 13: ...22mm in diameter with a 1 8 3mm diameter steel core wire running down the center of the anode material THE ANODE SHOULD BE REPLACED when the 1 8 3mm diameter core wire is visible as this means that t...

Page 14: ...operation is evidence of poor vent action Possible causes are too long a vent pipe or improper chimney operation 3 If the leakage is from the temperature and pressure relief valve or its discharge pi...

Page 15: ...is warranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by attaching non...

Page 16: ...16 PRODUCT SERVICE DIVISION 5621 W 115TH STREET ALSIP IL 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 E MAIL parts hotwater com www hotwater com REPLACEMENTPARTS...

Reviews: