Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4Evac SW6 / SW6-LITE INSTALLATION and USER
GUIDE V04
Author:
TC
Page 17 of 26
NOTE: Power leads connected to this 24V input must be installed inside the cabinet
of Voice evacuation system.
4E-SW6: 24V DC input
5.4.
Indications
SW6 has 2 bi-colour LED indicators per output. Status is given individually per speaker line.
Additionally general status of booting mode or calibration mode is also displayed on LEDs.
LED indicators show status of each output line, including:
a.
Whether a line is connected to channel A / B or none
b.
Fault status (short / open)
c.
EOL measurement calibration result.
status
which LED's
colour
mode
pattern
1
SW6 booting (no config)
all
blue
sequence
running circular
2
line disabled in config
both
continuous off
3
line not monitored in config
both
orange
simultaneous
flash
4
line under calibration
both
orange
alternative
fast blink
5
line not calibrated
both
orange
alternative
slow blink
6
line short (calibrated)
both
orange
simultaneous
continuous on
7
line open (calibrated)
both
orange
simultaneous
slow blink