background image

- -

3

External display controller

Normal power under voltage transfer value: 187V
Normal power Over voltage transfer value: 2 3V

5

Reserve power under voltage transfer value: 187V
Reserve power Over voltage transfer value: 2 3V

5

Transfer delay time: 5 sec
Recovery delay time: 5 sec
Generator start delay time : 5 sec
Generator stop delay time:  5 sec
Transfer Mode: Power Grid - Power Grid

Factory default value settings

N

R

OFF

S

High frequency protection  value setting, Press

increase, press                decrease

11

Hz

.

High frequency protection  value setting, Press

increase, press                decrease (accuracy around 2%)

11

Hz

.

increase, press                decrease

11

12

11

13

11

14

11

15

Generator exerciser mode setting, press                     to
change the mode. ( 000 OFF ; 001 Start once;

-

-

-

-

-

002 Start daily; 003 Start weekly; 004 Start monthly)

Generator exerciser load mode setting, press                   to
change the mode. ( 000 Off load ; 001 On load)

-

-

Generator exerciser timer year setting, press                   to
change the timing of years ( 017 means the year of 2017).

Generator exerciser timer month setting, press                   to
change the timing of month. ( From 001 to 012)

Generator exerciser timer date setting,    press                   to
change the timing of date (from 001 to 031).

Generator exerciser timer week setting,   press                   to
change the timing of week (000 - Sunday;001-Monday;
002 - Tuesday; ....; 006 - Saturday).

Generator exerciser timer hour setting,    press                   to
change the timing of hour (from 000 to 023);

Generator exerciser timer minute setting, press                   to
change the timing of minute (from 000 to 059).

Generator exerciser timer second setting, press                   to
change the timing of second (from 000 to 059).

Generator exerciser time duration hour setting, press                      to
change the timing of hours (from 000 to max. 500 hours).

Generator exerciser time duration minute setting,   press
to change the timing of minute. ( From 000 to 059 min.)

16

17

18

19

20

21

22

Settings menu

Low frequency protection setting, Press          increase,

press            decrease  (accuracy around 2%)

10

Hz

.

N

R

ON

OFF

Password input, press                      to change position,

press                     to input the password :888

Normal Power Under voltage transfer value set, Press

increase press            decrease

Normal  Power over voltage transfer value set, Press

increase,  press            decrease

Transfer delay time setting, Press          increase,
press            decrease

Reserve Power Under voltage transfer value setting, Press

increase, press                decrease

Reserve Power Over voltage transfer value setting, Press

increase, press               decrease

Recovery  time delay, Press          increase,

press           decrease

Generator stop delay time setting, Press

increase, press           decrease

Generator Start time delay, Press

increase, press          decrease

Transfer Mode setting, press                     to change
the transfer mode (the last digit: 0 - no source priority;
1 - source # I  priority, 2 - source # II priority).

When controller is working, press Set button on the LCD display front panel. Under the setting menu, press "         "    or    "            "

button to scrol the setting items. Press "        "   or    "           "   button to modify item value settings. Press "                " button to exit the

setting menu.

Key-press instruction

Summary of Contents for 125A-4P-di

Page 1: ...iary power supply only High density silver alloy contacts providing thousands operating cycles at 100 rated load Bridge type double break design not requiring special SCPD and matching AC 33B requirements Optimized magnetic blow out arc extinquish system allowing to reach 10le capacity Multi mode operation including manual transfer automatic transfer with without autorecovery and generator control...

Page 2: ...Generator start signal activity 4 Fire linkage input activity ATS stops when fire linkage input active 5 Normal main power data indication zone 6 Reserve power data indication zone 7 Setting mode button 8 Auto Manual transfer mode selection button in the work mode and Save Escape button in the setting mode 9 OFF button in the manual control mode and the value decrease button in the setting mode 10...

Page 3: ... 000 to 023 Generator exerciser timer minute setting press to change the timing of minute from 000 to 059 Generator exerciser timer second setting press to change the timing of second from 000 to 059 Generator exerciser time duration hour setting press to change the timing of hours from 000 to max 500 hours Generator exerciser time duration minute setting press to change the timing of minute From ...

Page 4: ...r exerciser timer settings parameters A 12 A 22 are not configured To cancel the exerciser during the generator exerciser duration time change the switch mode to manual and press any button Controller functions Under over voltage detection Controller monitors configured under over voltage values of normal and reserve power supply phases When the under over voltage is detected for one of the power ...

Page 5: ... 103 Normal Power external Indicator outputs Active AC230V 0 5A 101 Indicator common neutral line 102 Normal power indicator signal output 103 Normal power ON signal output 201 203 Reserve power external indicator outputs Active AC230V 0 5A 201 Indicator common neutral line 202 Reserve power indicator signal output 203 Reserve power ON signal output 301 302 Auxiliary power supply 24VDC inputs 15 3...

Page 6: ...er EN55011 Radio frequency radiation Transmit test as per EN55011 Anti interference Test Static Discharge air discharge class 4 contact discharge class 3 as per IEC61000 4 2 Radio frequency electromagnetic field Class 3 as per IEC61000 4 3 and IEC61000 4 6 Fast transient pulse group Class 4 as per IEC61000 4 4 Surge Class 4 as per IEC61000 4 5 Short time voltage drop and voltage off passed Fault C...

Page 7: ...29 70 29 29 29 27 4PRO ATS 250A 4P di 133 66 5 5 35 110 55 127 112 56 127 38 38 41 90 38 42 190 228 58 240 237 400 430 58 58 272 50 30 4PRO ATS 630A 4P di Display controller outline and split mounting dimensions overall dimensions Split mounting dimensions 3 2 1 4 5 6 Accessories RJ 45 Connector User manual Notes Outline Drawing Size ...

Reviews: