3
External display controller
Normal power under voltage transfer value: 187V
Normal power Over voltage transfer value: 2 3V
5
Reserve power under voltage transfer value: 187V
Reserve power Over voltage transfer value: 2 3V
5
Transfer delay time: 5 sec
Recovery delay time: 5 sec
Generator start delay time : 5 sec
Generator stop delay time: 5 sec
Transfer Mode: Power Grid - Power Grid
Factory default value settings
N
R
OFF
S
High frequency protection value setting, Press
increase, press decrease
11
Hz
.
High frequency protection value setting, Press
increase, press decrease (accuracy around 2%)
11
Hz
.
increase, press decrease
11
12
11
13
11
14
11
15
Generator exerciser mode setting, press to
change the mode. ( 000 OFF ; 001 Start once;
-
-
-
-
-
002 Start daily; 003 Start weekly; 004 Start monthly)
Generator exerciser load mode setting, press to
change the mode. ( 000 Off load ; 001 On load)
-
-
Generator exerciser timer year setting, press to
change the timing of years ( 017 means the year of 2017).
Generator exerciser timer month setting, press to
change the timing of month. ( From 001 to 012)
Generator exerciser timer date setting, press to
change the timing of date (from 001 to 031).
Generator exerciser timer week setting, press to
change the timing of week (000 - Sunday;001-Monday;
002 - Tuesday; ....; 006 - Saturday).
Generator exerciser timer hour setting, press to
change the timing of hour (from 000 to 023);
Generator exerciser timer minute setting, press to
change the timing of minute (from 000 to 059).
Generator exerciser timer second setting, press to
change the timing of second (from 000 to 059).
Generator exerciser time duration hour setting, press to
change the timing of hours (from 000 to max. 500 hours).
Generator exerciser time duration minute setting, press
to change the timing of minute. ( From 000 to 059 min.)
16
17
18
19
20
21
22
Settings menu
Low frequency protection setting, Press increase,
press decrease (accuracy around 2%)
10
Hz
.
N
R
ON
OFF
Password input, press to change position,
press to input the password :888
Normal Power Under voltage transfer value set, Press
increase press decrease
Normal Power over voltage transfer value set, Press
increase, press decrease
Transfer delay time setting, Press increase,
press decrease
Reserve Power Under voltage transfer value setting, Press
increase, press decrease
Reserve Power Over voltage transfer value setting, Press
increase, press decrease
Recovery time delay, Press increase,
press decrease
Generator stop delay time setting, Press
increase, press decrease
Generator Start time delay, Press
increase, press decrease
Transfer Mode setting, press to change
the transfer mode (the last digit: 0 - no source priority;
1 - source # I priority, 2 - source # II priority).
When controller is working, press Set button on the LCD display front panel. Under the setting menu, press " " or " "
button to scrol the setting items. Press " " or " " button to modify item value settings. Press " " button to exit the
setting menu.
Key-press instruction