Automatic Transfer Switch model:

125A-4P-di

250A-4P-di

630A-4P-di

Poles

Rated working current (A) Ie

Rated working voltage (V) Ue

Rated insulation voltage (V)Ui

Rated impulse withstand voltage (KV) Uimp

Use category

Rated short time withstand current(KA, rms)Icw

Rated short circuit making capacity (KA peak)Icm

Rated limit short circuit current (KA)Iq

Rated control power supply voltage (V) Us

Contact transfer time (s)

Operation cycles

no electricify

with electricify

Total

Outline size (mm) WxDxH

Weight (kg)

Characteristics

N

R

OFF

S

Device controls

Display controls and indicators

1: Operation mode;

2: Setting status;

3: Generator start signal activity;

4: Fire linkage input activity (ATS stops when fire

linkage input active);

5: Normal (main) power data indication zone;

6: Reserve power data indication zone;

7: Setting mode button;

8: Auto/Manual transfer mode selection button (in the

work mode) and Save/Escape button(in the setting

mode);

9: OFF button (in the manual control mode) and the

value decrease button (in the setting mode);

10: Normal power transfer button (in the manual control

mode) and a page up button (in the setting mode);

11: Reserve power transfer button (in the manual

control mode) and a page up button (in the setting

mode);

12. “+” button: the value increase button (in the setting

mode);  the time query menu entrance (click and hold);

start/stop generator test button (in the manual mode);

stop generator exerciser button (during the exerciser

time).

Summary of Contents for 125A-4P-di

Page 1: ...iary power supply only High density silver alloy contacts providing thousands operating cycles at 100 rated load Bridge type double break design not requiring special SCPD and matching AC 33B requirements Optimized magnetic blow out arc extinquish system allowing to reach 10le capacity Multi mode operation including manual transfer automatic transfer with without autorecovery and generator control...

Page 2: ...Generator start signal activity 4 Fire linkage input activity ATS stops when fire linkage input active 5 Normal main power data indication zone 6 Reserve power data indication zone 7 Setting mode button 8 Auto Manual transfer mode selection button in the work mode and Save Escape button in the setting mode 9 OFF button in the manual control mode and the value decrease button in the setting mode 10...

Page 3: ... 000 to 023 Generator exerciser timer minute setting press to change the timing of minute from 000 to 059 Generator exerciser timer second setting press to change the timing of second from 000 to 059 Generator exerciser time duration hour setting press to change the timing of hours from 000 to max 500 hours Generator exerciser time duration minute setting press to change the timing of minute From ...

Page 4: ...r exerciser timer settings parameters A 12 A 22 are not configured To cancel the exerciser during the generator exerciser duration time change the switch mode to manual and press any button Controller functions Under over voltage detection Controller monitors configured under over voltage values of normal and reserve power supply phases When the under over voltage is detected for one of the power ...

Page 5: ... 103 Normal Power external Indicator outputs Active AC230V 0 5A 101 Indicator common neutral line 102 Normal power indicator signal output 103 Normal power ON signal output 201 203 Reserve power external indicator outputs Active AC230V 0 5A 201 Indicator common neutral line 202 Reserve power indicator signal output 203 Reserve power ON signal output 301 302 Auxiliary power supply 24VDC inputs 15 3...

Page 6: ...er EN55011 Radio frequency radiation Transmit test as per EN55011 Anti interference Test Static Discharge air discharge class 4 contact discharge class 3 as per IEC61000 4 2 Radio frequency electromagnetic field Class 3 as per IEC61000 4 3 and IEC61000 4 6 Fast transient pulse group Class 4 as per IEC61000 4 4 Surge Class 4 as per IEC61000 4 5 Short time voltage drop and voltage off passed Fault C...

Page 7: ...29 70 29 29 29 27 4PRO ATS 250A 4P di 133 66 5 5 35 110 55 127 112 56 127 38 38 41 90 38 42 190 228 58 240 237 400 430 58 58 272 50 30 4PRO ATS 630A 4P di Display controller outline and split mounting dimensions overall dimensions Split mounting dimensions 3 2 1 4 5 6 Accessories RJ 45 Connector User manual Notes Outline Drawing Size ...

Reviews: