background image

6

INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

COMMONWEALTH OF MASSACHUSETTS

For all side wall terminated, horizontally vented power vent, direct 

vent, and power direct vent gas fueled water heaters installed in 

every dwelling, building or structure used in whole or in part for 

residential purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust vent termination 

is less than seven (7) feet above finished grade in the area of 

the venting, including but not limited to decks and porches, the 

following requirements shall be satisfied:

INSTALLATION OF CARBON MONOXIDE DETECTORS

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gasfitter shall 

observe that a hard wired carbon monoxide detector with an 

alarm and battery back-up is installed on the floor level where 

the gas equipment is to be installed. In addition, the installing 

plumber  or  gasfitter  shall  observe  that  a  battery  operated  or 

hard wired carbon monoxide detector with an alarm is installed 

on each additional level of the dwelling, building or structure 

served by the sidewall horizontal vented gas fueled equipment. 

It shall be the responsibility of the property owner to secure the 

services of qualified licensed professionals for the installation of 

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or an attic, the hard wired 

carbon monoxide detector with alarm and battery back-up may 

be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be 

met at the time of completion of installation, the owner shall have 

a period of thirty (30) days to comply with the above requirements 

provided that during said thirty (30) day period, a battery operated 

carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE DETECTORS

Each carbon monoxide detector as required in accordance with 

the above provisions shall comply with NFPA 720 and be ANSI/

UL 2034 listed and CSA certified.

SIGNAGE

A  metal  or  plastic  identification  plate  shall  be  permanently 

mounted to the exterior of the building at a minimum height of 

eight (8) feet above grade directly in line with the exhaust vent 

terminal for the horizontally vented gas fueled heating appliance 

or equipment. The sign shall read, in print size no less than one-

half (1/2) inch in size, 

“GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS.”

INSPECTION

The state or local gas inspector of the side wall horizontally 

vented gas fueled equipment shall not approve the installation 

unless, upon inspection, the inspector observes carbon monoxide 

detectors and signage installed in accordance with the provisions 

of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS

The following equipment is exempt from 248 CMR 5.08(2)(a)1 

through 4:
1.  The equipment listed in Chapter 10 entitled “Equipment Not 

Required To Be Vented” in the most current edition of NFPA 

54 as adopted by the Board; and

2.  Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from the 

dwelling, building, or structure used in whole or in part for 

residential purposes.

MANUFACTURER REQUIREMENTS - GAS 

EQUIPMENT VENTING SYSTEM PROVIDED

When the manufacturer of Product Approved side wall horizontally 

vented gas equipment provides a venting system design or 

venting system components with the equipment, the instructions 

provided by the manufacturer for installation of the equipment 

and the venting system shall include:
1.  Detailed instructions for the installation of the venting system 

design or the venting system components; and

2.  A complete parts list for the venting system design or venting 

system.

MANUFACTURER REQUIREMENTS - GAS 

EQUIPMENT VENTING SYSTEM NOT PROVIDED

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not provide the 

parts  for  venting  the  flue  gases,  but  identifies  “special  venting 

systems,”  the  following  requirements  shall  be  satisfied  by  the 

manufacturer:
1.  The  referenced  “special  venting  system”  instructions  shall 

be included with the appliance or equipment installation 

 instructions; and 

2.  The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions. 

A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all 

venting design instructions shall remain with the appliance or  

equipment at the completion of the installation.

Summary of Contents for 110

Page 1: ... MODEL BTX 80 SERIES 110 ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER COMMERCIAL GAS WATER HEATERS For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER 500 Tennessee Waltz Parkway Ashland City TN 37015 LOW LEA...

Page 2: ...y alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoid the risk of injury The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California...

Page 3: ...L SAFETY INFORMATION Fire Hazard For continued protection against risk of fire Do not install water heater on carpeted floor Do not operate water heater if any part has been exposed to flooding or water damage ...

Page 4: ...rifice must be installed Do not operate if soot buildup is present Do NOT elevate any portion of the field supplied drain line beyond the 1 2 adaptor above the adaptor This must be true for the entire length of the drain line including the exit into an appropriate drain Condensate lines must be free and clear of debris and must not allow back flow through the hose The condensate lines must be able...

Page 5: ...cumentsarealsoavailablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local codes the National Electrical Code NFPA 70 or the Canadian Electrical Code C22 1 4 If after reading this manual you have any questions or do not understand any portion of the instructions...

Page 6: ... feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation...

Page 7: ...tch FF Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Sediment Trap K Outer Door L Union M Inlet Water Shut Off Valve N Cold Water Inlet O Inlet Dip Tube P Temperature Pressure Relief Valve H H Bushing II Nipple JJ Condensate Tee KK Adapter LL Plug MM Vent Pip...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued ...

Page 9: ...e water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use then special precautions must be taken In addition to using lowest possible temperature setting that satisfies demand of application a Mixing Valve should be installed at water heater see Figure 3 or at hot water taps to further reduce syst...

Page 10: ...nder both load and no load static and dynamic conditions Recovery Capacities U S Gallons Hr and Liters Hr at Temperature Rise Indicated Recovery capacity based on 90 thermal efficiency Rough In Dimensions Model Units A B C D E F G H J K BTX 80 Inches 71 12 68 70 51 90 20 90 9 15 12 00 22 00 8 00 15 81 26 92 cm 180 64 174 50 131 83 53 09 23 24 40 48 55 88 20 32 40 16 68 38 Top Side Inlet and Outlet...

Page 11: ...an piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater wh...

Page 12: ...orine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater The results can be hazardous and also cause product failure INSULATION BLANKETS Insulation blankets are available to the general public for external use on gas water heaters but are not necessary w...

Page 13: ...ne the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is installed in the same space with a water heater sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan Undersized op...

