15
IM D -0 06 1
IM D -0 06 2
Figure 10 and 11 - Roof discharge.
All measurements are in mm.
The following applies for the horizontal pipe: slope of at
least 5 mm per metre of pipe to the water heater.
A maximum of 2 bends (45° or 90°) may be used with
Flue configurations roof discharge BFM-unit
Measurement
BFM 30
BFM 50
BFM 80
min.
max.
min.
max.
min.
max.
A
0
7000
0
7000
0
7000
B
0
7000
0
7000
0
7000
A+B
< 7000
< 7000
< 7000
-
Roof discharge (see figures 10 and 11).
Type:
M2000 DDV SE HR/VR
Manufacturer:
Meulink & Grol
Pipe material flue tube:
Thick-walled aluminium with lip ring seal.
Pipe material air supply:
Thin-walled galvanised steel plate.
Pipe diameter BFM 30:
Ø 80 / 125 mm
BFM 50:
Ø 100 / 150 mm
BFM 80:
Ø 130 / 200 mm
Angle:
45°/90° (max 2)
these flue configurations.
These will each equate to 1 metre of flue length.
The maximum flue configuration is therefore 7000 mm
pipe, 2 bends (45°/90°) and a lead-through set.