Page 14: ... a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 19 26 for complete venting installation instructions FIGURE 9 The confined space shall be provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing withi...

Page 15: ...de requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water system to be a closed system CHEMICAL VAPOR CORROSION CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILURE ...

Page 16: ...f the T P valve Secure all insulation using tape TEMPERATURE PRESSURE RELIEF VALVE Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized Temperature Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death This water heater is provided with a pro...

Page 17: ...T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems and Thermal Expansion on page 15 16 If you do not understand these instructions or have any questions regardingtheTemperature PressureReliefValvecallthetollfreenumber listed on the back cover of t...

Page 18: ...y piping system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping to the gas control valve of water heater can be accomplished by either of two methods shown in Figures 12 and 13 FIGURE 12 GAS PIPING WITH FLEXIBLE CONNECTOR FIGURE 13 GAS PIPING WITH ALL BLA...

Page 19: ...und that either of the two pieces of pipe in Vent Pipe Assembly 2 are too long for proper fit up then remove as little material as possible to improve the fit up Keep in mind that the pipes will insert slightly further into the elbows when cement is applied as it acts as a lubricating agent The vertical distance from the bottom of the Condensate U Assembly to the floor that supports the water heat...

Page 20: ...30 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm L Clearance above paved sidewalk or paved driveway located on public property 7 feet 2 13 m 7 feet 2 13 m F Clearance to outside corner 2 feet 60 cm 2 feet 60 cm M Clearance under veranda porch deck...

Page 21: ... pipe lengths discussed above where each elbow is equal to 5 feet 1 5 m of straight pipe 3 vent pipe or 8 feet 2 4 m of straight pipe 4 vent pipe APPROVED VENT INTAKE MATERIAL Approved vent and intake air pipe materials that may be used in the United States PVC pipe materials DWV ASTM D2665 or CSA B181 2 Schedule 40 80 120 ASTM D1785 or CSA B137 3 SDR Series ASTM 2241 or CSA B137 3 CPVC pipe mater...

Page 22: ...s do not use cement to connect the pipe and elbow sections but use a push together gasket seal method Do not attempt to connect Polypropylene with sealant cement All vent connections MUST be secured by the vent manufacturer s joint connector The installer must use a specific vent starter adapter at the flue connection The adapter is supplied by the vent manufacturer to adapt to its vent system In ...

Page 23: ...that the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 6 Make sure the ON OFF switch is in the OFF position and that the outer harness is connected from the blower control box to the connector on the bottom side of the gas valve 7 If the outer har...

Page 24: ...line This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLATIONS FIGURE 18 Cut a length of PVC pipe about 3 5 inches 8 9 cm longer than wall thickness at the opening Glue vent terminal to this section of pipe Slide the wall plate over the pipe to stop agains...

Page 25: ...tallation of a snorkel it is necessary to use two 90 elbows that shall be considered along with the additional vent pipe when calculating maximum equivalent feet of venting INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed the equivalent feet of pipe as listed in Table 1 Provide support for...

Page 26: ... cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4 Make sure the VAA and vent pipe is supported securely to a permanent fixture stud or wall Use standard support straps not supplied with kit that may be found at a local hardware store Failure to pro...

Page 27: ...A and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for Vertical Vent with 3 or 4 inch Pipe Installation of VAA with 3 4 inch Pipe for Horizontal Vent Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths...

Page 28: ... and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC or CPVC surfaces A chemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10 20 by weight virgin PVC m...

Page 29: ...d make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and prepares the PVC or CPVC for the solvent cementing step Move quickly and without hesitation to the cementing procedure while the surfaces are still wet with primer E Application of solvent cement Apply...

Page 30: ...ER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all electric power to the appliance if service is to be performed BEFORE OPERATING ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES 1 STOP Read the safety information above on this labe...

Page 31: ...ic does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing the COOLER button decreases temperature and pressing the HOTTER button increases the temperature Setting water heater temperature at 120 F 49 C Approx mark on temperature setting of gas valve will red...

Page 32: ...ocal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chlorination treatment we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem Do not remove the anode leaving the tank unprotected By doing so...

Page 33: ...ould be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner operation through the Viewport on the Inner Door see Figure 1 The main burner should provide complete combustion of gas ignite rapidly give reasonably quiet operation and cause no excessive flame lifting...

Page 34: ... not have a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALVE OPENING THIS CAN CAUSE PROPERTY DAMAGE SERIOUS INJURY OR DEATH Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized Temperature P...

Page 35: ...oose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances water lines or ground seepage should also be checked To check where threaded portion enters tank insert cotton swab between jacket opening and fitting If cotton is wet follow Draining instructions in th...

Page 36: ... control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the air pressure switch sensing tube is properly connected not kinked or damaged 3 Check continuity of vent temperature limit switch replace switch if contacts remain open under 160ºF 71 C 4 Ensure the ...

Page 37: ...off for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is positioned to provide consistent ignition 6 Check for any cracks in ignitor assembly ceramic insulators replace ignitor assembly if damaged 7 Check resistance of ignitor at room temperature 77ºF 25 C ...

Page 38: ...hin tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent temperature limit switch is opening its contacts at normal operating temperatures during heating cycle replace the vent temperature limit switch 3 Ensure water heater is not over firing 3 1 Check burn...

Page 39: ...39 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES ...

Page 40: ...40 NOTES ...

Page 41: ...41 NOTES ...

Page 42: ...42 NOTES ...

Page 43: ...g gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Improper installation sizing delivery or maintenance Claims related to rust noise smell or taste of water Failure to conduct authorized factory start up if required Alterations to the water heater Non outdoor heaters installed outdoors Damages due to a fa...

Page 44: ...44 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2015 A O Smith Corporation All rights reserved ...

Reviews: